The 64FF event code in the ABB ACS380 drive indicates an informational fault reset notification. The drive registers this entry when an active fault state is acknowledged and cleared from an external interface or operator panel.
When this code logs into the internal event history, the VFD control unit completes a handshake routine to clear latched safety trips. It does not stop pulse-width modulation (PWM) by itself; rather, it indicates that internal trip registers in the intermediate DC control circuit and gate firing drivers have transitioned from a tripped lockout status back to a ready-to-run state.
What Causes 64FF in ABB ACS380?
- An operator manually pressed the reset key on the integrated control panel or assistant assistant keypad.
- A digital input programmed under parameter
31.11 Fault reset selectionreceived an intentional reset pulse. - A supervisory PLC sent a reset command word via fieldbus protocol over parameter
06.01 Main control wordbit 7. - An active maintenance session using Drive Composer PC tool issued an online fault clear command.
- An automated reset function programmed in parameter group
31 Fault functionsexecuted after an intermittent trip.
Step-by-Step Troubleshooting and Solutions
- Access parameter group
04 Warnings and faultsto review preceding trip logs, specifically parameter04.01 Tripping fault, to diagnose the root issue that preceded the reset. - Inspect digital input terminal mappings such as
DI1throughDI6to verify if noise or unintended signal pulses trigger parameter31.11 Fault reset selection. - Verify PLC communication logs and cyclic fieldbus control bits to ensure continuous reset requests are not masking active motor overload states.
- Confirm that the originating physical fault condition, such as ground leakage or thermal overload, was rectified before releasing the start command on terminals
DI1orDI2. - Review parameter
31.12 Autoreset selectionto ensure auto-reset attempts do not cycle excessively against stalled machinery.
Preventative Maintenance to Avoid 64FF Faults
Maintain clean control wiring connections and apply proper grounding across shielded fieldbus cables. Periodically audit the drive fault logger through Drive Composer to ensure operators or automated PLC scripts are not repeatedly clearing recurring equipment warnings without addressing underlying physical stress.
Frequently Asked Questions (FAQs)
What is the meaning of 64FF fault in ABB ACS380 drive?
Event 64FF is an informational log indicating that an active drive fault condition was successfully acknowledged and cleared through a control interface.
What are the primary causes of 64FF fault?
The primary causes include manual keypad resets, automated PLC fieldbus reset commands, digital input pulses, Drive Composer actions, and auto-reset parameter routines.
How do I troubleshoot and correct 64FF fault?
Check parameter 04.01 to diagnose the actual fault preceding the reset, inspect reset input signals, and confirm fieldbus control word health.