A985 alarm in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/A985 alarm in ABB ACS380 drive

The A985 alarm signifies that external supervisory event channel 5 has been triggered on the ABB ACS380 drive. It indicates that an external safety sensor, interlock, or auxiliary apparatus linked to event 5 has signaled a fault condition.

The ACS380 utilizes programmable external monitoring channels to maintain overarching process coordination. When external event 5 goes active, the drive registers the abnormal condition via software parameters while keeping PWM modulation and the intermediate DC link active, providing a non-tripping supervisory alert unless configured for immediate hardware shutdown.

What Causes A985 in ABB ACS380?

  1. Tripping or failure of external hardware device 5 (such as an external cooling fan flow switch, cabinet door switch, or duct damper contact).
  2. Accidental disconnection, wire break, or corrosion on the digital input terminal assigned to event 5.
  3. Parameter configuration error in parameter 31.09 External event 5 source pointing to an incorrect input channel.
  4. Mismatched trip definition configured in parameter 31.10 External event 5 type (e.g., configured as Fault or Warning when contact states invert).
  5. Transient electrical noise spikes coupling onto unshielded long-distance digital input conductors.

Step-by-Step Troubleshooting and Solutions

  1. Check parameter 31.09 External event 5 source to determine the exact hardware terminal or communication bit assigned to this function.
  2. Examine parameter 31.10 External event 5 type and ensure the assigned action (Warning or Fault) aligns with system engineering design.
  3. Measure live potential at the mapped terminal with a DC voltmeter to ensure a steady 24V DC signal exists across the digital input and common ground DGND.
  4. Test the external auxiliary sensor or contactor auxiliary contact directly with a continuity meter to verify positive physical closure.
  5. Perform an insulation resistance test at 500V DC across motor phases U2, V2, W2 and earth to rule out grounding arc noise inducing false trip signals into digital I/O.

Preventative Maintenance to Avoid A985 Faults

Periodically clean and lubricate external mechanical limit switches and interlocks. Verify the physical tightness of terminal strip connections across auxiliary safety circuits, and ensure control cable shields are properly grounded at the drive cable entry plate.

Frequently Asked Questions (FAQs)

What is the meaning of A985 fault in ABB ACS380 drive?

It is an external supervisory warning indicating that external device 5 has opened or closed in violation of the programmed monitoring parameters.

What are the primary causes of A985 fault?

Common causes include external interlock contact opening, broken field wiring, improper terminal assignment in parameter 31.09, and electrical noise.

How do I troubleshoot and correct A985 fault?

Check the mapped digital input voltage, inspect the physical interlock device, review parameters 31.09 and 31.10, and secure all wiring connections.