The 2310 fault indicates that the output current of the ABB ACS560 drive has exceeded its internal hardware instantaneous overcurrent trip limit. This protection mechanism shuts down the inverter bridge within microseconds to prevent destructive thermal overstress on the IGBT transistors.
The ACS560 hardware overcurrent trip comparator triggers when peak output phase current exceeds approximately 200% to 250% of nominal rated current I2N. The driver board shuts down IGBT gate signals immediately, forcing the output into high impedance. When an instantaneous overcurrent event occurs, the energy circulating through the output inductive filter and motor coils discharges back into the intermediate DC bus capacitors via the freewheeling diodes. While this protects the power stage against immediate short-circuit failure, repetitive starting into an unresolved overcurrent state will puncture semiconductor junctions and degrade DC bus capacitors.
What Causes 2310 in ABB ACS560?
- Sudden mechanical impact load, machine jam, or seized bearings on the driven mechanism.
- Acceleration ramps configured too short in parameters
23.12 Acceleration time 1or28.72 Freq acceleration time 1. - Incorrect motor nameplate ratings programmed into parameter group
99 Motor data(current, voltage, power). - Inter-turn stator winding failure or an earth fault developing in the motor feeder cables.
- Output contactors opening or closing while the drive is actively modulating output power to the motor.
Step-by-Step Troubleshooting and Solutions
- Decouple the motor from the driven machinery and rotate the shaft by hand to confirm the absence of mechanical jams or binding.
- Increase acceleration ramp times in group
23 Speed reference rampor group28 Frequency reference chainto lower starting current demand. - Review speed and frequency scaling parameters
46.01 Speed scaling,46.02 Frequency scaling, and46.03 Torque scaling. - Disconnect motor cables from drive terminals
U2, V2, W2and perform an insulation resistance megger test at1000V DC; readings must exceed100 MΩ. - Verify that motor nameplate specifications in group
99strictly match the physical rating plate and confirm star/delta links are configured correctly.
Preventative Maintenance to Avoid 2310 Faults
Ensure mechanical couplings and bearings receive regular lubrication, audit motor current draw with true-RMS clamp meters under peak load, and ensure power factor correction capacitors or surge absorbers are never installed on the drive output.
Frequently Asked Questions (FAQs)
What is the meaning of 2310 fault in ABB ACS560 drive?
The 2310 fault is an instantaneous overcurrent trip indicating that output current has exceeded the safe hardware threshold of the inverter.
What are the primary causes of 2310 fault?
This trip is typically caused by mechanical jams, overly aggressive acceleration ramp times, incorrect motor nameplate parameters, or motor insulation breakdowns.
How do I troubleshoot and correct 2310 fault?
Inspect machinery for binding, extend acceleration ramp times in group 23, verify group 99 motor data, and test motor winding insulation with a megger.