The F1013 fault flags a mathematical mismatch between the total number of PFC motors and the relay allocation matrix required for system operation. The drive stops pulse modulation immediately to protect line contactors from overlapping switching states.
Parameter 8127 MOTORS defines the total fleet of motors controlled by the system (the variable speed lead motor plus all direct-on-line lag motors). When auto-change is engaged via parameter 8118 AUTOCHNG INTERV, every pump in the fleet must be switchable between VFD modulation and line power. If the motor count configured in 8127 does not align precisely with the assigned relays in group 14 RELAY OUTPUTS and auto-change rules, the internal sequencing logic trips out on F1013 to eliminate the risk of short-circuiting the inverter output to mains power.
What Causes F1013 in ABB ACS550?
- Discrepancy between total motor count in parameter
8127 MOTORSand auxiliary motor count in parameter8117 NR OF AUX MOT. - Activating auto-change in parameter
8118 AUTOCHNG INTERVwhen parameter8127 MOTORSexceeds the capacity of parameterized PFC relay outputs. - Reconfiguring relay functions in parameters
1401-1403without updating motor fleet size parameters in group81 PFC CONTROL. - Communication loss or physical unseating of the optional
OREL-01relay expansion module while controlling a 4-to-7 pump manifold. - Transferring pump parameter macros between drives having unequal numbers of physical hardware relay outputs.
Step-by-Step Troubleshooting and Solutions
- Verify parameter
8127 MOTORS; ensure it reflects the true total motor fleet count (for standard PFC without autochange,8127 = 8117 + 1). - Cross-reference parameter
8127with parameter group14; confirm every motor has dedicated relay control lines assigned to option31 (PFC). - Evaluate parameter
8118 AUTOCHNG INTERV; ensure auto-change schemes account for both drive-contactor and line-contactor relay requirements. - Inspect option slot 2 on the drive control card to ensure the
OREL-01board is firmly latched and its terminal block screws are tight. - Perform an insulation resistance test at
1000 V DCon all auxiliary motor feeder cables to verify motor electrical safety prior to resetting the fault.
Preventative Maintenance to Avoid F1013 Faults
Perform scheduled inspection of mechanical interlocks on all dual-contactor auto-change bypass assemblies. Periodically test auxiliary contact feedback signals and keep parameter configuration printouts inside the control cabinet door pouch.
Frequently Asked Questions (FAQs)
What is the meaning of F1013 fault in ABB ACS550 drive?
This fault indicates that the total number of PFC motors configured in parameter 8127 does not match the relay output assignments and auto-change parameters.
What are the primary causes of F1013 fault?
Leading causes include setting an invalid motor quantity in parameter 8127, mismatched auxiliary motor settings in parameter 8117, or insufficient relays for auto-change operation.
How do I troubleshoot and correct F1013 fault?
Align parameter 8127 with actual motor quantities, ensure group 14 relays support the selected auto-change mode, and clear the fault on the control panel.