AFEC alarm in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/AFEC alarm in ABB ACS560 drive

The AFEC warning indicates that the external 24V DC power supply signal to the control unit is missing while parameter 95.04 is set to external supply. The ABB ACS560 alerts operators to redundant control power loss before digital communications drop during line dips.

When the control board power source is parameterized for an external supply, the internal supervisory logic monitors the dedicated auxiliary input terminals. If the main AC line is present, internal switch-mode circuits continue powering basic PWM gate control; however, loss of the external 24V backup eliminates logic ride-through protection, increasing the risk of immediate processor reset, fieldbus dropouts, and sudden motor de-energization during brief utility interruptions.

What Causes AFEC in ABB ACS560?

  1. Parameter 95.04 Control board supply set to [1] External 24V without external auxiliary power connected.
  2. Tripped miniature circuit breaker, blown fuse, or overload fault on the external 24V DC power supply unit.
  3. Loose, corroded, or disconnected wiring landing on control unit power terminals +24V and DGND.
  4. Excessive voltage drop across long control wiring runs causing voltage at the control board to fall below 20.4V DC.
  5. Defective auxiliary power supply generating heavy voltage ripple or experiencing intermittent output regulation.

Step-by-Step Troubleshooting and Solutions

  1. Measure DC voltage across control board auxiliary terminals +24V and DGND using a digital multimeter to confirm 24V DC presence.
  2. If no external 24V supply is physically installed, change parameter 95.04 Control board supply back to [0] Internal 24V.
  3. Inspect external switch-mode power supplies, testing for output short circuits, blown branch fuses, or tripped safety breakers.
  4. Check all screw terminals on the control board interface and re-torque loose connections to ensure reliable electrical continuity.
  5. Perform an insulation resistance test at 500V DC across motor leads U2, V2, W2 to ensure no physical ground faults induce noise into 24V commons.

Preventative Maintenance to Avoid AFEC Faults

Routinely inspect 24V DC power supply output voltages under full panel load, verify terminal screw tightness during annual shutdowns, and ensure industrial power supplies have sufficient reserve capacity to manage inrush current from external option modules.

Frequently Asked Questions (FAQs)

What is the meaning of AFEC fault in ABB ACS560 drive?

The AFEC warning indicates that the control unit is programmed to expect an external 24V DC power supply, but the voltage signal is absent at the control terminals.

What are the primary causes of AFEC fault?

Primary causes include incorrect setting of parameter 95.04, failed external 24V power supplies, tripped circuit breakers, and loose control terminal connections.

How do I troubleshoot and correct AFEC fault?

Measure voltage at the 24V input terminals, reset parameter 95.04 to internal if external power is not used, and repair any damaged auxiliary wiring.