The 5695 fault indicates that the power unit hardware detected by the ABB ACS560 drive does not match the configured power unit topology. The drive halts motor operation because the system cannot verify power stage capacity or current balancing.
In multi-module drive architectures or when running under reduced run operating modes, the control unit polls all connected power modules over internal optical or serial links. When fewer power modules respond than defined in parameter 95.13 Reduced run mode, pulse-width modulation is locked out. Operating with missing power units without firmware reconfiguration risks severe current overloading and thermal destruction across the remaining power modules.
What Causes 5695 in ABB ACS560?
- Physical power module removed or unpowered without updating parameter
95.13 Reduced run mode. - Disconnected, damaged, or swapped fiber-optic or parallel communication cables linking power modules.
- Auxiliary power supply failure on one of the parallel power unit modules preventing communication.
- Mismatched firmware revisions or module rating data across parallel power stages.
- Incorrect commissioning parameter entry in parameter group
95 HW configuration.
Step-by-Step Troubleshooting and Solutions
- Navigate to parameter group
95 HW configurationand review parameter95.13 Reduced run mode. - Set parameter
95.13to reflect the actual number of connected and operational power units available in the system. - Inspect all internal communication links and fiber-optic cables between the control unit and each power module.
- Verify auxiliary control supply voltage at each power module to ensure all units power up simultaneously.
- Review parameter group
07 System infoto confirm that all connected power units report identical firmware versions.
Preventative Maintenance to Avoid 5695 Faults
Always execute the specified reduced run reconfiguration procedure prior to isolating physical power units for maintenance. Inspect parallel communication harnesses for secure latching and protect fiber optic cables from tight bends or mechanical crushing.
Frequently Asked Questions (FAQs)
What is the meaning of 5695 fault in ABB ACS560 drive?
It indicates that the drive cannot locate all configured power unit modules specified in the hardware parameters.
What are the primary causes of 5695 fault?
This fault occurs when a power module is physically disconnected, auxiliary power to a unit fails, or parameter 95.13 is misconfigured.
How do I troubleshoot and correct 5695 fault?
Check parameter 95.13 Reduced run mode, verify parallel communication cables, confirm auxiliary power to all units, and reconfigure the topology.