The A2015 PFC I LOCK alarm in the ABB ACS550 drive indicates that pump and fan control (PFC) interlocks are active and inhibiting motor startup. The drive prevents motor staging and speed modulation because an open interlock signal indicates that the designated pump or auxiliary motor is offline or in an unready state.
Parameter 8120 INTERLOCKS enables feedback monitoring of auxiliary disconnect switches or motor circuit protector auxiliary contacts via digital inputs (e.g., DI1 through DI6). If autochange is enabled and all motor interlocks are open, no motor can be started. If autochange is disabled and the interlock for the speed-regulated VFD motor is missing, inverter modulation is inhibited. The drive’s internal sequencing state machine halts gate pulse triggering to avoid running deadheaded pumps or commanding unpowered contactors into closed circuits.
What Causes A2015 in ABB ACS550?
- Digital input assigned as a PFC interlock is in an open-circuit state due to a tripped motor starter or open disconnect switch.
- Parameter
8120 INTERLOCKSenabled without physical interlock wiring connected to digital input terminals. - Broken feedback wiring or loose terminal screw connections on terminals
DI1throughDI6. - An auxiliary contact block on a motor circuit protector or contactor failing mechanically to close.
- Inadvertently configuring high interlock counts in parameter
8120exceeding the actual physical contactor switches installed.
Step-by-Step Troubleshooting and Solutions
- Inspect parameter
8120 INTERLOCKSto identify how many interlock digital inputs are assigned and whether they match installed hardware. - Monitor parameter
0111 DI 1-6 STATUSon the control panel to see which specific interlock digital input is open. - Measure
24 V DCcontrol voltages across the relevant digital input terminal (e.g.,DI3,DI4) and ground to verify signal presence. - Verify that all manual motor circuit protectors, overload relays, and local disconnect switches are fully closed.
- If interlock verification is not required for the system, disable the function by setting parameter
8120to0 [NOT SEL].
Preventative Maintenance to Avoid A2015 Faults
Regularly inspect auxiliary microswitches on manual disconnect handles, tighten control wiring screws in terminal blocks, test auxiliary contact continuity during annual shutdowns, and clean moisture or dust from external junction enclosures.
Frequently Asked Questions (FAQs)
What is the meaning of A2015 alarm in ABB ACS550 drive?
The A2015 PFC I LOCK alarm indicates that active pump and fan control interlocks are open, preventing the drive from starting the speed-regulated motor.
What are the primary causes of A2015 alarm?
Primary causes include open auxiliary contacts on motor disconnects, broken interlock control wiring, tripped overload protectors, or misconfigured group 81 parameters.
How do I troubleshoot and correct A2015 alarm?
Check digital input status in parameter 0111, verify that motor disconnects are closed, measure 24V DC at the interlock terminals, and review parameter 8120.