A6E5 alarm in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/A6E5 alarm in ABB ACS380 drive

The A6E5 alarm indicates an analog input (AI) parametrization conflict in the ABB ACS380 drive. It occurs when the physical hardware switch setting (current or voltage) does not match the software configuration parameters.

The drive analog front-end uses internal input load resistors when configured for current (0/4...20 mA) and high-impedance divider paths when configured for voltage (0/2...10 V). A mismatch between hardware switches and the ADC sampling algorithms impairs speed reference scaling and can lead to process control error loops.

What Causes A6E5 in ABB ACS380?

  1. Physical hardware DIP switch or jumper set to current (mA) while parameter 12.15 is set to voltage (V), or vice-versa.
  2. Parameter 12.25 AI2 unit selection configured incompatibly with the physical hardware selection for AI2.
  3. Changing physical hardware switch positions while the drive is powered without executing a control board reboot.
  4. Restoring parameter backup files originating from a drive with different hardware input configurations.
  5. Defective hardware detection circuitry on the analog terminal block.

Step-by-Step Troubleshooting and Solutions

  1. Check the drive event log for the specific auxiliary code to identify whether AI1 or AI2 contains the conflicting configuration.
  2. Inspect the physical hardware switch on the ACS380 control card to verify if it is positioned for voltage (V) or current (mA).
  3. Align the software setting: adjust parameter 12.15 AI1 unit selection or parameter 12.25 AI2 unit selection to match the hardware position.
  4. Execute a control board reboot via parameter 96.08 Control board boot or completely cycle line power to register hardware switch changes.
  5. Measure reference signal levels across terminals AI1/AI2 and AGND using a multimeter to verify correct input scaling.

Preventative Maintenance to Avoid A6E5 Faults

Always verify both hardware switch positions and parameter configurations prior to commissioning analog loops. Clearly label the analog input signal type inside the control enclosure to prevent wiring or configuration errors during field maintenance.

Frequently Asked Questions (FAQs)

What is the meaning of A6E5 fault in ABB ACS380 drive?

It is an analog input warning showing that the physical current or voltage hardware switch disagrees with the software parameters.

What are the primary causes of A6E5 fault?

The primary causes are mismatched settings between hardware switches and parameters 12.15/12.25, or failing to reboot after altering physical switches.

How do I troubleshoot and correct A6E5 fault?

Identify the conflicting input via the event log, match parameter 12.15 or 12.25 with the hardware switch, and reboot the control board.