A2022 START ENABLE 2 MISSING alarm in ABB ACS550 drive

Home/ABB/ABB ACS550 drive/A2022 START ENABLE 2 MISSING alarm in ABB ACS550 drive

The A2022 alarm indicates that the secondary Start Enable supervisory signal configured in parameter 1609 is missing. The inverter halts gate pulse initiation to prevent starting until secondary safety and process conditions are met.

Parameter 1609 START ENABLE 2 defines an independent secondary hardware or software permissive loop. This channel is typically wired to secondary equipment safeguards such as chilled-water flow verification switches, vibration trip monitors, or auxiliary cooling fan contactors. When the drive receives a run command while this secondary permissive remains de-energized, modulation of the intermediate DC voltage across the power semiconductors is blocked, and alarm A2022 is asserted until the circuit closes.

What Causes A2022 in ABB ACS550?

  1. An open contact on a secondary safety device or flow switch wired to the terminal mapped in parameter 1609 START ENABLE 2.
  2. Broken control conductors or loose screw terminals on the digital input block X1.
  3. Setting parameter 1609 START ENABLE 2 to an active input selection when no physical permissive loop exists.
  4. Power loss on the external 24 V DC auxiliary instrument power supply loop feeding permissive switches.
  5. Supervisory PLC or building management network failing to set the secondary enable bit in parameter 0301 FB CMD WORD 1.

Step-by-Step Troubleshooting and Solutions

  1. Check the assigned input selection in parameter 1609 START ENABLE 2 (e.g., DI1 through DI6 or COMM).
  2. Measure DC voltage across the assigned digital input terminal and common DCOM using a multimeter; confirm that +24 V DC is present when the circuit is healthy.
  3. Trace field wiring to auxiliary flow switches, vibration switches, or secondary cooling fans to verify contact continuity.
  4. If secondary start verification is not needed in the current installation, set parameter 1609 START ENABLE 2 to 0 (NOT SEL).
  5. Verify insulation resistance on connected motor leads U2, V2, W2 using a 1000 V DC insulation tester to confirm motor circuit integrity before clearing the alarm.

Preventative Maintenance to Avoid A2022 Alarms

Implement annual continuity and contact resistance testing on external secondary permissive switches. Ensure all field interlock cabling features braided shields grounded at the enclosure bulkhead to prevent false dropouts caused by high-frequency electrical transients.

Frequently Asked Questions (FAQs)

What is the meaning of A2022 alarm in ABB ACS550 drive?

It indicates that the secondary Start Enable permissive signal assigned in parameter 1609 is missing while a drive run command is present.

What are the primary causes of A2022 alarm?

Leading causes include an open secondary flow or vibration switch, disconnected digital input wires, missing auxiliary 24V loop power, or improper parameter configuration.

How do I troubleshoot and correct A2022 alarm?

Check parameter 1609, verify 24 V DC at the designated digital input terminal, resolve external field switch trips, or set parameter 1609 to NOT SEL.