F1007 PAR FIELDBUS MISSING fault in ABB ACS550 drive

Home/ABB/ABB ACS550 drive/F1007 PAR FIELDBUS MISSING fault in ABB ACS550 drive

The F1007 PAR FIELDBUS MISSING fault in the ABB ACS550 drive indicates that the drive control logic has been configured to receive commands from a fieldbus network, but fieldbus control parameters have not been properly activated. The drive enters a configuration trip state to prevent unattended run operations.

The ACS550 control architecture permits reference, start/stop, and direction commands to be commanded from external fieldbus sources selected in parameter groups 10 START/STOP/DIR, 11 REFERENCE SELECT, or 16 SYSTEM CONTROLS (e.g., setting control source to COMM). If any control word or setpoint references are pointed to fieldbus interfaces while neither the embedded fieldbus (parameter group 53 EFB PROTOCOL) nor a fieldbus adapter option module (parameter group 51 EXT COMM MODULE) is activated, the core supervisor detects missing communications control mappings, disabling PWM output to ensure failsafe operational integrity.

What Causes F1007 in ABB ACS550?

  1. Parameter 1001, 1002, or 1103 set to COMM without activating parameter 9802 COMM PROT SEL.
  2. Setting parameter 9802 COMM PROT SEL to 0 [NOT SEL] while fieldbus control links remain assigned.
  3. Installing a fieldbus option adapter (such as RPBA-01 or RDNA-01) without properly configuring parameter group 51.
  4. Loading an external application macro or parameter backup containing network references into a standalone hardwired drive.
  5. Mismatched communication timeout fault functions triggering configuration inconsistencies across parameter group 30.

Step-by-Step Troubleshooting and Solutions

  1. Navigate to parameter 9802 COMM PROT SEL and select the appropriate protocol (e.g., 1 [STD MODBUS] for embedded RS-485 or 4 [EXT FBA] for adapter modules).
  2. If fieldbus control is not intended, inspect parameters 1001 EXT1 COMMANDS, 1002 EXT2 COMMANDS, and 1103 REF1 SELECT, changing any COMM settings to local DI or AI terminals.
  3. When using an external fieldbus adapter module in slot 1, configure parameter group 51 EXT COMM MODULE and refresh settings via parameter 5127 FBA PAR REFRESH.
  4. When using the embedded Modbus interface, verify station address and baud rate in parameter group 53 EFB PROTOCOL.
  5. Cycle control power or press the RESET button to clear the fault once communication mapping consistency is restored.

Preventative Maintenance to Avoid F1007 Faults

Standardize PLC drive communication templates across automation facilities, verify all parameter assignments before cutting over from hardwired commissioning to serial communication, and maintain detailed I/O tables for every field installation.

Frequently Asked Questions (FAQs)

What is the meaning of F1007 fault in ABB ACS550 drive?

The F1007 PAR FIELDBUS MISSING code signifies that the drive is configured to accept fieldbus control commands without an active fieldbus protocol selected.

What are the primary causes of F1007 fault?

This issue occurs when parameters point to network control while parameter 9802 is set to NOT SEL, or when fieldbus adapter options are unconfigured.

How do I troubleshoot and correct F1007 fault?

Activate the communication protocol in parameter 9802, reassign control references back to local terminals if running standalone, and refresh adapter parameters.