The 8002 fault indicates a User Load Curve (ULC) overload condition where motor torque or current has exceeded the programmed upper load curve envelope for longer than the configured trip delay. The ABB ACS560 trips into a protected stop to avoid mechanical machine breakdown and motor thermal stress.
The ACS560 user load curve supervision allows operators to protect equipment from mechanical overload conditions before generic motor thermal trips occur. The controller compares real-time shaft torque from parameter 01.10 Motor torque against a customized five-point speed-versus-torque boundary programmed across parameters 37.11...37.15. If mechanical friction, material jamming, or downstream process restrictions force operating torque above this curve for longer than parameter 37.42 ULC overload timer, parameter 37.03 ULC overload actions commands the drive to trip on 8002. The drive cuts power to output terminals U2, V2, W2, saving gearboxes and drive components from mechanical fatigue.
What Causes 8002 in ABB ACS560?
- Mechanical jamming, product accumulation, or foreign object obstruction in conveyors, augers, or crushers.
- Worn mechanical bearings, misaligned shafts, or dry gearboxes generating excessive parasitic drag.
- Process fluid viscosity increase, slurry thickening, or closed discharge valves in positive-displacement pump systems.
- Overload curve points programmed too low relative to required operational starting or peak running torques.
- Parameter
37.03 ULC overload actionsconfigured to initiate an immediate fault stop rather than an alarm.
Step-by-Step Troubleshooting and Solutions
- Inspect Driven Machinery for Jams: De-energize and lock out the motor; decouple the shaft and rotate mechanical machinery by hand to identify binding, gear friction, or material buildup.
- Perform Stator Insulation Megger Test: Disconnect leads from terminals
U2, V2, W2and execute a1000V DCinsulation resistance test to ground; confirm values exceed10 MΩto rule out winding faults. - Monitor Real-Time Torque Levels: Run the drive and observe parameter
01.10 Motor torqueon the keypad; compare actual operating torque against overload envelope parameters37.11...37.15. - Review Parameter 37.03 Settings: Inspect parameter
37.03 ULC overload actionsand determine whether setting the response toWarningbetter accommodates plant process needs. - Increase Overload Filter Timer: Lengthen parameter
37.42 ULC overload timerto allow the machinery sufficient time to clear temporary product surges without nuisance tripping.
Preventative Maintenance to Avoid 8002 Faults
Establish strict lubrication schedules for all drive bearings, conveyor rollers, and gear reducers to minimize drag torque. Use periodic vibration and infrared analysis to identify mechanical wear before it pushes motor loading above configured user load curves.
Frequently Asked Questions (FAQs)
What is the meaning of 8002 fault in ABB ACS560 drive?
The 8002 fault indicates that motor torque or current has exceeded the programmed upper envelope of the user load curve for a duration longer than the overload timer.
What are the primary causes of 8002 fault?
Primary root causes include mechanical binding, conveyor material jams, worn bearings, closed process valves, or overly restrictive curve settings in parameter group 37.
How do I troubleshoot and correct 8002 fault?
Clear mechanical obstructions, check gearbox and bearing condition, verify operating torque in parameter 01.10, and readjust curve points in parameters 37.11…37.15.