Allen-Bradley Kinetix 2000 Servo Drive Fault Codes & Diagnostic Guide
Complete fault code reference, E-series error indicators, root causes, and troubleshooting procedures for Rockwell Automation Allen-Bradley Kinetix 2000 multi-axis servo drives (Bulletin 2093). Search or filter through the complete diagnostic directory below.
Power Range
0.3 – 3.0 kW per Axis
Supply Voltage
230V AC (1-Phase / 3-Phase)
Control Platform
SERCOS Fiber Interface / Logix Motion
Operator Interface
4-Character LED / Studio 5000
Complete Allen-Bradley Kinetix 2000 Fault Code Directory
Use the search box in the table below to quickly find your fault code (e.g., search E04, E14, E18, or Feedback).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| - Power (PWR) indicator not ON | Cause: No AC power or auxiliary logic power, or internal power supply malfunction. Remedy:
|
| - Motor jumps when first enabled | Cause: Motor wiring error, incorrect motor chosen, or digital I/O not working correctly (I/O power disconnected). Remedy:
|
| E00 BusUndervoltage Fault (Blown fuse) | Cause: A blown fuse was detected on the inverter PCB. Remedy:
|
| E04 MotorOvertemp Fault | Cause: Motor thermal switch tripped due to high ambient motor temperature, excessive current, motor wiring error, or incorrect motor selection. Remedy:
|
| E05 DriveOvercurrent Fault (Power Fault) | Cause: Self-protection of the Intelligent Power Module (IPM) due to: - Motor cables shorted. - Motor winding shorted internally. - Drive temperature too high. - Operation above continuous power rating. - Short circuit/failed component. Remedy:
|
| E06 HardOvertravel Fault | Cause: Axis moved beyond physical travel limits (positive/negative) or dedicated overtravel input is inactive. Remedy:
|
| E07 MotFeedbackFault (Motor Feedback Loss) | Cause: The feedback wiring is open, shorted, or missing. Remedy:
|
| E09 BusUndervoltage Fault | Cause: DC bus voltage is below its limit (below 137V for 230V system) or fell below limit while an axis on the follower power rail was enabled. Remedy:
|
| E10 DriveOvervoltage Fault | Cause: The DC bus voltage is above its limit (over 410V for 230V system). Excessive regeneration of power. Remedy:
|
| E11 MotFeedbackFault (Illegal Hall State) | Cause: State of Hall feedback inputs is incorrect due to bad connections. Remedy:
|
| E16 Softovertravel Fault | Cause: Axis position exceeded maximum software setting. Remedy:
|
| E18 OverSpeedFault | Cause: Motor speed has exceeded 150% of maximum rated speed. Remedy:
|
| E19 PositionErrorFault (Follow Error) | Cause: Position error limit was exceeded. Remedy:
|
| E20 MotFeedbackFault (Mtr Fdbk AQB) | Cause: Motor Encoder State Error; the motor encoder encountered an illegal transition. Remedy:
|
| E21 AuxFeedbackFault | Cause: Communication was not established with an intelligent encoder. Remedy:
|
| E30 MotFeedbackFault | Cause: Communication was not established with an intelligent encoder. Remedy:
|
| E34 GroundShortFault | Cause: Excessive ground current detected due to: - Wiring error. - Motor internal ground short. - Internal malfunction. - Grounded control power terminal (230V systems). Remedy:
|
| E35 DriveUndervoltage Fault (Pre-charge Fault) | Cause: Converter pre-charge cycle failed due to low AC input voltage or internal malfunction. Remedy:
|
| E36 DriveOvertemp Fault | Cause: Converter thermal switch tripped; excessive heat exists in the power circuitry. Remedy:
|
| E37 PowerPhaseLoss Fault | Cause: One or more phases of input AC power missing, or axis enabled when main power removed. Remedy:
|
| E38 SERCOSFault (Ring Flt) | Cause: Cable disconnected; SERCOS ring not active after being active. Remedy:
|
| E39 DriveHardFault (Self Sense Flt) | Cause: Self-sensing Commutation Startup Error; motion required was obstructed. Remedy:
|
| E43 DriveEnableInput Fault | Cause: Missing Drive Enable Input Signal. Attempt to enable axis via software while hardware input was inactive, or input transitioned to inactive while enabled. Remedy:
|
| E50 SERCOSFault (Same ADDR) | Cause: Duplicate node address detected on SERCOS ring. Remedy:
|
| E54 DriveHardFault (Ifbk HW Fault) | Cause: Current feedback hardware fault detected. Remedy:
|
| E60 DriveHardFault (Unknown Axis) | Cause: Illegal ID bits detected. Remedy:
|
| E61 AuxFeedbackFault (Aux Fdbk AQB) | Cause: Auxiliary Encoder State Error; illegal transition encountered. Remedy:
|
| E62 AuxFeedbackFault (Aux Fdbk Loss) | Cause: The feedback wiring is open, shorted, or missing. Remedy:
|
| E63 AuxFeedbackNoise | Cause: Noise on auxiliary feedback cable. Recommended grounding instructions not followed. Remedy:
|
| E64 MotorFeedbackNoise | Cause: Noise on motor feedback cable. Remedy:
|
| E65 No Fault Message (Hookup Fault) | Cause: Hookup procedure failed due to motor or feedback device malfunction. Remedy:
|
| E66 No Fault Message (Atune Flt) | Cause: Autotune procedure failed due to motor or feedback device malfunction. Remedy:
|
| E67 DriveHardFault (Task init) Operating system failed | Cause: Software initialization fault detected due to hardware failure. Remedy:
|
| E68 DriveHardFault (SCANport Comm) DPI communication failed | Cause: The DPI device or cable is faulty. Remedy:
|
| E69 DriveHardFault (Objects Init) Non-volatile memory is corrupt due to control board hardware failure. | Cause: Control board hardware failure. Remedy:
|
| E70 DriveHardFault (NV Mem Init) Non-volatile memory is corrupt due to control board software error. | Cause: Control board software error. Remedy:
|
| E71 DriveHardFault (Memory Init) RAM or Flash memory validation failure | Cause: Validation failure during initialization. Remedy:
|
| E72 DriveOvertemp Fault (Drive Overtemp) Inverter thermal switch tripped | Cause:
Remedy:
|
| E73 Communicate (Backplane Comm) Power rail CAN communications failed | Cause:
Remedy:
|
| E74 DriveOvercurrent Fault (Bus OverCurrent) DC link current exceeds rating | Cause:
Remedy:
|
| E75 DriveOvervoltage Fault (Shunt Time Out) The IAM, AM, or SM has exceeded its shunt resistor continuous rating | Cause: Exceeded shunt resistor continuous rating. Remedy:
|
| E76 DriveHardFault (CAN Init) DPI hardware initialization fault detected | Cause: Control board hardware failure. Remedy:
|
| E78 DriveHardFault (SERCOS Init) Control hardware fault detected | Cause: Control hardware fault detected. Remedy:
|
| E79 DriveOvervoltage Fault (Shunt Module Flt) Shunt module fault | Cause:
Remedy:
|
| E80 DriveHardFault (CPLD Flt) Control hardware fault detected | Cause: Control hardware fault. Remedy:
|
| E81 DriveHardFault (Common Bus Flt) Follower IAM detected ac input power being applied | Cause: Follower IAM detected AC input power. Remedy:
|
| E90 DriveHardFault (Pre-charge Timeout Flt) Pre-charge resistor power exceeds the resistor rating | Cause: Pre-charge resistor power exceeds the resistor rating. Remedy:
|
| All others RESERVED | Cause: Unknown / Reserved error. Remedy:
|
How to Clear & Reset Allen-Bradley Kinetix 2000 Faults
- Studio 5000 / RSLogix 5000 Motion Instruction: Issue a Motion Axis Fault Reset (
MAFR) or Motion Group Fault Reset (MGFR) ladder instruction in your ControlLogix or CompactLogix routine to clear latched motion errors. - Motion Direct Commands (MDC): In Studio 5000 / RSLogix 5000, right-click the axis in the Controller Organizer, select Motion Direct Commands, choose Reset, and click Execute.
- SERCOS Ring Re-initialization: If optical communication is disrupted, cycle the SERCOS interface ring from Phase 0 up to Phase 4 via the 1756-M08SE / 1768-M04SE module properties to clear transient network faults.
- Safe Torque Off (STO) Interlock Check: If error code E49 is displayed, ensure the 24V DC safety circuit across the STO header terminals on the Integrated Axis Module (IAM) or Axis Module (AM) is closed and healthy prior to resetting.
- Control & Mains Power Cycle: Switch off the 230V AC incoming main line supply and 24V DC control power to the Integrated Axis Module (IAM). Wait for the front 4-character LED display and DC bus indicators to turn off completely (allow at least 5 minutes for bus capacitor discharge), then restore power.
⚠️ High-Voltage DC Bus & Servo Power Warning:
The shared power rail on the Kinetix 2000 Bulletin 2093 system distributes lethal DC bus voltages across all connected axis modules. After disconnecting line power, verify with a calibrated digital multimeter that voltage between the DC+ and DC- test points on the power rail measures strictly below 50 VDC before servicing motor power leads (U, V, W), feedback cables, or removing drive modules.