F0022 SUPPLY PHASE LOSS fault in ABB ACS550 drive

Home/ABB/ABB ACS550 drive/F0022 SUPPLY PHASE LOSS fault in ABB ACS550 drive

The F0022 SUPPLY PHASE LOSS fault indicates that the intermediate DC bus voltage is oscillating severely due to a missing incoming AC power line phase or a blown mains fuse. The drive trips when intermediate circuit DC ripple exceeds 14% of nominal voltage.

When one input phase drops at terminals U1, V1, W1, the three-phase bridge rectifier degenerates into a single-phase rectifier. Consequently, the intermediate DC bus capacitors must supply excessive continuous discharge currents during motor load demand. This causes severe 100Hz/120Hz voltage ripple across the intermediate capacitor bank. Running under continuous DC ripple accelerates capacitor dielectric breakdown, overheats input diodes, and threatens output IGBT switching stability.

What Causes F0022 in ABB ACS550?

  1. Blown input semiconductor fuse or tripped upstream circuit breaker on one incoming line phase.
  2. Severe input power supply phase voltage imbalance exceeding 3%.
  3. Loose, pitted, or oxidized connections on input supply terminals U1, V1, W1.
  4. Intermediate circuit capacitor bank degradation reducing ripple filtering capability.
  5. Uncalibrated monitoring threshold governed by parameter 3016 SUPPLY PHASE.

Step-by-Step Troubleshooting and Solutions

  1. Measure incoming three-phase line-to-line voltages (U1-V1, V1-W1, W1-U1) under load using a digital multimeter; verify balance within < 2%.
  2. Inspect and continuity-test all upstream line fuses, disconnect switches, and contactor main poles feeding the drive.
  3. Torque all electrical connections on input power terminals U1, V1, W1 to specified factory torque values.
  4. Inspect the parameter setting in 3016 SUPPLY PHASE (options: 0 = FAULT, 1 = LIMIT 1, 2 = LIMIT 2) according to site power quality requirements.
  5. Evaluate intermediate DC bus ripple: Measure AC ripple voltage across UDC+ and UDC-; an AC component exceeding 14% of nominal DC voltage verifies phase loss or dying filter capacitors.

Preventative Maintenance to Avoid F0022 Faults

Avoid line phase loss faults by implementing scheduled thermographic infrared inspections on supply switchgear, balancing factory busbar distributions, and utilizing properly matched input line reactors to suppress upstream phase dips.

Frequently Asked Questions (FAQs)

What is the meaning of F0022 fault in ABB ACS550 drive?

It indicates that one of the three incoming AC mains phases is absent or unbalanced, causing DC bus voltage ripple to surpass the fourteen percent threshold.

What are the primary causes of F0022 fault?

Primary causes are blown incoming line fuses, severe utility phase imbalance, loose terminal connections, or failing DC bus filter capacitors.

How do I troubleshoot and correct F0022 fault?

Test input voltage phase-to-phase under load, inspect upstream fuses, retorque terminal lugs, and evaluate the phase supervision setting in parameter thirty-sixteen.