The 7191 fault indicates that an internal short circuit has occurred within the brake chopper IGBT semiconductor of the ABB ACS560 drive. The drive shuts down all power gating to protect the DC bus capacitors and prevent continuous power delivery into the resistor.
If the brake chopper IGBT fails short-circuit across its collector and emitter terminals, the dynamic braking resistor remains permanently bridged across the high-voltage DC bus. This fault causes extreme current draw, rapid resistor boiling/burnout, and immediate collapse of intermediate DC circuit voltage. Internal hardware diagnostic routines detect this short circuit during initialization or switching and latch fault 7191 to prevent an electrical fire.
What Causes 7191 in ABB ACS560?
- Brake chopper IGBT module punctured or shorted due to excessive peak energy dissipation or thermal runaway.
- Connecting a brake resistor with an ohmic value below the specified minimum resistance rating
Rmin. - Severe transient overvoltage surges on the AC mains supply reflecting across the intermediate DC circuit.
- Failure of the internal gate driver circuit holding the chopper transistor continuously in active conduction.
- Physical flashover or conductive dust bridging internal chopper semiconductor terminals.
Step-by-Step Troubleshooting and Solutions
- Isolate all AC mains power, allow the intermediate circuit to discharge fully, and disconnect external leads from
R+andR-. - Measure resistance of the brake resistor using a multimeter; confirm the ohmic value is strictly equal to or above
Rmin. - Using the diode test function on a digital multimeter, check across drive terminals
R+andR-; a reading near0.00Vconfirms a shorted IGBT. - Inspect external resistor wiring for signs of severe heat damage, melted insulation, or earth contact.
- If the internal chopper IGBT tests short-circuit, the drive power module has suffered irreversible hardware damage and must be replaced.
Preventative Maintenance to Avoid 7191 Faults
Always verify that external dynamic braking resistors match ABB engineering tables for minimum ohmic resistance and continuous wattage. Install line reactors and surge arrestors to suppress grid transients that damage semiconductor gate oxide layers.
Frequently Asked Questions (FAQs)
What is the meaning of 7191 fault in ABB ACS560 drive?
It is a critical hardware trip indicating that the internal dynamic brake chopper IGBT transistor has suffered an internal short circuit.
What are the primary causes of 7191 fault?
This fault is caused by connecting an undersized brake resistor below Rmin, DC bus voltage spikes, thermal overload, or gate driver breakdown.
How do I troubleshoot and correct 7191 fault?
Disconnect resistor leads, perform a multimeter diode test across terminals R+ and R-, verify resistor ohms, and replace the power unit if shorted.