5681 fault in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/5681 fault in ABB ACS380 drive

The 5681 fault code in the ABB ACS380 drive indicates a power unit (PU) communication error. The drive trips and cuts motor power when data exchange between the main control unit and the power unit experiences severe frame transmission faults or timeouts.

High-speed internal communication links allow the main microprocessor to transmit pulse-width modulation (PWM) firing commands to the power unit while continuously acquiring phase current, intermediate DC bus voltage, and thermal feedback. When persistent cyclic frame errors or checksum mismatches corrupt this data link, real-time current regulation cannot be guaranteed. To prevent uncoordinated gate switching and destructive IGBT shoot-through, the supervisory logic halts firing pulses and latches fault 5681.

What Causes 5681 in ABB ACS380?

  1. Loose, unseated, or mechanically damaged internal ribbon cable connecting the control board to the power stage.
  2. High-frequency electromagnetic noise induced by unshielded motor cables or inadequate bonding to terminal PE.
  3. Incompatible firmware builds running between the drive control unit and the power unit FPGA logic.
  4. Power supply voltage fluctuations or ripple on the internal auxiliary logic power rail.
  5. Physical damage to high-speed communication transceiver chips on either circuit board.

Step-by-Step Troubleshooting and Solutions

  1. Isolate incoming mains voltage from terminals L1, L2, L3, wait 5 minutes for the DC link to discharge, and open the drive cover.
  2. Inspect the internal ribbon cable and board-to-board connectors; unseat, inspect for bent pins, and firmly reseat the interconnects.
  3. Verify 360-degree high-frequency shield clamping on motor power cables at the drive grounding shelf to eliminate severe electrical noise.
  4. Connect via Drive Composer PC tool and check parameter 07.05 Firmware version to ensure internal firmware modules are properly synchronized.
  5. Disconnect field control wiring and reboot the drive; if fault 5681 recurs under no-load idling conditions, the internal hardware requires factory repair.

Preventative Maintenance to Avoid 5681 Faults

Ensure control panels provide adequate shock and vibration isolation when installed near heavy vibrating machinery. Inspect internal ribbon connectors for oxidation or looseness during annual scheduled shutdowns and maintain strict separation between low-voltage signals and power leads.

Frequently Asked Questions (FAQs)

What is the meaning of 5681 fault in ABB ACS380 drive?

Fault 5681 indicates that communication between the drive control unit and the internal power unit has failed due to frame errors or packet loss.

What are the primary causes of 5681 fault?

Primary causes include loose internal board-to-board ribbon cables, severe electromagnetic interference, firmware incompatibilities, and damaged transceiver hardware.

How do I troubleshoot and correct 5681 fault?

Isolate power, reseat the internal ribbon cable connectors, verify motor cable shielding and ground clamps, and inspect firmware versions using Drive Composer.