AFF6 alarm in ABB ACS380 drive

Home/ABB/ABB ACS380 drive/AFF6 alarm in ABB ACS380 drive

The AFF6 warning code in the ABB ACS380 drive denotes an informational identification run notification. The drive asserts this warning to notify personnel that a motor ID run routine will execute upon the very next start command.

During a motor identification run, the drive control processor overrides normal process speed references to perform automated electrical modeling. By applying high-frequency test patterns and DC excitation through the inverter IGBT bridge into terminals U2, V2, W2, the drive calculates stator resistance, leakage inductance, and flux characteristics. Warning AFF6 informs operators that standard process modulation is temporarily suspended in favor of diagnostic calibration.

What Causes AFF6 in ABB ACS380?

  1. An ID run mode (such as Normal, Reduced, or Standstill) was selected in parameter 99.13 ID run requested.
  2. Initial motor commissioning setup initiated via the control panel setup assistant.
  3. Motor parameter modification in parameter group 99 Motor data requiring parameter model recalculation.
  4. Motor control mode switched to vector control in parameter 99.04 Motor control mode without a completed calibration.
  5. Commissioning script initiated through the Drive Composer PC tool commissioning wizard.

Step-by-Step Troubleshooting and Solutions

  1. Confirm that the motor is mechanically decoupled from driven machinery if a rotating ID run (such as Normal) is selected in parameter 99.13 ID run requested.
  2. If mechanical decoupling is impossible, change parameter 99.13 ID run requested to Standstill to perform calibration without rotating the motor shaft.
  3. Verify that motor nameplate values in parameter group 99 Motor data (specifically current, voltage, frequency, and speed) are accurately entered prior to initiating the run.
  4. Issue a run command via the control panel or field inputs to allow the motor ID routine to complete; warning AFF6 clears automatically upon successful completion.
  5. If the ID run was requested unintentionally, set parameter 99.13 ID run requested to None to cancel the pending calibration.

Preventative Maintenance to Avoid AFF6 Faults

Always execute motor ID runs during initial commissioning or whenever replacing motor units to ensure high motor efficiency and torque accuracy. Record completed motor equivalent circuit parameters to eliminate the need for redundant identification runs in production.

Frequently Asked Questions (FAQs)

What is the meaning of AFF6 fault in ABB ACS380 drive?

Alarm AFF6 is an informational notification indicating that a motor identification run has been requested and will execute upon the next start command.

What are the primary causes of AFF6 fault?

Primary causes include selecting an ID run in parameter 99.13, modifying motor nameplate parameters, or running the initial drive commissioning assistant.

How do I troubleshoot and correct AFF6 fault?

Give the drive a start command to allow the ID run to finish and automatically clear the code, or set parameter 99.13 back to none to cancel.