The A6A6 alarm signifies that the AC mains supply voltage category has not been explicitly defined in the ABB ACS380 drive configuration. The drive issues this warning to request supply calibration before normal operation commences.
The drive requires a defined supply voltage range to calibrate its internal DC bus monitoring limits, including overvoltage trip thresholds, undervoltage trip limits, and dynamic braking chopper activation levels. Without this value, the power stage cannot establish valid intermediate circuit protection setpoints, risking capacitor bank degradation or unexpected power unit trip events.
What Causes A6A6 in ABB ACS380?
- Initial commissioning performed without defining the incoming AC grid voltage range.
- Reversion to factory defaults where parameter
95.01 Supply voltagedefaults to an unselected state. - Installing a replacement control card or executing a full firmware re-flash without parameter restoration.
- Mismatched hardware profile loading during automated PLC configuration downloads.
- Incomplete custom macro parameter configuration.
Step-by-Step Troubleshooting and Solutions
- Measure the incoming AC supply line voltage across input terminals
L1, L2, L3with a calibrated true-RMS digital multimeter. - Navigate to parameter
95.01 Supply voltagein the drive control menu. - Select the correct nominal voltage category matching your facility mains (such as
200...240 V,380...415 V, or440...480 V). - Verify that parameter
01.11 DC voltagedisplays a stable value approximately equal to1.35to1.41times the measured AC line-to-line RMS voltage. - Cycle main input power or execute a software reboot via parameter
96.08 Control board bootto latch the new supply category.
Preventative Maintenance to Avoid A6A6 Faults
Document the line supply category in all project engineering drawings. When installing replacement drives, ensure the commissioning checklist includes parameter 95.01 verification before transferring the machine to production.
Frequently Asked Questions (FAQs)
What is the meaning of A6A6 fault in ABB ACS380 drive?
It indicates that the drive has not been assigned an AC incoming supply voltage category, preventing proper DC link threshold calibration.
What are the primary causes of A6A6 fault?
Primary causes are unassigned supply voltage parameters during initial commissioning, factory default resets, and unconfigured control unit replacements.
How do I troubleshoot and correct A6A6 fault?
Measure incoming three-phase AC line voltage and assign the corresponding grid range in parameter 95.01 Supply voltage, then cycle control power.