Allen-Bradley Kinetix 7000 Servo Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, E-series error diagnostics, root causes, and troubleshooting procedures for Rockwell Automation Allen-Bradley Kinetix 7000 high-power servo drives (Bulletin 2099). Search or filter through the complete diagnostic directory below.
Power Range
22 – 149 kW (30 – 200 HP)
Supply Voltage
380–480V AC (3-Phase)
Control Platform
SERCOS Multi-Axis Motion Control
Operator Interface
4-Character Scrolling LED / Studio 5000
Complete Allen-Bradley Kinetix 7000 Fault Code Directory
Use the search box in the table below to quickly find your fault code (e.g., search E04, E14, E18, or Feedback).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| No Error Code Displayed Power (PWR) indicator not ON | Cause: No AC power or auxiliary logic power. Remedy:
Cause: Internal power supply malfunction. Remedy:
|
| No Error Code Displayed Motor jumps when first enabled | Cause: Motor wiring error. Remedy:
Cause: Incorrect motor chosen. Remedy:
|
| No Error Code Displayed Digital I/O not working correctly | Cause: I/O power supply disconnected. Remedy:
|
| E04 MotorOvertemp Fault (Motor thermal switch tripped) | Cause: High motor ambient temperature and/or excessive current. Remedy:
Cause: Motor wiring error. Remedy:
Cause: Incorrect motor selection. Remedy:
Cause: Mechanical failure. Remedy:
|
| E05 DriveOvercurrent Fault (Inverter Overcurrent IOC) | Cause: Motor cables shorted. Remedy:
Cause: Motor winding shorted internally. Remedy:
Cause: Drive temperature too high. Remedy:
Cause: Operation above continuous power rating and/or product environmental ratings. Remedy:
Cause: Kinetix 7000 drive has a short-circuit, overcurrent, or failed component. Remedy:
|
| E06 HardOvertravelFault | Cause: Axis moved beyond the physical travel limits in the positive/negative direction. Dedicated overtravel input is inactive. Remedy:
|
| E07 MotFeedbackFault | Cause: The feedback wiring is open, shorted, or missing. Remedy:
|
| E09 BusUndervoltageFault | Cause: Bus voltage for 460V system is below 275V DC (With three-phase power present). Remedy:
Cause: Bus voltage is at least 180V DC below the precharge level of 323… 525V DC. Remedy:
Cause: One of more phases of AC input power failed. Remedy:
|
| E10 DriveOvervoltageFault (DC bus voltage is above limits) | Cause: Excessive regeneration of power. Remedy:
Cause: Bus voltage for 460V system is over 800V DC. Remedy:
|
| E11 MotFeedbackFault | Cause: Improper connection (State of Hall feedback inputs is incorrect). Remedy:
|
| E16 SoftOvertravelFault | Cause: Axis moved beyond the software axis position in either the positive or negative direction. Remedy:
|
| E18 OverSpeedFault | Cause: Motor speed has exceeded 150% of maximum rated speed. The 100% trip point is dictated by the lesser of the user velocity limits or the motor rated base speed. Remedy:
|
| E19 PositionErrorFault | Cause: Position error limit exceeded. Remedy:
|
| E20 MotFeedbackFault | Cause: The motor encoder encountered an illegal transition (Motor encoder state error). Remedy:
|
| E21 AuxFeedbackFault | Cause: Communication was not established with an intelligent encoder. Remedy:
|
| E23 DriveOvertempFault (IPM thermal protection fault) | Cause: The internal filter protecting the drive from overheating has tripped. Remedy:
|
| E30 MotFeedbackFault | Cause: Communication was not established with an intelligent encoder. Remedy:
|
| E34 GroundShortFault (Excessive ground current) | Cause: Wiring error. Remedy:
Cause: Motor internal ground short. Remedy:
Cause: Internal malfunction. Remedy:
|
| E35 DriveUndervoltageFault (Converter precharge cycle failed) | Cause: Low AC input voltage. Remedy:
Cause: Internal malfunction. Remedy:
|
| E37 PowerPhaseLossFault One or more phases of the AC input power is missing. | Cause: AC input power failure or fuse issue. Remedy:
|
| E38 SercosFault The Sercos ring is not active after being active and operational. | Cause: Cable disconnected. Remedy:
|
| E39 DriveHardFault Self-sensing Commutation Startup Error. | Cause: Obstruction prevents motion required for self-sensing startup commutation. Remedy:
|
| E43 DriveEnableInputFault Missing Drive Enable input signal. | Cause:
Remedy:
|
| E49 DriveHardFault Safe Torque Off function mismatch. Drive will not permit motion. | Cause:
Remedy:
|
| E50 SercosFault Duplicate node address detected on Sercos ring. | Cause: Duplicate addressing configuration. Remedy:
|
| E54 DriveHardFault Excessive Current Feedback Offset. | Cause: Defective current feedback sensing. Remedy:
|
| E61 AuxFeedbackFault Auxiliary Encoder State Error. | Cause: The auxiliary encoder encountered an illegal transition. Remedy:
|
| E62 AuxFeedbackFault The feedback wiring is open, shorted, or missing. | Cause: Feedback wiring issues. Remedy:
|
| E63 AuxFeedbackNoise Noise on auxiliary feedback cable. | Cause: Recommended grounding, per installation instructions, has not been followed. Remedy:
|
| E64 MotorFeedbackNoise Noise on motor feedback cable. | Cause: Recommended grounding, per installation instructions, has not been followed. Remedy:
|
| E65 No Fault Message Hookup procedure failed. | Cause: Motor or feedback device malfunction. Remedy:
|
| E66 No Fault Message Autotune procedure failed. | Cause: Motor or feedback device malfunction. Remedy:
|
| E67 DriveHardFault Operating system failed. | Cause: Software initialization fault detected due to hardware failure. Remedy:
|
| E68 DriveHardFault DPI™ communication failed. | Cause: The DPI device or cable is faulty. Remedy:
|
| E69 DriveHardFault Nonvolatile memory is corrupt due to control board hardware failure. | Cause: Control board hardware failure. Remedy:
|
| E70 DriveHardFault Nonvolatile memory is corrupt due to control board software error. | Cause: Control board software error. Remedy:
|
| E71 DriveHardFault RAM or flash memory validation failure. | Cause: Memory validation failure. Remedy:
|
| E72 DriveOvertemp Fault Inverter thermal switch tripped. | Cause:
Remedy:
|
| E76 DriveHardFault DPI hardware initialization fault detected. | Cause: Control board hardware failure. Remedy:
|
| E78 DriveHardFault (Sercos Init) Control hardware fault detected. | Cause: Control hardware fault. Remedy:
|
| E80 DriveHardFault (CPLD Flt) Control hardware fault detected. | Cause: A-to-D conversion state machine error. Remedy:
|
| E109 IGBT_TempFault Junction temperature of Insulated Gate Bipolar Transistor exceeded. | Cause: Drive sizing or load issue. Remedy:
|
| E110 EEPROM_Fault EEPROM failed. | Cause: EEPROM data corrupted or bus not calibrated. Remedy:
|
| E111 Regen_PS_OK The Regen_OK signal is missing at pins 7 and 8 of the GPIO connector. | Cause: Signal missing at GPIO connector. Remedy:
|
How to Clear & Reset Allen-Bradley Kinetix 7000 Faults
- Studio 5000 / RSLogix 5000 Motion Instruction: Issue a Motion Axis Fault Reset (
MAFR) or Motion Group Fault Reset (MGFR) ladder instruction in your ControlLogix routine to clear latched drive errors. - Motion Direct Commands (MDC): In Studio 5000 / RSLogix 5000, right-click the designated motion axis in the Controller Organizer, select Motion Direct Commands, choose Reset, and click Execute.
- SERCOS Ring Re-synchronization: If optical communication faults occur (Phase ring disruption), cycle the SERCOS interface ring state through the 1756-M08SE / 1756-M16SE motion module properties from Phase 0 to Phase 4 to clear communication trip flags.
- Safe Torque Off (STO) Circuit Check: If error code E49 is active, verify that the 24V DC redundant safety interlock inputs on the STO terminal header are energized and healthy before attempting a fault reset.
- Mains 480V & Auxiliary Control Power Cycle: De-energize the incoming 3-phase 480V AC mains disconnect and the separate 120V/230V AC control power supply. Wait until the front scrolling LED and internal DC bus status indicator lamps extinguish completely (allow at least 10 minutes for capacitor bank discharge), then restore power.
⚠️ Extreme High-Voltage Stored Energy Warning:
Kinetix 7000 high-power servo drives contain large capacitor banks that retain lethal DC bus voltages exceeding 650 to 750 VDC after mains disconnect. Wait a minimum of 10 to 15 minutes after power removal, and use a calibrated 1000V DC multimeter across terminals DC+ and DC- to confirm the voltage has dropped strictly below 50 VDC before servicing high-power motor leads (U, V, W), dynamic brake connections, or opening internal chassis panels.