4982 fault in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/4982 fault in ABB ACS560 drive

The 4982 fault indicates that external temperature channel 2 has exceeded its programmed trip limit in the ABB ACS560 drive. This thermal protection trip cuts inverter output modulation to prevent irreversible thermal degradation of driven motor windings or bearing assemblies.

The ACS560 monitors secondary temperature transducers—such as PT100, PT1000, KTY84, or positive temperature coefficient (PTC) thermistors—assigned to Channel 2 via analog inputs or an auxiliary sensor interface. When mechanical friction, severe overload, or cooling passage blockages force measured thermal resistance to escalate, parameter 35.03 Measured temperature 2 climbs past the limit established in parameter 35.22 Temperature 2 fault limit. The drive controller terminates gating pulses to the output IGBT modules immediately, bringing the motor to a coast-to-stop state while leaving the intermediate DC link bus capacitors charged to protect the machine from catastrophic winding burnout.

What Causes 4982 in ABB ACS560?

  1. Actual physical overheating of the motor stator windings or mechanical bearings due to excessive duty cycles.
  2. Blocked motor cooling cowls, clogged air intake filters, or failed external forced-cooling ventilation blowers.
  3. A short-circuit, ground fault, or broken wire along the temperature sensor cable connecting to the control terminal block.
  4. Mismatched temperature sensor type selection configured in parameter 35.21 Temperature 2 sensor type.
  5. The trip threshold configured in parameter 35.22 Temperature 2 fault limit is set unrealistically low for ambient operating conditions.

Step-by-Step Troubleshooting and Solutions

  1. Examine parameter 35.03 Measured temperature 2 on the assistant control panel to compare the live feedback value against the physical machine temperature.
  2. Inspect parameter 35.22 Temperature 2 fault limit and verify that the fault setpoint aligns with the motor thermal insulation class (e.g., Class F 155°C or Class H 180°C).
  3. Disconnect sensor leads at control terminals AI1/AI2 or sensor expansion terminals and measure circuit resistance using a calibrated multimeter to check for sensor shorting.
  4. Verify that the sensor type chosen in parameter 35.21 matches the physical sensor probe (e.g., 1 x PT100, 3 x PT100, or PTC).
  5. Inspect the driven machinery for mechanical binding, heavy friction drag, or broken external cooling blower supply breakers.

Preventative Maintenance to Avoid 4982 Faults

Perform quarterly thermal imaging audits across motor stator frames, clean motor ventilation fins and fan cowls regularly, ensure shielded instrument wiring is grounded solely at the drive chassis, and test thermal sensor resistance balances during scheduled downtime.

Frequently Asked Questions (FAQs)

What is the meaning of 4982 fault in ABB ACS560 drive?

The 4982 code is an overtemperature trip indicating that temperature channel 2 has exceeded the maximum safe limit configured in parameter 35.22.

What are the primary causes of 4982 fault?

This trip is typically caused by motor cooling failure, excessive mechanical overloading, sensor wiring shorts, or mismatched sensor type selection in parameter group 35.

How do I troubleshoot and correct 4982 fault?

Check live temperature in parameter 35.03, inspect motor ventilation, verify sensor resistance with a multimeter, and adjust parameter 35.22 to match motor ratings.