3385 fault in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/3385 fault in ABB ACS380 drive

The 3385 fault code in the ABB ACS380 drive indicates an autophasing fault. The drive shuts down when the automated magnetic pole detection routine for permanent magnet or synchronous reluctance motors fails to converge or produces invalid alignment data.

Permanent magnet synchronous motors require precise knowledge of the rotor magnetic pole angle before the inverter can synthesize forward rotating vector torque. During autophasing, the drive applies DC test voltage pulses across terminals U2, V2, W2 to detect magnetic saturation differences. If the motor rotates due to external windmilling, or if motor electrical ratings are incorrect, flux angles cannot be determined. The drive trips on fault 3385 to prevent violent reverse torque or severe overcurrent spikes.

What Causes 3385 in ABB ACS380?

  1. The motor shaft was already rotating or windmilling when the autophasing sequence initiated.
  2. The motor identification run in parameter 99.13 ID run requested was not completed successfully.
  3. Incorrect motor type configured in parameter 99.03 Motor type (e.g., asynchronous induction selected instead of permanent magnet).
  4. Mismatched motor nameplate values entered into parameter group 99 Motor data, especially back-EMF voltage or nominal current.
  5. Excessive external load torque or mechanical holding brake remaining clamped during turning autophasing routines.

Step-by-Step Troubleshooting and Solutions

  1. Confirm that the motor shaft is completely stationary and uncoupled from mechanical windmilling or fluid backflow before issuing a start command.
  2. Check parameter 99.03 Motor type and verify that it correctly reflects your motor technology (such as Permanent magnet motor).
  3. Review all motor nameplate parameters entered in group 99 Motor data; confirm that nominal voltage, nominal current, and nominal frequency match motor ratings.
  4. Re-execute a motor ID run by selecting Standstill or Normal in parameter 99.13 ID run requested.
  5. Examine parameter 21.13 Autophasing mode and test switching between Turning and Standstill modes to suit mechanical brake constraints.

Preventative Maintenance to Avoid 3385 Faults

Ensure mechanical holding brakes release cleanly during commissioning tests and confirm that mechanical backstops prevent reverse rotation on fan applications. Store completed motor parameter profiles via Drive Composer to prevent lost calibration data during field maintenance.

Frequently Asked Questions (FAQs)

What is the meaning of 3385 fault in ABB ACS380 drive?

Fault 3385 indicates that the drive was unable to determine the rotor magnetic pole position during its autophasing routine on a permanent magnet motor.

What are the primary causes of 3385 fault?

Primary causes include a rotating motor shaft at startup, incomplete motor ID runs, incorrect motor type selection in parameter 99.03, and clamped mechanical brakes.

How do I troubleshoot and correct 3385 fault?

Ensure the motor is stationary before starting, verify motor type in parameter 99.03, execute a motor ID run, and test autophasing modes in parameter 21.13.