AF90 alarm in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/AF90 alarm in ABB ACS380 drive

The AF90 alarm indicates that the speed controller autotuning routine has been interrupted or failed to complete successfully on the ABB ACS380 drive. The drive generates this advisory warning along with an auxiliary code specifying the exact mechanical or electrical tuning failure.

The speed controller autotune calculates mechanical system inertia, proportional gain (Kp), and integration time (Ti) by injecting dynamic torque pulses into the motor while measuring velocity response. When interrupted, the drive stops modulating test pulses across the IGBT inverter bridge, preventing erroneous gain calculations that could cause closed-loop torque oscillations or current saturation.

What Causes AF90 in ABB ACS380?

  1. Auxiliary code 0000: The autotune sequence was aborted prematurely by a manual stop command, enable loss, or external fault.
  2. Auxiliary code 0001: The drive was started without fulfilling autotune prerequisites (e.g., Safe Torque Off active or limits too restrictive).
  3. Auxiliary code 0002: The required torque reference could not be attained before the motor hit maximum speed limits.
  4. Auxiliary codes 0003, 0004, or 0005: The motor failed to accelerate or decelerate within autotune torque boundaries due to excessive load friction or high load inertia.
  5. Auxiliary code 0006: The microprocessor failed to save calculated gains to non-volatile memory.

Step-by-Step Troubleshooting and Solutions

  1. Check the drive fault log and record the auxiliary code in the XXXX YYYY format to identify the exact cause from YYYY.
  2. If code 0002 or 0005 appears, decrease the torque step or decrease the speed step in parameter group 25 Speed control.
  3. If code 0003 or 0004 appears, increase the torque step or decrease the speed step in parameter group 25 to provide sufficient acceleration torque.
  4. For code 0006, reboot the control board by cycling main power or triggering parameter 96.08 Control board boot, then repeat autotuning.
  5. Disconnect motor terminals T1, T2, T3 and execute an insulation megger test at 500V DC to ensure mechanical bind or ground leakage is not retarding rotor movement.

Preventative Maintenance to Avoid AF90 Faults

Ensure mechanical couplings, gearboxes, and driven machinery rotate smoothly without binding before running speed autotuning. Always uncouple high-friction or high-backlash mechanical loads during baseline motor tuning routines whenever possible.

Frequently Asked Questions (FAQs)

What is the meaning of AF90 fault in ABB ACS380 drive?

It is an autotuning warning indicating that the automatic speed controller tuning procedure was interrupted or could not identify load inertia.

What are the primary causes of AF90 fault?

Primary causes include stopping the drive during autotuning, mechanical load friction, insufficient acceleration torque steps, and parameter write failures.

How do I troubleshoot and correct AF90 fault?

Read the auxiliary code, adjust torque or speed step parameters in group 25 according to the error code, and restart the autotune routine.