The 5691 fault signals a failure in the Analog-to-Digital Converter (ADC) measurement circuitry within the ABB ACS560 drive. The drive shuts down output gating immediately to prevent unmonitored current or voltage operation.
Precise vector control and overload protection require continuous analog sampling of intermediate DC bus voltage, output phase currents, and heatsink temperatures. When the on-board ADC fails diagnostic self-tests or generates out-of-range conversion registers, the motor control algorithm loses vital feedback telemetry. Inverter modulation terminates instantly to protect the power semiconductors against uncontrolled overcurrent or catastrophic phase short circuits.
What Causes 5691 in ABB ACS560?
- Defective ADC integrated circuit or degraded voltage reference source on the drive power or control board.
- Severe electrical surge or transient spike coupled into analog measurement channels from external line disturbances.
- Internal power supply rail deviation feeding the analog conversion circuits (e.g.,
+5Vor±15Vrails). - Moisture condensation, chemical contamination, or conductive particulate matter shorting surface-mount pins.
- Hardware sensor failure within internal Hall-effect current transducers feeding the ADC inputs.
Step-by-Step Troubleshooting and Solutions
- Disconnect mains power, allow the DC link to discharge fully, and power cycle the drive to check if the fault clears on boot.
- Inspect the control and power circuit boards for signs of electrical flashover, heat discoloration, or moisture ingress.
- Check incoming mains voltage balance across terminals
L1, L2, L3with a multimeter to ensure clean supply quality. - Perform a motor insulation megger test at
1000V DCacross terminalsU2, V2, W2to ground to rule out external voltage spikes. - If fault 5691 reappears immediately following restart without motor cables attached, replace the damaged power board or drive.
Preventative Maintenance to Avoid 5691 Faults
Install upstream surge protection devices (SPDs) and line reactors to protect internal measurement electronics from grid transients. Maintain climate-controlled, dry enclosure environments to prevent condensation from bridging delicate analog surface-mount components.
Frequently Asked Questions (FAQs)
What is the meaning of 5691 fault in ABB ACS560 drive?
It is an internal hardware fault indicating that the Analog-to-Digital Converter (ADC) circuit responsible for current and voltage sensing has failed.
What are the primary causes of 5691 fault?
This fault is caused by damaged ADC chips, internal reference voltage failures, electrical line surges, or PCB surface contamination.
How do I troubleshoot and correct 5691 fault?
Perform a complete power reboot, check incoming power quality, disconnect motor leads to test the drive unloaded, and replace the board if the fault persists.