AFF6 alarm in ABB ACS560 drive

Home/ABB/ABB ACS560 drive/AFF6 alarm in ABB ACS560 drive

The AFF6 warning indicates that a motor identification (ID) run has been scheduled and will execute automatically upon the next drive start command. The ABB ACS560 alerts technicians that special motor modeling routines are queued for motor characterization.

During an ID run, standard speed reference ramping is suspended while the inverter executes a specialized test pattern. The drive modulates the IGBT bridge to inject precision DC and AC voltage pulses into motor terminals U2, V2, W2, measuring stator resistance, leakage inductance, saturation coefficients, and rotor time constants. The intermediate DC bus capacitor bank supplies dynamic energy while the DSP calculates high-accuracy flux vectors for optimal vector motor control.

What Causes AFF6 in ABB ACS560?

  1. Motor identification run manually selected and requested via parameter 99.13 ID run requested.
  2. Initial drive setup routine triggered by the commissioning assistant on the control panel.
  3. Motor nominal parameters changed in parameter group 99, prompting the firmware to request re-identification.
  4. Motor control mode changed from Scalar to Vector mode in parameter 99.04 Motor control mode.
  5. Automated commissioning script or PC tool executing motor tuning routines before equipment handover.

Step-by-Step Troubleshooting and Solutions

  1. Recognize that AFF6 is an informative notification confirming that an ID run will initiate on the next start command.
  2. Check parameter 99.13 ID run requested to verify the selected ID run mode (e.g., Standstill, Normal, or Reduced).
  3. If a rotating ID run (Normal or Reduced) is selected, ensure the motor shaft is completely uncoupled from driven machinery.
  4. Perform an insulation resistance megger test at 500V DC on motor leads U2, V2, W2 to verify winding integrity before test excitation.
  5. Ensure safety perimeters are clear, verify motor wiring, and issue a local start command to permit the ID run to complete.

Preventative Maintenance to Avoid AFF6 Faults

Perform motor identification runs whenever motor cabling or stator rewindings take place, always back up newly identified motor parameters using Drive Composer, and ensure mechanical decouplings are scheduled before executing rotating ID runs.

Frequently Asked Questions (FAQs)

What is the meaning of AFF6 fault in ABB ACS560 drive?

The AFF6 code is an informative warning indicating that a motor identification run is armed and will begin the moment the next start command is given.

What are the primary causes of AFF6 fault?

Primary causes include manual selection in parameter 99.13, switching to vector control mode, and commissioning wizard configuration routines.

How do I troubleshoot and correct AFF6 fault?

No fault correction is needed; ensure the motor is safe to test, uncouple the load if required by the test mode, and press start to execute the ID run.