71A2 fault in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/71A2 fault in ABB ACS560 drive

The 71A2 fault indicates a mechanical brake control trip where the brake acknowledgment signal failed to confirm closure in the ABB ACS560 drive. The drive shuts down motor control to prevent mechanical load slippage and machinery damage.

In vertical hoists, winches, and inclined conveyors, parameter group 44 Mechanical brake control governs safe torque handover between the electric motor and the mechanical holding brake. When a stop command is given and the mechanical brake is ordered closed, the drive monitors the acknowledgment feedback digital input. If the signal does not transition within parameter 44.13 Mechanical brake close delay, the drive triggers 71A2 per parameter 44.17 Brake fault function, halting PWM modulation and de-energizing output terminals U2, V2, W2.

What Causes 71A2 in ABB ACS560?

  1. Mechanical brake binding, jammed shoes, broken springs, or worn linings preventing physical brake closure.
  2. Defective, misaligned, or contaminated brake acknowledgment limit switch or proximity sensor.
  3. Parameter 44.13 Mechanical brake close delay set shorter than the physical engagement time of the brake.
  4. Interposing control relay or contactor contacts welded in the closed position, keeping the brake coil energized.
  5. Incorrect signal source mapping configured in parameter 44.07 Brake acknowledge selection.

Step-by-Step Troubleshooting and Solutions

  1. Inspect the physical mechanical brake assembly to verify that friction linings seat firmly against the brake disc or drum.
  2. Verify brake acknowledgment switch operation and monitor its digital input status under parameter group 10 Standard DI, RO.
  3. Check parameter group 44 Mechanical brake control, confirming parameters 44.07 and 44.13 match mechanical specs.
  4. Examine parameter 44.17 Brake fault function to verify whether acknowledgment timeout is programmed as a fault or warning.
  5. Measure brake coil de-energization voltage and perform an insulation resistance megger test at 500V DC on brake coil cabling.

Preventative Maintenance to Avoid 71A2 Faults

Measure brake friction lining wear and air gaps during quarterly mechanical servicing, lubricate mechanical linkages per manufacturer instructions, clean limit switch contact mechanisms, and perform periodic dynamic brake torque tests.

Frequently Asked Questions (FAQs)

What is the meaning of 71A2 fault in ABB ACS560 drive?

The 71A2 fault indicates that the mechanical brake was commanded to close, but the feedback confirmation switch failed to verify closure within the allowed time.

What are the primary causes of 71A2 fault?

Primary causes include jammed mechanical brake shoes, defective acknowledgment limit switches, welded relay contacts, and insufficient close delay settings.

How do I troubleshoot and correct 71A2 fault?

Check physical brake engagement, inspect feedback switch wiring, increase parameter 44.13 close delay, and verify parameter 44.17 fault settings.