7191 fault in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/7191 fault in ABB ACS380 drive

Fault 7191 in the ABB ACS380 drive indicates a Brake Chopper (BC) Short Circuit. The drive protection circuitry halts inverter modulation immediately upon sensing an overcurrent condition or silicon breakdown across the dynamic braking chopper IGBT.

During regenerative motor deceleration, excess kinetic energy charges the intermediate DC bus capacitors, causing bus voltage to rise. The ACS380 internal brake chopper transistor regulates this voltage by pulsing excess current across terminals R+ and R- into an external power resistor. If the external resistor has shorted, if the connected resistance is below the drive minimum allowed value (Rmin), or if the chopper IGBT suffers collector-to-emitter punch-through, a direct short circuit occurs across the intermediate DC link. The drive desaturation sensors clamp gate drive signals within microseconds to prevent power stage destruction and trip on fault 7191.

What Causes 7191 in ABB ACS380?

  1. Direct electrical short circuit or grounded winding within the external dynamic braking resistor assembly.
  2. Brake resistor resistance value is lower than the minimum allowable resistance rating (Rmin) specified for the ACS380 frame size.
  3. Damaged or short-circuited brake chopper IGBT module on the drive internal power circuit board.
  4. Crushed, pinched, or improperly insulated cabling connecting braking terminals R+ and R-.
  5. Conductive metallic dust or foreign objects bridging the dynamic braking terminal block connectors.

Step-by-Step Troubleshooting and Solutions

  1. Isolate input AC power, wait at least five minutes for intermediate DC capacitors to discharge below 50V DC, and disconnect cables from terminals R+ and R-.
  2. Measure the resistance of the external brake resistor using a calibrated digital ohmmeter; verify the value matches the nameplate and exceeds the drive Rmin threshold.
  3. Perform an insulation resistance test at 500V DC between the brake resistor terminals and protective earth (PE); resistance must exceed 10 MΩ.
  4. Using a multimeter in diode test mode, check the internal brake chopper IGBT across terminals R+ and R- to detect semiconductor short circuits.
  5. Inspect parameter group 43 Brake chopper, ensuring parameter 43.06 Brake resistor resistance is programmed with the exact measured ohmic value.

Preventative Maintenance to Avoid 7191 Faults

Inspect dynamic brake resistor enclosures bi-annually for physical thermal damage, broken ceramic insulators, or debris accumulation. Ensure thermal overload switches wired in series with the resistor are integrated into the drive digital interlock circuit to disconnect power before resistors suffer catastrophic burnout.

Frequently Asked Questions (FAQs)

What is the meaning of 7191 fault in ABB ACS380 drive?

The 7191 fault indicates that a short circuit has been detected in the dynamic brake chopper circuit or across the external braking resistor terminals.

What are the primary causes of 7191 fault?

Primary causes include a shorted external brake resistor, resistor resistance below the minimum drive specification, pinched braking cables, and damaged chopper IGBTs.

How do I troubleshoot and correct 7191 fault?

Disconnect braking leads, measure resistor resistance against drive minimum specifications, test for ground faults with a megger, and check the chopper IGBT with a multimeter.