The AF90 alarm indicates that the speed controller autotuning routine has been interrupted or failed to complete successfully on the ABB ACS380 drive. The drive generates this advisory warning along with an auxiliary code specifying the exact mechanical or electrical tuning failure.
The speed controller autotune calculates mechanical system inertia, proportional gain (Kp), and integration time (Ti) by injecting dynamic torque pulses into the motor while measuring velocity response. When interrupted, the drive stops modulating test pulses across the IGBT inverter bridge, preventing erroneous gain calculations that could cause closed-loop torque oscillations or current saturation.
What Causes AF90 in ABB ACS380?
- Auxiliary code
0000: The autotune sequence was aborted prematurely by a manual stop command, enable loss, or external fault. - Auxiliary code
0001: The drive was started without fulfilling autotune prerequisites (e.g., Safe Torque Off active or limits too restrictive). - Auxiliary code
0002: The required torque reference could not be attained before the motor hit maximum speed limits. - Auxiliary codes
0003,0004, or0005: The motor failed to accelerate or decelerate within autotune torque boundaries due to excessive load friction or high load inertia. - Auxiliary code
0006: The microprocessor failed to save calculated gains to non-volatile memory.
Step-by-Step Troubleshooting and Solutions
- Check the drive fault log and record the auxiliary code in the
XXXX YYYYformat to identify the exact cause fromYYYY. - If code
0002or0005appears, decrease the torque step or decrease the speed step in parameter group25 Speed control. - If code
0003or0004appears, increase the torque step or decrease the speed step in parameter group25to provide sufficient acceleration torque. - For code
0006, reboot the control board by cycling main power or triggering parameter96.08 Control board boot, then repeat autotuning. - Disconnect motor terminals
T1, T2, T3and execute an insulation megger test at500V DCto ensure mechanical bind or ground leakage is not retarding rotor movement.
Preventative Maintenance to Avoid AF90 Faults
Ensure mechanical couplings, gearboxes, and driven machinery rotate smoothly without binding before running speed autotuning. Always uncouple high-friction or high-backlash mechanical loads during baseline motor tuning routines whenever possible.
Frequently Asked Questions (FAQs)
What is the meaning of AF90 fault in ABB ACS380 drive?
It is an autotuning warning indicating that the automatic speed controller tuning procedure was interrupted or could not identify load inertia.
What are the primary causes of AF90 fault?
Primary causes include stopping the drive during autotuning, mechanical load friction, insufficient acceleration torque steps, and parameter write failures.
How do I troubleshoot and correct AF90 fault?
Read the auxiliary code, adjust torque or speed step parameters in group 25 according to the error code, and restart the autotune routine.