The AFED warning code in the ABB ACS380 drive indicates an Enable to Rotate timeout. The drive raises this alert when a valid start command is received, but the external run permissive signal assigned in parameter 20.22 Enable to rotate has not transitioned to active within 240 seconds.
The “enable to rotate” function serves as an operational safety interlock used in machinery like conveyors, mixers, and draw works. While the drive awaits this permissive signal, the intermediate DC link bus remains fully charged, but gate driver firing pulses to the output IGBTs are inhibited. If 240 seconds elapse without permissive verification, the drive alerts operators with warning AFED to avoid indefinitely standing with active run commands.
What Causes AFED in ABB ACS380?
- The run permissive signal mapped to parameter
20.22 Enable to rotatewas not switched on within the 240-second timeout window. - Misconfigured source selection in parameter
20.22 Enable to rotateassigning an incorrect digital input (e.g.,DI3instead ofDI2). - Open external interlock contact such as a conveyor pull-cord switch, lubrication pressure switch, or downstream process permissive.
- Broken control wiring or loose screw terminals on the assigned digital input terminal.
- PLC sequence error failing to assert the corresponding fieldbus control bit prior to issuing a drive run command.
Step-by-Step Troubleshooting and Solutions
- Review parameter
20.22 Enable to rotateto identify the exact digital input, fieldbus bit, or logic pointer designated as the rotation permissive. - Verify the real-time status of the assigned digital input in parameter
05.12 Digital inputs statususing the control panel or Drive Composer. - Inspect external field safety devices, flow switches, and guard interlocks to ensure mechanical permissive conditions are closed.
- Measure DC voltage across the assigned digital input terminal and
+24Vcommon to verify signal level transitions when the interlock closes. - If the rotation permissive function is not required by your machine safety logic, change parameter
20.22 Enable to rotatetoNot used.
Preventative Maintenance to Avoid AFED Faults
Routinely inspect and cycle field interlock switches and emergency trip wires to prevent contact oxidation. Verify PLC sequence timing during annual commissioning audits to ensure interlocks consistently precede start commands by sufficient margins.
Frequently Asked Questions (FAQs)
What is the meaning of AFED fault in ABB ACS380 drive?
Alarm AFED indicates that the drive received a start command, but the rotation permissive signal defined in parameter 20.22 was not energized within 240 seconds.
What are the primary causes of AFED fault?
Top causes include open process interlocks, unasserted digital inputs, broken field wiring, incorrect parameter 20.22 configuration, and PLC sequencing faults.
How do I troubleshoot and correct AFED fault?
Check parameter 20.22 to verify the signal source, confirm input voltage on the assigned terminal, close external field interlocks, or set the parameter to not used.