A2007 AI2 LOSS alarm in ABB ACS550 drive

Home/ABB/ABB ACS550 drive/A2007 AI2 LOSS alarm in ABB ACS550 drive

The A2007 AI2 LOSS alarm indicates that the analog input 2 signal has fallen below the minimum supervision threshold configured in parameter 3022 AI2 FAULT LIMIT. The drive warns the operator while maintaining defined fail-safe speed reference settings.

Analog input 2 (AI2) is frequently assigned to process PID feedback loops or secondary speed trimming references. When a 4-20mA transducer on AI2 experiences a cable severance, power loss, or sensor failure, the measured signal collapses below 20% of nominal span. The microprocessor evaluates this drop against the setting in parameter 3022. Rather than immediately interrupting power to the motor, the drive initiates an alarm and executes the protective fallback assigned in parameter 3001 AI (such as holding last speed or selecting constant speed 7) to keep pump or fan processes stable.

What Causes A2007 in ABB ACS550?

  1. Broken signal wire or high-resistance terminal connection at terminal 5 (AI2) or 6 (AGND).
  2. Failure of an external process transmitter (e.g., pressure, level, or flow sensor).
  3. DIP switch J2 positioned incorrectly for the incoming signal format (voltage vs. current).
  4. Supervisory limit in parameter 3022 AI2 FAULT LIMIT configured higher than actual incoming process minimum.
  5. External transducer 24V loop power supply tripped or disconnected.

Step-by-Step Troubleshooting and Solutions

  1. Measure loop signal on terminal block X1: Check voltage or current across terminals 5 (AI2) and 6 (AGND) with a calibrated true-RMS meter.
  2. Verify transmitter power: Check external 24V DC loop supplies or measure terminal 10 (+24V) on the drive control board to ensure excitation voltage is healthy.
  3. Check hardware switch configuration: Inspect DIP switch J2 on the OMIO board to confirm whether it is set to Current (ON/mA) or Voltage (OFF/V).
  4. Review fault limit parameters: Access parameter 3022 AI2 FAULT LIMIT and calibrate the percentage threshold to match your transmitter's live-zero range (e.g., 20.0% for 4mA).
  5. Verify fail-safe strategy: Review parameter 3001 AI to confirm how the drive should respond during signal loss conditions.

Preventative Maintenance to Avoid A2007 Faults

Conduct routine insulation resistance tests on control signal cables, verify sensor calibration twice yearly, and ensure analog shields are properly bonded to the chassis grounding clamp to eliminate noise-induced sensor dropouts.

Frequently Asked Questions (FAQs)

What is the meaning of A2007 alarm in ABB ACS550 drive?

It means the analog input signal wired to terminal AI2 has fallen below the safety limit programmed in parameter thirty-twenty-two.

What are the primary causes of A2007 alarm?

The primary causes are open-circuit sensor wiring, a failed process transmitter, misconfigured J2 hardware DIP switches, or an incorrectly scaled fault limit parameter.

How do I troubleshoot and correct A2007 alarm?

Verify loop current at terminal five, check sensor supply power, inspect the position of DIP switch J2, and adjust parameter thirty-twenty-two to match your sensor range.