4380 fault in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/4380 fault in ABB ACS560 drive

The 4380 fault signals an intolerable temperature difference between the IGBTs of different output phases in the ABB ACS560 drive. The drive shuts down motor modulation immediately to prevent isolated phase semiconductor destruction.

Under symmetrical three-phase conditions, switching losses and conduction heat dissipate equally across phases U2, V2, W2. When an asymmetric load, localized heatsink thermal interface breakdown, or a high-resistance motor connection occurs, one phase bridge absorbs disproportionate thermal stress. The resulting thermal divergence destabilizes intermediate DC circuit balance and triggers fault 4380 to prevent individual IGBT destruction.

What Causes 4380 in ABB ACS560?

  1. Phase current imbalance caused by an asymmetrical motor winding fault or internal turn-to-turn short.
  2. High-resistance junction or loose terminal bolt on motor output terminals U2, V2, W2.
  3. Localized thermal path blockage, uneven thermal grease degradation, or clogged ducting under one phase leg.
  4. Damaged or unbalanced gate driver circuit causing elevated conduction losses in a specific IGBT.
  5. Defective motor cable with high resistance or partial breakdown in one phase conductor.

Step-by-Step Troubleshooting and Solutions

  1. Isolate incoming power, wait for DC bus discharge, and measure phase-to-phase resistance balance of motor windings with a milliohm meter.
  2. Perform an insulation resistance test at 1000V DC across motor leads U2-PE, V2-PE, and W2-PE using an insulation megger.
  3. Check torque tightness on all output power connections at terminals U2, V2, W2 to eliminate contact resistance.
  4. Inspect heatsink ducting and clean away localized dust buildup beneath each individual power phase module.
  5. Monitor output phase currents in parameters 01.18, 01.19, and 01.20 to detect current asymmetry during low-speed testing.

Preventative Maintenance to Avoid 4380 Faults

Perform annual torque verification on all high-current power terminations. Test motor winding resistance balance and insulation health during scheduled maintenance shutdowns, and ensure uniform cooling air distribution across the entire drive heatsink.

Frequently Asked Questions (FAQs)

What is the meaning of 4380 fault in ABB ACS560 drive?

It is a protective trip indicating that the temperature disparity between output phase IGBTs has exceeded safe balance tolerances.

What are the primary causes of 4380 fault?

This fault is caused by motor cabling imbalance, loose phase terminals, motor winding defects, or uneven localized heatsink cooling.

How do I troubleshoot and correct 4380 fault?

Measure motor phase resistances, torque output terminals U2, V2, W2, megger test motor cables, and inspect heatsink cooling uniformity.