6681 fault in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/6681 fault in ABB ACS560 drive

The 6681 fault indicates that cyclic communication across the embedded fieldbus (EFB) interface has been lost in the ABB ACS560 drive. The drive executes a protective shutdown to prevent unmonitored motor operation following a network communication break.

The integrated EIA-485 Modbus RTU interface on terminal block X5 directly controls start/stop commands, velocity references, and process interlocks. When polling packets cease or arrive corrupted, the internal watchdog timer expires. In accordance with parameter 58.14 Communication loss action set to Fault, the drive immediately ceases PWM modulation and coasts or ramps the motor to a stop to avoid hazardous loss of supervisory plant control.

What Causes 6681 in ABB ACS560?

  1. Broken, loose, or severed RS-485 serial communication wiring on control unit terminals 29 (B+), 30 (A-), or 31 (AGND).
  2. Host Modbus master (PLC or RTU) placed in stop mode, powered down, or suffering network polling overruns.
  3. Missing, misconfigured, or excess 120 Ω bus termination resistors causing signal reflections along the serial daisy chain.
  4. Communication timeout setting in parameter 58.16 Communication loss time set too short for the network cycle speed.
  5. Severe common-mode electrical noise or ground loops induced by unshielded motor output lines.

Step-by-Step Troubleshooting and Solutions

  1. Inspect wiring continuity and terminal tightness on EIA-485/X5 terminals 29, 30, 31 on the control board.
  2. Verify bus termination switches; ensure only the physical beginning and end nodes of the RS-485 trunk have termination enabled.
  3. Confirm that the fieldbus master is online and actively polling the drive station address defined in parameter 58.03 Node address.
  4. Verify serial port parameters in group 58: check 58.04 Baud rate, 58.05 Parity, and timeout threshold in 58.16.
  5. Review parameter 58.14 Communication loss action to confirm whether Fault, Warning, or Keep speed is appropriate for the system.

Preventative Maintenance to Avoid 6681 Faults

Use shielded twisted-pair cables with 120-ohm nominal impedance designed specifically for EIA-485 networks. Ground the shield at a single point to prevent ground circulating currents, and inspect terminal screw torques semi-annually.

Frequently Asked Questions (FAQs)

What is the meaning of 6681 fault in ABB ACS560 drive?

It indicates that the drive has lost serial Modbus RTU communication across its embedded EIA-485 interface for longer than the timeout period.

What are the primary causes of 6681 fault?

This fault is caused by disconnected terminals 29, 30, 31, PLC master timeouts, incorrect baud rate or parity settings, and missing termination.

How do I troubleshoot and correct 6681 fault?

Inspect terminal block X5 wiring, verify the master PLC status, match parameter group 58 communication settings, and check bus termination.