The FA90 fault alerts that the Safe Torque Off (STO) internal diagnostic routine has detected a software or internal microprocessor failure in the ABB ACS560 drive. The drive hardware disables IGBT firing circuits immediately to guarantee functional safety.
The ACS560 integrates dual-channel hardware architecture on terminals S1, S2, IN1, IN2, constantly cross-checked by background safety firmware routines. When the diagnostic supervisor detects calculation checksum errors, timing skew, or internal test cycle failures between dual safety channels, it triggers fault FA90. Inverter output shuts off irreversibly, preventing torque generation until internal safety self-diagnostics are re-validated.
What Causes FA90 in ABB ACS560?
- Internal safety diagnostic software execution error or corrupted firmware memory sector.
- Severe electromagnetic interference (EMI) corrupting microsecond pulse diagnostic cycles on STO lines.
- Transient auxiliary control voltage dip or high ripple on the internal
+24V DCsafety power rail. - Unsynchronized switching or contact bounce across dual external STO channels exceeding maximum allowed skew.
- Internal hardware failure within the Safe Torque Off optocoupler or gating isolation circuitry.
Step-by-Step Troubleshooting and Solutions
- Cycle auxiliary power to the control unit completely (wait until DC bus completely discharges) to restart internal safety processors.
- Measure voltage on STO inputs
IN1andIN2relative toSGND; verify identical+24V DClevels without ripple. - Inspect external emergency stop or safety relay contacts for uneven wear, high resistance, or contact chatter.
- Verify that STO wiring utilizes shielded twisted-pair cables, run strictly apart from high-voltage motor output lines.
- If fault FA90 recurs immediately after control unit reboot and STO circuits are verified, replace the control unit.
Preventative Maintenance to Avoid FA90 Faults
Conduct annual functional safety proof testing on the complete STO circuit, ensuring both channels drop and energize simultaneously. Maintain low-impedance ground bonding across drive enclosure plates to suppress high-frequency common-mode noise.
Frequently Asked Questions (FAQs)
What is the meaning of FA90 fault in ABB ACS560 drive?
It is a critical safety fault indicating that internal Safe Torque Off (STO) diagnostic software routines have detected an execution failure.
What are the primary causes of FA90 fault?
This fault is caused by internal safety firmware timing errors, heavy electrical noise transients, STO channel contact bounce, or hardware failures.
How do I troubleshoot and correct FA90 fault?
Reboot the control unit, inspect dual-channel STO voltages on terminals IN1 and IN2, eliminate electrical noise, and test safety relays.