A5013 alarm in ABB ACS550 drive

Home/ABB/ABB ACS550 drive/A5013 alarm in ABB ACS550 drive

The A5013 alarm indicates that control panel starting is disabled because an active start inhibit, emergency stop, or 3-wire stop command is asserted on the drive hardware circuits. The drive inhibits semiconductor gating to protect personnel and mechanical assets.

The ACS550 integrates comprehensive hardware interlock logic into its central processing core. If a field circuit wired to an emergency stop input (governed by parameter 2109 EMERG STOP SEL) or Run Enable input (parameter 1601 RUN ENABLE) is opened, or if 3-wire pulse stop logic requires initialization, start inhibit mode activates. Even when transferred to Local (LOC) mode, pressing the green Start key fails to initiate PWM switching. The inverter bridge stays in high-impedance mode while intermediate DC bus voltage remains safely disconnected from motor output terminals.

What Causes A5013 in ABB ACS550?

  1. Active emergency stop command asserted via digital inputs mapped under parameter 2109 EMERG STOP SEL.
  2. Run Enable signal missing at terminal block X1 as dictated by parameter 1601 RUN ENABLE.
  3. Active stop interlock asserted on 3-wire control macros configured in parameter 1001 EXT1 COMMANDS.
  4. Parameter 2108 START INHIBIT enabled following an automatic fault clearance or power-cycling event.
  5. Broken, disconnected, or oxidized wiring on safety interlock loop terminals.

Step-by-Step Troubleshooting and Solutions

  1. Inspect field emergency stop circuits: Check external E-stop pushbuttons, pull cords, and safety relays; reset all tripped field safety hardware.
  2. Check parameter 2109 EMERG STOP SEL: Identify the assigned digital input (e.g., DI4 or DI5) and measure DC voltage across the terminal and GND with a multimeter (must read 24V DC).
  3. Verify 3-wire pulse control: If using a 3-wire macro, confirm that the normally closed stop circuit on terminal DI2 is intact and delivering a constant 24V DC signal.
  4. Inspect Run Enable input: Access parameter 1601 RUN ENABLE; if enabled, verify that terminal DI1 or the configured input is receiving a continuous run permissory signal.
  5. Inspect parameter 2108 START INHIBIT: If set to 1 (ON), cycle the start command after resetting faults to disengage the start prevention circuit.

Preventative Maintenance to Avoid A5013 Faults

Perform scheduled functional testing on all emergency stop buttons and interlock circuits, torque digital input terminal connections during preventative audits, and replace aging mechanical safety contacts exhibiting high resistance.

Frequently Asked Questions (FAQs)

What is the meaning of A5013 alarm in ABB ACS550 drive?

It means the motor cannot be started from the control panel because an external emergency stop, run enable, or start inhibit interlock is active.

What are the primary causes of A5013 alarm?

Primary causes are tripped emergency stop circuits, a missing run enable signal, an open three-wire stop circuit, or parameter start inhibit protection.

How do I troubleshoot and correct A5013 alarm?

Reset all physical emergency stop buttons, verify twenty-four volt signals across safety interlock terminals, review parameter twenty-one-zero-nine, and re-attempt starting.