AFED alarm in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/AFED alarm in ABB ACS560 drive

The AFED warning indicates that the enable-to-rotate permission signal was not asserted within the fixed 240-second time delay after receiving a start command. The ABB ACS560 holds the motor in standby to protect operators and machinery from unexpected shaft motion.

When a run command is initiated, the drive pre-charges control registers and prepares for modulation. However, if the functional interlock assigned in parameter 20.22 Enable to rotate remains open, gate pulses to the output IGBT inverter bridge remain blocked. Inhibiting PWM switching prevents the motor from producing torque against engaged mechanical holding brakes, eliminating stator winding overheating while waiting for safety guards or process valves to clear.

What Causes AFED in ABB ACS560?

  1. External process interlock, safety gate switch, or mechanical brake auxiliary contact remaining open after a start request.
  2. The digital input selected in parameter 20.22 Enable to rotate not receiving a continuous 24V DC high-level signal.
  3. Damaged control cable or disconnected wire leading from field interlock contacts to the assigned digital input.
  4. Incorrect signal source selection configured in parameter 20.22 Enable to rotate (e.g., mapped to wrong DI or fieldbus bit).
  5. Start command initiated from an upstream automation PLC while upstream permissive safety conditions are unfulfilled.

Step-by-Step Troubleshooting and Solutions

  1. Access parameter 20.22 Enable to rotate to identify the designated digital input or communication bit configured for rotation enable.
  2. Monitor input status in parameter group 10 Standard DI, RO to verify whether the assigned digital input physically transitions high.
  3. Measure voltage across the configured digital input terminal and DGND with a multimeter; confirm 24V DC is present when interlocks close.
  4. Inspect mechanical process interlocks, emergency rope pulls, lubrication pressure switches, and safety limit gates in the field.
  5. Perform an insulation resistance megger test at 500V DC across motor leads U2, V2, W2 to ensure no phase defects exist while diagnosing interlocks.

Preventative Maintenance to Avoid AFED Faults

Regularly inspect and clean mechanical limit switch plungers, test auxiliary safety interlock circuits during quarterly reviews, verify PLC sequencing logic, and ensure field control terminal screws remain tight in vibrating environments.

Frequently Asked Questions (FAQs)

What is the meaning of AFED fault in ABB ACS560 drive?

The AFED warning indicates that the drive received a start command, but the required enable-to-rotate interlock signal was not received within 240 seconds.

What are the primary causes of AFED fault?

Primary causes include open field interlock switches, missing 24V signals on the designated digital input, misconfigured parameter 20.22, and PLC sequence delays.

How do I troubleshoot and correct AFED fault?

Identify the input configured in parameter 20.22, verify 24V DC is supplied to that terminal, and inspect mechanical safety switches for open contacts.