A2028 START DELAY alarm in ABB ACS550 drive

Home/ABB/ABB ACS550 drive/A2028 START DELAY alarm in ABB ACS550 drive

The A2028 START DELAY alarm on the ABB ACS550 drive indicates that an active start command has been received and the drive is currently executing a pre-programmed start delay timer. The drive holds inverter modulation and keeps the motor at zero speed until the configured countdown completes.

Industrial applications frequently require auxiliary preparations before a motor begins rotational acceleration—such as sounding pre-start warning horns, opening motorized damper valves, or establishing lube oil lubrication pressure. The ACS550 facilitates this sequence through parameter 2113 START DELAY. When a run command is asserted via digital input terminals DI1 through DI6 or serial communication, the microprocessor starts internal timer countdown and displays A2028. Inverter IGBT firing pulses remain inhibited until the timer reaches zero, after which normal acceleration begins.

What Causes A2028 in ABB ACS550?

  1. Parameter 2113 START DELAY is configured with a non-zero time value (ranging from 0.0 s to 60.0 s).
  2. A valid start command has been triggered via digital input, control panel, or serial fieldbus network.
  3. Auxiliary pre-start automation logic (such as an oil pump interlock or cabinet purge) delaying the final run sequence.
  4. Pre-magnetization or DC braking functions configured under parameter group 21 START/STOP holding the shaft.
  5. Operator mistaking a programmed process delay countdown for a drive hardware fault.

Step-by-Step Troubleshooting and Solutions

  1. Review parameter 2113 START DELAY on the control panel to check the configured time value; set it to 0.0 s if immediate start is required.
  2. Check auxiliary relay outputs configured in parameter group 14 RELAY OUTPUTS (e.g., parameter 1401 RELAY OUTPUT 1) to verify pre-start devices operate correctly.
  3. Observe the control panel display; verify that the motor begins accelerating normally once the start delay countdown expires.
  4. Measure DC voltage between the assigned digital start terminal (such as DI1) and X1:11 to ensure the start signal remains stable throughout the delay.
  5. Inspect parameter group 21 START/STOP to confirm that parameters like 2101 START FUNCTION and 2102 STOP FUNCTION match application design.

Preventative Maintenance to Avoid A2028 Alarms

Clearly document intentional start delay parameters in standard operating procedures so plant operators recognize normal sequencing, and periodically verify pre-start safety horn and damper interlocks.

Frequently Asked Questions (FAQs)

What is the meaning of A2028 alarm in ABB ACS550 drive?

The A2028 alarm indicates that a start command was received and the drive is currently executing a programmed start delay countdown.

What are the primary causes of A2028 alarm?

The primary cause is an active non-zero time value programmed in parameter 2113 along with an active motor start command.

How do I troubleshoot and correct A2028 alarm?

Allow the delay timer to elapse or adjust parameter 2113 start delay to zero seconds if an immediate start is desired.