Allen-Bradley Kinetix 6000 servo drive

Home / Allen-Bradley / Allen-Bradley Kinetix 6000 servo drive

Allen-Bradley Kinetix 6000 Servo Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, module LED alarm causes, and step-by-step troubleshooting procedures for the Allen-Bradley Kinetix 6000 multi-axis servo drive system (Bulletin 2094). Search or filter through the complete fault code directory below.

Multi-Axis Servo Drive (Bulletin 2094) Power: 0.5 to 45 kW (Shared Power Rail) Integrated Safe Torque Off (STO)
Power Range 0.5 – 45 kW (Modular IAM / AM)
Supply Voltage 200–240V / 380–480V (3-Phase)
Control Modes Position, Velocity & Torque (SERCOS / CIP)
Operator Interface 7-Segment Status LED / Studio 5000

Complete Allen-Bradley Kinetix 6000 Servo Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E04, E06, E19, E54, or Overcurrent).

Fault Code and MeaningCause and Remedy
N/A

Power (PWR) indicator not ON

Cause:

No AC power or auxiliary logic power OR Internal power supply malfunction.



Remedy:


  • Verify AC control power is applied to the Kinetix 6000 system.

  • Call your Rockwell Automation sales representative to return module for repair.


N/A

Motor jumps when first enabled

Cause:

Motor wiring error OR Incorrect motor chosen.



Remedy:


  • Check motor wiring.

  • Run Hookup test in the Logix Designer application.

  • Verify the proper motor is selected.


E00

BusUndervoltage Fault
(Blown fuse)

Cause:

A blown fuse was detected on the inverter PCB.



Remedy:

Call your Rockwell Automation sales representative to return module for repair.
E04

MotorOvertemp Fault
(Motor Overtemp)

Cause:

Motor thermal switch tripped due to:

  • High motor ambient temperature.

  • Excessive current.

  • Motor wiring error.

  • Incorrect motor selection.





Remedy:


  • Operate within (not above) the continuous torque rating for the ambient temperature 40 °C (104 °F) maximum.

  • Lower ambient temperature, increase motor cooling.

  • Check motor wiring at MF connector on the IAM/AM module.

  • Verify the proper motor has been selected.


E05

DriveOvercurrent Fault
(Power Fault)

Cause:

Self-protection of the Intelligent Power Module (IPM) indicating:

  • Motor cables shorted.

  • Motor winding shorted internally.

  • Kinetix 6000 drive temperature too high.

  • Operation above continuous power rating.

  • Drive has a short circuit or failed component.





Remedy:


  • Verify continuity of motor power cable and connector.

  • Disconnect motor power cables; if motor is difficult to turn by hand, consider replacing motor.

  • Check for clogged vents or defective fan.

  • Verify ambient temperature is not too high.

  • Reduce acceleration/deceleration rates.

  • Check for wire fibers between terminals or send drive for repair.


E06

HardOvertravel Fault
(+/- Hard Overtravel)

Cause:

Axis moved beyond physical travel limits or Dedicated overtravel input is inactive.



Remedy:


  • Check wiring.

  • Verify motion profile.

  • Verify axis configuration in software.


E07

MotFeedbackFault
(Motor Feedback Loss)

Cause:

The feedback wiring is open, shorted, or missing.



Remedy:


  • Check motor encoder wiring.

  • Run Hookup test in the Logix Designer application.


E09

BusUndervoltage Fault
(Bus Undervoltage)

Cause:

DC bus voltage fell below limits:

  • DC bus < 275V (460V system).

  • DC bus < 137V (230V system).





Remedy:


  • Verify voltage level of the incoming AC power.

  • Check AC power source for glitches or line drop.

  • Install an uninterruptible power supply (UPS) on your AC input.

  • Disable follower axis before removing power.


E10

DriveOvervoltage Fault
(Bus Overvoltage)

Cause:

The DC bus voltage is above limits due to excessive regeneration of power.



Remedy:


  • Change the deceleration or motion profile.

  • Use a larger system (motor and Kinetix 6000 drive).

  • Install shunt module.

  • Verify input is within specifications.


E11

MotFeedbackFault
(Illegal Hall State)

Cause:

State of Hall feedback inputs is incorrect due to improper connections.



Remedy:


  • Verify the Hall wiring at the MF connector on the IAM/AM module.

  • Verify 5V power supply to the encoder.


E16

Softovertravel Fault
(+/- Software Overtravel)

Cause:

Axis position exceeded maximum software setting.



Remedy:


  • Verify motion profile.

  • Verify overtravel settings are appropriate.


E18

OverSpeedFault
(Overspeed Fault)

Cause:

Motor speed has exceeded 150% of maximum rated speed.



Remedy:


  • Check cables for noise.

  • Check tuning.


E19

PositionErrorFault
(Follow Error)

Cause:

Position error limit was exceeded.



Remedy:


  • Increase the feed forward gain.

  • Increase following error limit or time.

  • Check position loop tuning.

  • Verify sizing of system.

  • Verify mechanical integrity of system within specification limits.


E20

MotFeedbackFault
(Mtr Fdbk AQB)

Cause:

The motor encoder encountered an illegal transition (Motor Encoder State Error).



Remedy:


  • Use shielded cables with twisted pair wires.

  • Route the feedback away from potential noise sources.

  • Check the system grounds.

  • Replace the motor/encoder.


E21

AuxFeedbackFault
(Aux Feedback Comm)

Cause:

Communication was not established with an intelligent encoder.



Remedy:

Verify auxiliary encoder wiring.
E30

MotFeedbackFault
(Motor Feedback Comm)

Cause:

Communication was not established with an intelligent encoder.



Remedy:


  • Verify motor selection.

  • Verify the motor supports automatic identification.

  • Verify motor encoder wiring.


E31

DriveHardFault

Cause:

Excessive motor shaft movement during power up, Sercos ring phase-up, or after a fault reset.



Remedy:

Make sure there is no motor shaft movement during power up, Sercos ring phase-up, or during a fault reset.
E34

GroundShortFault
(Ground Fault)

Cause:

Excessive ground current detected due to:

  • Wiring error.

  • Motor internal ground short.

  • Internal malfunction.

  • Grounded control power terminal (230V systems only).





Remedy:


  • Check motor/input power wiring.

  • Replace motor.

  • Disconnect motor power cable to isolate; if fault remains, call sales representative.

  • Remove ground from control power input.


E35

DriveUndervoltage Fault
(Precharge Fault)

Cause:

Converter precharge cycle failed due to Low AC input voltage or Internal malfunction.



Remedy:


  • Check input AC voltage on all phases.

  • Call your sales representative.


E36

DriveOvertemp Fault
(System Overtemperature)

Cause:

Converter thermal switch tripped; Excessive heat exists in the power circuitry.



Remedy:


  • Reduce acceleration rates.

  • Reduce duty cycle (ON/OFF) of commanded motion.

  • Use larger IAM converter module.

  • Check for clogged vents or defective fan.


E37

PowerPhaseLoss Fault
(Phase Loss Flt)

Cause:

One or more phases of the input AC power is missing OR Axis was enabled when main power was removed.



Remedy:


  • Check input AC voltage on all phases.

  • Disable axis before removing power.


E38

SercosFault
(Sercos Ring Flt)

Cause:

Cable disconnected; The Sercos ring is not active after being active.



Remedy:

Check that fiber-optic cable is present and connected properly.
E39

DriveHardFault
(Self Sense Flt)

Cause:

Motion required for self-sensing start-up commutation was obstructed.



Remedy:


  • Verify that there are no impediments to motion at startup (hard limits).

  • Increase self-sensing current if high friction/load exists.

  • Check motor or encoder wiring.


E43

DriveEnableInput Fault
(Drive Enable Flt)

Cause:

Missing Drive Enable Input Signal; Attempt to enable axis while HW input inactive.



Remedy:


  • Disable the Drive Enable Input fault.

  • Verify that Drive Enable hardware input is active whenever the drive is enabled through software.


E49

DriveHardFault
(Safe-off HW Flt)

Cause:

Safe torque-off function mismatch:

  • Loose wiring at STO connector.

  • Cable/header not seated properly.

  • Safe torque-off circuit missing +24V DC.





Remedy:


  • Verify wire terminations, cable/header connections, and +24V.

  • Reset error and run proof test.

  • If error persists, return the drive to Rockwell Automation.


E50

SercosFault
(Sercos Same ADDR)

Cause:

Duplicate node address detected on Sercos ring.



Remedy:

Verify that each Sercos drive is assigned a unique node address.
E54

DriveHardFault
(Ifbk HW Fault)

Cause:

Current feedback hardware fault detected.



Remedy:

Replace the module.
E55

OverSpeedFault

Cause:

Motor has exceeded velocity error limit.



Remedy:

Check the cables for noise.
E60

DriveHardFault
(Unknown Axis)

Cause:

Illegal ID bits detected.



Remedy:

Replace the module.
E61

AuxFeedbackFault
(Aux Fdbk AQB)

Cause:

The auxiliary encoder encountered an illegal transition.



Remedy:


  • Use shielded cables with twisted pair wires.

  • Route the feedback away from potential noise sources.

  • Check the system grounds.

  • Replace the motor/encoder.


E62

AuxFeedbackFault
(Aux Fdbk Loss)

Cause:

The feedback wiring is open, shorted, or missing.



Remedy:

Check the motor feedback cable connectors/wiring to the IAM/AM module and servo motor.
E63

AuxFeedbackNoise
(Aux Fdbk Noise)

Cause:

Noise on auxiliary feedback cable; Grounding instructions not followed.



Remedy:


  • Verify grounding.

  • Route feedback cable away from noise sources.

  • Refer to System Design Manual GMC-RM001.


E64

MotorFeedbackNoise
(Mtr Fdbk Noise)

Cause:

Noise on motor feedback cable; Grounding instructions not followed.



Remedy:


  • Verify grounding.

  • Route feedback cable away from noise sources.

  • Refer to System Design Manual GMC-RM001.


E65

No Fault Message
(Hookup Fault)

Cause:

Hookup procedure failed; Motor or feedback device malfunction.



Remedy:


  • Check motor power/feedback wiring.

  • Refer to on-screen message for resolution.


E66

No Fault Message
(Atune Flt)

Cause:

Autotune procedure failed; Motor or feedback device malfunction.



Remedy:


  • Check motor power/feedback wiring.

  • Refer to on-screen message for resolution.

  • Perform Hookup in the Logix Designer application.


E67

DriveHardFault
(Task init)

Cause:

Software initialization fault detected due to hardware failure.



Remedy:


  • Cycle power.

  • If fault persists, replace module.


E68

DriveHardFault
(SCANport™ Comm)

Cause:

The DPI device or cable is faulty.



Remedy:

Check DPI connections.
E69

DriveHardFault
(Objects Init)

Cause:

Nonvolatile memory is corrupt due to control board hardware failure.



Remedy:

Load default parameters, save to nonvolatile memory, and recycle power or reset the drive.
E70

DriveHardFault
(NV Mem Init)

Cause:

Nonvolatile memory is corrupt due to control board software error.



Remedy:

Load default parameters, save to nonvolatile memory, and recycle power or reset the drive.
E71

DriveHardFault
(Memory Init)

Cause:

RAM or nonvolatile memory validation failure.



Remedy:


  • Cycle power.

  • If fault persists, replace module.


E72

DriveOvertemp Fault
(Drive Overtemp)

Cause:

Inverter thermal switch tripped:

  • The IAM or an AM module fan failed.

  • The cabinet ambient temperature is above rating.

  • The machine duty cycle requires an RMS current exceeding continuous rating.

  • The airflow access to the Kinetix 6000 system is limited or blocked.





Remedy:


  • Replace the failed module.

  • Check the cabinet temperature.

  • Change the command profile to reduce speed or increase time.

  • Check airflow and re-route cables away from the Kinetix 6000 system.


E73

Communicate
(Backplane Comm)

Cause:

Power rail CAN communication failed OR Power rail connection shorted/open.



Remedy:


  • Check module for proper mount.

  • Check power rail and module for foreign objects.


E74

DriveOvercurrent Fault
(Bus OverCurrent)

Cause:

DC link current exceeds rating due to Motor/transmission malfunction OR IAM module not sized properly.



Remedy:


  • Check for proper motor sizing.

  • Check/replace transmission device.

  • Check/replace motor.

  • Check for proper IAM module sizing.

  • Install larger kW rated IAM module.


E75

DriveOvervoltage Fault
(Shunt Time Out)

Cause:

The IAM/AM module, or shunt module has exceeded its shunt resistor continuous rating.



Remedy:


  • Use a properly sized shunt or modify duty cycle of the application.

  • System uses internal shunt and requires external shunt for additional capacity.


E76

DriveHardFault
(CAN Init)

Cause:

Control board hardware failure (DPI hardware initialization fault).



Remedy:


  • Reset System.

  • If fault persists, replace system module.


E77

DriveHardFault
(Module Mismatch)

Cause:

Either 230V AM module is installed on power rail with 460V IAM module, or 460V AM module is installed on power rail with 230V IAM module.



Remedy:

Replace mismatched module.
E78

DriveHardFault
(Sercos Init)

Cause:

Control hardware fault detected.



Remedy:


  • Cycle power.

  • If fault persists, replace module.


E79

DriveOvervoltage Fault
(Shunt Module Flt)

Cause:


  • Over-temperature fault indicator on Bulletin 2094 shunt module is steady red.

  • Shunt-fault indicator on Bulletin 2094 shunt module is steady red.

  • Bulletin 2094 shunt module is missing from power rail.





Remedy:


  • Refer to manual Table 108 or 109.

  • Install missing module on power rail.

  • Fill empty slot with slot-filler module.


E80

DriveHardFault
(CPLD Flt)

Cause:

Control hardware fault detected.



Remedy:

Replace module.
E81

DriveHardFault
(Common Bus Flt)

Cause:

Follower IAM module detected AC input power being applied.



Remedy:

Remove AC input power connections from follower IAM module.
E90

DriveHardFault
(Precharge Timeout Flt)

Cause:

Precharge resistor power exceeds the resistor rating.



Remedy:

Wait for resistor to cool.
E95

IPIMFault
(IPIM Module Flt)

Cause:

A fault has occurred in one or more IPIM modules on the power rail.



Remedy:

Refer to the troubleshooting chapter in the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003.

How to Clear & Reset Allen-Bradley Kinetix 6000 Drive Faults

  1. Motion Axis Fault Reset (MAFR / MGFR): In Studio 5000 / RSLogix 5000, trigger a Motion Axis Fault Reset (MAFR) instruction on the faulted servo axis, or execute a Motion Group Fault Reset (MGFR) to clear all coordinated axes simultaneously.
  2. Motion Direct Commands: Open your Logix controller project offline or online, right-click the designated motion axis in the Controller Organizer, select Motion Direct Commands, and click “Reset Axis Fault”.
  3. Safe Torque Off (STO) Reset: For safety-related error codes (such as code E54), inspect the emergency stop string, verify +24VDC is restored across both safety input channels (connector IED/ST), and cycle the safety circuit reset contact.
  4. SERCOS / Network Ring Reset: If fiber-optic ring alarms appear (E90 through E99), inspect cable bend radiuses and transmitter/receiver integrity, then re-initialize the SERCOS ring sync via controller run-mode transition.
  5. Complete Power Cycle: Disconnect the 3-phase AC main supply and 24VDC logic control power to the Integrated Axis Module (IAM). Wait until all module 7-segment displays and the bus LED extinguish completely (allow at least 5 minutes for the shared power rail capacitors to bleed down safely below 50VDC), then re-apply power.
⚠️ High-Voltage Electrical Safety Warning: The Kinetix 6000 system utilizes a shared DC bus power rail connecting the IAM and multiple AM modules. Always verify with a calibrated digital multimeter that the intermediate DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] on the power rail or shunt module before servicing motor connections, removing axis modules, or touching motor power terminals U, V, and W.