The A5028 INVALID VALUE alarm on the ABB ACS550 drive indicates that an entered parameter value is invalid or does not match any allowed selection within the discrete option list. The drive rejects the command to protect memory integrity and prevent erratic logic execution.
Many parameters in the ACS550 operate on discrete enumerated integer lists—such as selecting control macros, digital input functions, or communication profiles. When a user or supervisory network transmits a value that does not map to a recognized option (for example, configuring an unassigned option integer in parameter 9902 APPLIC MACRO), the internal parameter validation engine rejects the entry. This safeguard ensures that unmapped pointers or corrupted data words cannot overwrite memory tables, protecting inverter gate switching profiles and active control functions.
What Causes A5028 in ABB ACS550?
- Attempting to select a numerical option code that does not exist in the parameter enumeration list.
- Entering an invalid motor control mode selection in parameter
9904 MOTOR CTRL MODE. - Configuring conflicting or incompatible digital input source selections across parameter groups
10 START/STOP/DIRand11 REFERENCE SELECT. - Sending raw integer words from an external PLC over Modbus RTU or Profibus that exceed the valid option count.
- Attempting to write non-zero or unpermitted values to diagnostic or read-only monitoring parameters in group
01 OPERATING DATA.
Step-by-Step Troubleshooting and Solutions
- Examine the target parameter in the ACS550 Firmware Manual to review the exact list of valid enumerated integer options.
- Press the
EXITorCANCELkey on the Assistant Control Panel to discard the invalid entry and revert to the prior setting. - Inspect PLC communication blocks to verify that transmitted control integers match standard ABB drive communication profiles.
- Check parameter
9902 APPLIC MACROto ensure the selected macro matches standard factory configurations (such as1 = ABB STANDARD). - If sending parameters over serial communication, verify word order, byte endianness, and register data types in parameter group
53 EFB PROTOCOL.
Preventative Maintenance to Avoid A5028 Alarms
Always verify valid parameter option lists prior to commissioning automated fieldbus write routines, and maintain validated parameter backups to avoid manual data entry errors.
Frequently Asked Questions (FAQs)
What is the meaning of A5028 alarm in ABB ACS550 drive?
The A5028 alarm signifies that an entered parameter value is invalid and does not correspond to any recognized option in the drive dictionary.
What are the primary causes of A5028 alarm?
Common causes include selecting non-existent discrete option codes, conflicting digital input assignments, and incorrect PLC data registers.
How do I troubleshoot and correct A5028 alarm?
Check the parameter manual for permissible integer selections, exit the invalid edit screen, and align PLC communication word mapping.