AFE1 alarm in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/AFE1 alarm in ABB ACS560 drive

The AFE1 warning indicates that the ABB ACS560 drive has received an active Emergency Stop command configured for OFF2 mode. This emergency safety warning notifies operators that motor modulation has ceased, allowing the driven motor to coast freely to a stop.

When the drive receives an emergency stop trigger mapped to OFF2 mode via parameter 21.05 Emergency stop source, the digital signal processor immediately shuts down gating signals to all output IGBTs. Unlike OFF1 or OFF3 modes that ramp the motor down through controlled regenerative deceleration, OFF2 mode de-energizes the stator windings instantly, allowing the mechanical load to coast to rest entirely under friction and load inertia. The intermediate DC link capacitor bank remains fully charged to line potential, but warning AFE1 remains latched on the control interface until the safety input circuit is restored and acknowledged.

What Causes AFE1 in ABB ACS560?

  1. An external emergency stop pushbutton or safety trip switch wired to the input selected in parameter 21.05 has been depressed.
  2. A fieldbus master (e.g., PLC via Modbus RTU) commanded emergency stop bit OFF2 through the communication control word.
  3. Loose, broken, or disconnected field wiring on the digital input terminal assigned to the emergency stop source.
  4. Incorrect logic inversion configured on the emergency stop digital input parameter.
  5. Premature machine safety gate opening interrupting the assigned 24V DC control circuit.

Step-by-Step Troubleshooting and Solutions

  1. Verify the physical safety of the machine and operator, then inspect external emergency stop pushbuttons to confirm they are released and reset.
  2. Inspect parameter 21.05 Emergency stop source on the assistant control panel to identify the specific digital input or fieldbus bit assigned.
  3. Measure DC voltage with a multimeter across the assigned digital input terminal (e.g., DI1 through DI6) and common DGND to confirm a steady 24V DC input.
  4. Check parameter 21.04 Emergency stop mode to verify whether Coast (Off2) is the intended emergency stopping behavior.
  5. Once the emergency circuit is safely closed, cycle the drive start/run command to resume normal motor modulation.

Preventative Maintenance to Avoid AFE1 Faults

Test mechanical emergency stop pushbuttons and safety gate switches monthly, ensure terminal screw torques conform to specifications, and verify fieldbus emergency stop control word bits during PLC code commissioning.

Frequently Asked Questions (FAQs)

What is the meaning of AFE1 fault in ABB ACS560 drive?

The AFE1 warning indicates that an emergency stop command configured for OFF2 mode has been triggered, causing the motor to coast to a standstill.

What are the primary causes of AFE1 fault?

It is caused by depressed E-stop pushbuttons, broken input wiring, PLC emergency stop commands, or tripped safety gate interlocks.

How do I troubleshoot and correct AFE1 fault?

Ensure machine safety, release the physical E-stop button, verify 24V DC on the assigned digital input terminal, and restart the drive.