A8C6 alarm in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/A8C6 alarm in ABB ACS560 drive

The A8C6 warning indicates that overload curve points programmed in the user load curve table of the ABB ACS560 drive are mathematically invalid or out of permissible range. The drive alerts operators that overload supervision is inactive until the table values are reconciled.

Overload supervision in the ACS560 protects mechanical systems and drive power electronics by bounding maximum permissible torque or current across the speed range. Parameters 37.31 through 37.35 define overload points 1 through 5. When these points are programmed with values lower than corresponding underload thresholds or exceed absolute drive torque and current limits, the internal algorithm cannot generate valid evaluation corridors, leaving the motor and IGBT power stage without targeted mechanical jam supervision.

What Causes A8C6 in ABB ACS560?

  1. Overload curve points in parameters 37.31 through 37.35 programmed with values lower than or equal to underload points in 37.21 through 37.25.
  2. Overload values programmed beyond maximum drive current or maximum motor torque limits defined in parameter group 30 Limits.
  3. Negative or zero percentage values entered into overload points during manual keypad programming.
  4. Incomplete parameter entry leaving default or zero values at higher speed points in group 37.
  5. Inadvertent parameter transpositions between underload and overload groups during remote PLC configuration.

Step-by-Step Troubleshooting and Solutions

  1. Inspect parameter group 37 User load curve, specifically parameters 37.31 ULC overload point 1 through 37.35 ULC overload point 5.
  2. Cross-reference each overload point with its respective underload point to ensure 37.31 > 37.21 through 37.35 > 37.25.
  3. Verify that overload setpoints do not exceed maximum operational limits set in parameter 30.17 Maximum torque 1 or 30.19 Maximum current.
  4. Confirm that signal type configured in parameter 37.02 ULC supervision signal corresponds with the programmed percentage scale.
  5. Conduct an insulation resistance megger test at 500V DC across motor leads U2, V2, W2 to ensure no physical motor faults contribute to load instability.

Preventative Maintenance to Avoid A8C6 Faults

Document and archive verified ULC profile curves in plant electrical records, establish commissioning sign-offs for ULC limit parameters, and perform functional test runs across all operating speed points.

Frequently Asked Questions (FAQs)

What is the meaning of A8C6 fault in ABB ACS560 drive?

The A8C6 warning indicates that the overload curve points in parameter group 37 are invalid, out of permissible range, or lower than underload points.

What are the primary causes of A8C6 fault?

Primary causes include overload values set below underload levels, parameters exceeding drive torque limits, zero or negative entries, and transposition errors.

How do I troubleshoot and correct A8C6 fault?

Review parameters 37.31 through 37.35, ensure overload values exceed underload values, and verify torque limit boundaries.