The AFE2 alarm indicates that the drive has received an active emergency stop command configured for Off1 or Off3 deceleration mode. The ABB ACS560 issues this priority alert while executing controlled emergency ramp-down to bring machinery to a standstill.
When an emergency stop command is initiated via field pushbuttons, safety interlocks, or PLC communication networks, the control core bypasses the primary speed reference. In Off1 mode, the drive decelerates along the active standard deceleration ramp defined in parameter 23.13 Deceleration time 1. In Off3 mode, the inverter modulates aggressive braking along parameter 23.23 Emergency stop time, frequently utilizing dynamic braking through external resistors across terminals R+ and R- to bleed kinetic load energy. The drive maintains the AFE2 warning banner until the stop cycle finishes and the safety circuit is manually reset.
What Causes AFE2 in ABB ACS560?
- Actuation of an external emergency stop pushbutton or trip wire wired to a designated digital input.
- Incorrect signal source assignment programmed in parameter
21.05 Emergency stop source. - Tripped safety relay contact or open safety circuit in the plant emergency stop loop.
- Loss of
24V DCcontrol power to the digital input terminal assigned to the E-stop function. - Fieldbus master controller asserting the emergency stop control bit within parameter group
58 Embedded fieldbus.
Step-by-Step Troubleshooting and Solutions
- Inspect Field E-Stop Buttons: Check physical emergency stop buttons on control panels and machine perimeters; twist to release any mechanically locked actuators.
- Verify Parameter 21.05 Configuration: Navigate to parameter
21.05 Emergency stop sourceand confirm whether the assigned source (e.g.,DI1,DI2, orEmbedded fieldbus) matches field wiring schematics. - Measure Terminal Voltage: Use a digital multimeter to measure DC voltage across the assigned digital input terminal (e.g., terminal
DI4) and+24V; ensure a steady24V DCis present when the safety circuit is healthy. - Verify Parameter 21.04 Settings: Inspect parameter
21.04 Emergency stop modeto ensure whether Off1 (standard ramp) or Off3 (fast ramp) matches process safety requirements. - Check PLC Fieldbus Control Words: If controlled over Modbus RTU or industrial fieldbus, inspect the control word bit states using parameter
06.01 Main control wordto ensure the PLC is not commanding a stop.
Preventative Maintenance to Avoid AFE2 Faults
Conduct monthly functional testing of all emergency stop pushbuttons, cable-pull switches, and intermediate safety relays. Check terminal screw torques on safety I/O channels annually to prevent loose connections from causing false tripping during machine vibration.
Frequently Asked Questions (FAQs)
What is the meaning of AFE2 fault in ABB ACS560 drive?
The AFE2 code is an operational warning indicating that the drive has initiated an emergency stop sequence following an Off1 or Off3 deceleration command.
What are the primary causes of AFE2 fault?
Primary root causes include depressed emergency stop pushbuttons, tripped external safety relays, open control wiring on digital inputs, or fieldbus PLC commands.
How do I troubleshoot and correct AFE2 fault?
Ensure machine safety conditions are met, reset all field E-stop buttons, verify 24V DC on the terminal assigned in parameter 21.05, and reapply start commands.