Allen-Bradley Kinetix 350 Servo Drive Fault Codes & Diagnostic Guide

Complete fault code directory, 4-character alphanumeric LED errors, CIP Motion axis exception handling, and step-by-step troubleshooting procedures for the Allen-Bradley Kinetix 350 (Bulletin 2097) servo drive series.

Single-Axis EtherNet/IP Servo Power: 0.4 to 3.0 kW (0.5 to 4.0 HP) Embedded Safe Torque Off (STO)
Power Range 0.4 – 3.0 kW (0.5 – 4.0 HP)
Supply Voltage 120V (1-Ph), 240V (1/3-Ph), 480V (3-Ph) AC
Control Modes Position, Velocity & Torque (CIP Motion)
Operator Interface 4-Character Status Display / Studio 5000

Complete Allen-Bradley Kinetix 350 Fault Code Directory

Use the search box in the table below to quickly find your fault code or exception (e.g., type E04, E18, E45, Overcurrent, or Feedback).

Fault Code and MeaningCause and Remedy
S 01
Axis enable input

Cause: Axis Enable Input is not active.



Remedy:

  • Check wiring and 24V source for drive ENABLE Input.

  • Disable enableInputChecking attribute by using a message instruction.


S 02
Motor not configured

Cause: Faulty intelligent encoder or incorrect motor file.



Remedy:

  • Cycle power or reset the drive.

  • Check that proper motor has been selected in Logix Designer Application.

  • Replace motor if faulting continues.


S 03
Feedback not configured

Cause: The associated feedback device has not been configured for use or the configuration does not match what is connected.



Remedy:

  • Verify feedback configuration matches connected device.


Sc05
Safe torque off

Cause: The safety function has disabled the power structure.



Remedy:

  • Apply 24V sources to safety circuit.

  • Use jumpers to bypass safety circuit.


F 02
Illegal Hall State

Cause: Improper connections.



Remedy:

  • Check wiring of S1, S2, and S3.

  • Check the power supply to the encoder.


F 03
Motor Overspeed

Cause: Motor speed has exceeded 125% of maximum rated speed.



Remedy:

  • Check motor wire phasing.

  • Check cables for noise.

  • Check tuning.


F 05
Motor Overtemperature

Cause: High motor ambient temperature and/or Excessive Current.



Remedy:

  • Check motor wiring at motor feedback (MF) connector.

  • Check TS+ and COM wiring.

  • Operate within (not above) the continuous torque rating for the ambient temperature.

  • Lower ambient temperature or increase motor cooling.

  • Verify that the proper motor has been selected.


F 07
Motor Thermal Protection

Cause: The machine duty cycle requires an RMS current that exceeds the continuous rating of the motor.



Remedy:

  • Change the command profile to reduce speed or increase time.


F 10
Inverter Overcurrent

Cause:

- Motor cables shorted.

- Motor winding shorted internally.

- Drive temperature too high.

- Loss of TTL signal.



Remedy:

  • Verify continuity of motor power cable and connector.

  • Disconnect motor power cables; check phase-to-phase is not open and phase-to-ground is open.

  • Check for clogged vents, defective fan, or insufficient space around unit.

  • Operate within continuous power rating.

  • Check AM+, AM-, BM+, and BM- signals.


F 11
Inverter Overtemperature

Cause: Drive fan failed, High cabinet ambient temperature, or Blocked airflow.



Remedy:

  • Replace the failed drive.

  • Check cabinet temperature (See specifications).

  • Change the command profile to reduce speed or increase time.

  • Check airflow and reroute cables away from drive system.


F 13
Inverter Thermal Protection

Cause: Machine duty cycle exceeds continuous rating OR Motor brake on.



Remedy:

  • Change the command profile to reduce speed or increase time.

  • Turn off motor brake.


F 33
Bus Undervoltage

Cause: DC bus voltage is below limits (460V system < 275V, 230V system < 137V, 120V system < 80V).



Remedy:

  • Verify the voltage level of the incoming AC power.

  • Check AC power source for glitches or line drop.

  • Install an uninterruptible power supply (UPS) on your AC input.


F 35
Bus Overvoltage

Cause: Excessive regeneration of power, external mechanical power source, or high AC line voltage.



Remedy:

  • Change the deceleration or motion profile.

  • Use a larger system (motor and drive).

  • Install shunt resistor.


F 43
Feedback Loss

Cause: The motor feedback wiring is open, shorted, or missing; OR Excessive noise on feedback signals.



Remedy:

  • Check motor encoder wiring.

  • Run Hookup test in RSLogix 5000 software.

  • Use shielded cables, route feedback away from potential noise sources.

  • Check system grounds, replace motor/encoder.

  • Verify Attribute #2703 (0=Lost, 1=Bad Hall, 2=Sin/Cos Limit, 3=Noise).


F 45
Feedback Serial Comms

Cause: Communication was not established with an intelligent encoder.



Remedy:

  • Verify motor selection.

  • Verify motor encoder wiring.


F 47
Feedback Self Test

Cause: Damage to feedback device.



Remedy:

  • Call Rockwell Automation sales representative to return the motor for repair.


F 50
Hardware Overtravel - Positive

Cause: Dedicated overtravel input is inactive.



Remedy:

  • Check wiring.

  • Verify motion profile.

  • Verify axis configuration in software.


F 51
Hardware Overtravel - Negative

Cause: Dedicated overtravel input is inactive.



Remedy:

  • Check wiring.

  • Verify motion profile.

  • Verify axis configuration in software.


F 54
Excessive Position Error

Cause: Partial loss of feedback signals, Improperly sized drive/motor, or Mechanical system out of specifications.



Remedy:

  • Check all wiring at the motor feedback (MF) connector.

  • Verify the sizing of the system.

  • Increase feed forward gain or following error limit.

  • Check position loop tuning.

  • Verify mechanical integrity of system.

  • Check motor power wiring.


F 55

Excessive Velocity Error

Cause:

  • Partial loss of feedback signals.

  • Improperly sized drive or motor.

  • Mechanical system out of specifications.




Remedy:

  • Check all wiring at motor feedback (MF) connector.

  • Increase velocity error limit or time.

  • Check velocity loop tuning.

  • Verify sizing of system.

  • Verify mechanical integrity of system within specification limits.

  • Check motor power wiring.

  • Reduce acceleration.


F 56

Overtorque Limit

Cause:

  • Overly aggressive motion profile.

  • Mechanical binding.

  • Mechanical system out of specifications.




Remedy:

  • Verify motion profile.

  • Verify that Overtorque settings are appropriate.

  • Verify sizing of system.

  • Verify torque offset.

  • Verify mechanical integrity of system within specification limits.


F 57

Undertorque Limit

Cause:

  • Improperly configured limit.

  • Improperly configured motion.

  • Improperly drive/motor sizing.

  • Mechanical system out of specifications.




Remedy:

  • Verify motion profile.

  • Verify that Overtorque settings are appropriate.

  • Verify sizing of system.

  • Verify mechanical integrity of system within specification limits.


F 61

Drive Enable Input

Cause:

  • An attempt was made to enable the axis through software while the Drive Enable hardware input was inactive.

  • The Drive Enable input transitioned from active to inactive while the axis was enabled.




Remedy:

  • Check wiring of drive enable input.

  • Check 24V source.

  • Verify that Drive Enable hardware input is active whenever the drive is enabled through the software.


F 62

Controller Initiated Exception

Cause:

User configured software overtravel.



Remedy:

  • Move axis out of soft overtravel range.

  • Clear soft overtravel fault.

  • Check soft overtravel configuration.

  • Consult controller documentation.


Fc 02

Motor Voltage Mismatch

Cause:

Wrong motor has been connected to drive.



Remedy:

Connect appropriate motor to drive.
Fc 05

Motor Encoder Battery Loss

Cause:

Weak battery or poor battery connection.



Remedy:

  • Replace battery.

  • Check battery connection.


Fc 06

Motor Encoder Battery Low

Cause:

The battery voltage on a battery-backed motor encoder is low enough such that a power loss causes the absolute position to be lost.



Remedy:

(See Fc 05: Replace battery / Check connection).
Fc 14

Excessive Current Feedback Offset

Cause:

Current in one or more phases have been lost or remains below a preset level.



Remedy:

Replace the drive.
Fc 26

Runtime Drive Error

Cause:

The drive firmware encountered an unrecoverable runtime error.



Remedy:

  • Cycle control power.

  • Replace drive.


Ic 01

Boot Block Check Sum Fault

Cause:

Faulty intelligent encoder.



Remedy:

  • Cycle power or reset the drive.

  • Replace motor if faulting continues.


Ic 02

Motor Data Range Error

Cause:

Faulty intelligent encoder or incorrect motor file.



Remedy:

  • Cycle power or reset the drive.

  • Check validity of the motion database.

  • Replace motor if faulting continues.


Ic 03

Motor Feedback Communication Startup

Cause:

  • An incorrect motor has been selected or connected.

  • Faulty wiring.




Remedy:

  • Check motor selection.

  • Check motor encoder wiring.


Ic 06

Motor Absolute Startup Speed

Cause:

Mechanical movement of the machine has caused excessive rotation of the motor during powerup (>100 rpm).



Remedy:

Allow machine motion to stop before powerup.
L001

Identity block corrupted

Cause:
Unrecoverable error while starting the drive.



Remedy:
Reload the firmware and restart the drive. If message repeats, contact Rockwell Automation technical support.
L002

Firmware file load failed

Cause:
Unrecoverable error while starting the drive.



Remedy:
Reload the firmware and restart the drive. If message repeats, contact Rockwell Automation technical support.
L004

Firmware not programmed (drive is new)

Cause:
Drive is new or memory wiped.



Remedy:
Reload the firmware and restart the drive.
L008

DSP load operation failed

Cause:
Unrecoverable error while starting the drive.



Remedy:
Reload the firmware and restart the drive. If message repeats, contact Rockwell Automation technical support.
P001 - P007

POST (Power-on Self Test) Failure

Cause:

  • P001: SDRAM test failed

  • P002: FPGA load operation failed

  • P004: DPRAM Test failed

  • P005: DSP I/F to DPram - no DSP response

  • P006: I/F to DPram failed

  • P007: Firmware file md5 test failure




Remedy:

Unrecoverable error during POST. Contact Rockwell Automation technical support to return the drive for repair.
nF 01

Control Update Fault

Cause:

  • Excessive network traffic.

  • Noisy environment.




Remedy:

  • Remove unnecessary network devices from the motion network.

  • Change the network topology so that fewer devices share common paths.

  • Use faster/higher performance network equipment.

  • Isolate signal wiring from power wiring.

  • Use shielded cables.

  • Add snubbers to power devices.


nF 02

Processor Watchdog Fault

Cause:

The watchdog-circuit monitoring processor operation detected a problem.



Remedy:

  • Recycle control power or reset the drive.

  • Replace the control module if the problem persists.


nF 03

Hardware Fault

Cause:

  • The drive has an internal hardware problem.

  • Faulty memory component (Nonvolatile write failure).




Remedy:

  • Recycle control power or reset the drive.

  • Replace the drive if problem persists.


nF 04

Data Format Error

Cause:

Faulty memory component (Data format error discovered in controller-to-drive message).



Remedy:

  • Recycle control power or reset the drive.

  • Replace the control module if problem persists.


How to Clear & Reset Kinetix 350 Servo Drive Faults

  1. Motion Axis Fault Reset (MAFR): In your Logix controller ladder logic program, trigger an execution pulse on the MAFR instruction mapped to the faulted Kinetix 350 CIP Motion axis.
  2. Studio 5000 Motion Direct Commands (MDC): Open the motion axis configuration window in Studio 5000 Logix Designer, right-click the axis, select Motion Direct Commands, choose Reset, and execute the command.
  3. Safe Torque Off (STO) Reset: If an STO safety interlock tripped (displayed as S t O or axis inhibited), restore the safety dual-channel +24V DC circuit into terminal block IOD, verify safety integrity, and issue a Motion Servo On (MSO) command.
  4. Controller / HMI Reset Tag: Program an operator reset pushbutton on your FactoryTalk View or PanelView HMI that sets a bit monitored by your Logix controller to initiate an axis fault clearing routine.
  5. Control & Mains Power Cycle: Remove both the incoming AC line power (Mains) and the auxiliary 24V DC logic control power. Wait at least 5 minutes for the DC bus capacitors to discharge below 50VDC before restoring power.
⚠️ High-Voltage Electrical Safety Warning: Dangerous residual DC bus voltages remain energized inside the Kinetix 350 power circuit after AC mains isolation. Always verify with a calibrated digital multimeter across the DC bus terminals [DC+] and [DC-] that the voltage measures strictly below 50VDC before inspecting servo motor power cables (U, V, W), encoder feedback wiring, or external shunt resistors.