A79C alarm in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/A79C alarm in ABB ACS380 drive

The A79C warning code in the ABB ACS380 drive indicates brake chopper (BC) IGBT excess temperature. The drive activates this alarm when internal thermal sensors register excessive heat on the dynamic braking semiconductor switch.

The internal brake chopper IGBT connects directly across the positive and negative rails of the intermediate DC link bus. During aggressive deceleration, the chopper cycles at high frequencies to divert energy into terminals R+ and R-. If the resistor has too low an ohmic value or cooling airflow is restricted, peak collector current creates intense thermal dissipation in the silicon die, risking punch-through breakdown and shorting the DC bus.

What Causes A79C in ABB ACS380?

  1. Braking resistor connected to terminals R+ and R- having an ohmic resistance below the drive minimum allowed value.
  2. Cooling fan failure or clogged heatsink channels impeding airflow across the power module.
  3. Excessive cabinet ambient temperature operating higher than the drive rated 50 °C limit.
  4. High AC incoming line voltage driving constant DC bus elevation and excessive chopper firing duty.
  5. Repetitive high-inertia braking cycles occurring without sufficient dwell cooling intervals.

Step-by-Step Troubleshooting and Solutions

  1. Stop the drive, disconnect mains power, and measure the resistance between terminals R+ and R- using a digital multimeter to ensure it meets or exceeds the minimum specified resistance in the hardware manual.
  2. Check the drive cooling fan for rotation, cleaning off dust accumulations or replacing the fan if parameter 05.04 Fan on-time counter indicates end of service life.
  3. Measure the incoming line voltage on terminals L1, L2, L3; excessive AC mains voltage causes higher DC bus levels that force prolonged chopper conduction.
  4. Review braking duty cycles and increase the deceleration ramp in parameter 23.13 Deceleration time 1.
  5. Inspect control cabinet ventilation fans, heat exchangers, and air filter mats to reduce internal enclosure temperatures.

Preventative Maintenance to Avoid A79C Faults

Perform quarterly thermal imaging audits across the VFD heatsink and dynamic braking cabling connections. Inspect cooling fans for bearing noise and clear dust clogs from enclosure grilles to ensure consistent airflow across the internal chopper power module.

Frequently Asked Questions (FAQs)

What is the meaning of A79C fault in ABB ACS380 drive?

Alarm A79C warns that the internal dynamic brake chopper IGBT transistor has exceeded its factory thermal warning threshold.

What are the primary causes of A79C fault?

Primary causes include using a brake resistor with resistance below the allowable minimum, internal fan failures, high ambient temperatures, and excessive braking duty.

How do I troubleshoot and correct A79C fault?

Allow the chopper to cool, verify that resistor resistance exceeds the minimum allowed rating, verify cooling fan operation, and verify input AC voltage levels.