Allen-Bradley PowerFlex 4 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Allen-Bradley PowerFlex 4 compact AC drive series. Search or filter through the complete fault code directory below.
Power Range
0.2 – 3.7 kW (0.25 – 5 HP)
Supply Voltage
115V, 230V, 460V (1-Ph & 3-Ph)
Control Modes
Volts per Hertz (V/Hz)
Operator Interface
4-Digit Display / RS-485 DSI Port
Complete Allen-Bradley PowerFlex 4 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type F2, F4, F13, or Overload).
| Fault Codes | Cause & Solutions |
|---|---|
| F2 Auxiliary Input | Cause : Auxiliary input interlock is open. Solution: - Check remote wiring. - Verify communications programming for intentional fault. |
| F3 Power Loss | Cause: Excessive DC Bus voltage ripple. Solution: - Monitor the incoming AC line for low voltage or line power interruption. - Check input fuses. - Reduce load. |
| F4 UnderVoltage | Cause: DC bus voltage fell below the min value. Solution: Monitor the incoming AC line for low voltage or line power interruption. |
| F5 OverVoltage | Cause: DC bus voltage exceeded max value. Solution: - Monitor the AC line for high line voltage or transient conditions. - Bus overvoltage can also be caused by motor regeneration. - Extend the decel time or install dynamic brake option. |
| F6 Motor Stalled | Cause: Drive is unable to accelerate or decelerate motor. Solution: - Increase P039…A067 [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A089 [Current Limit]. - Check for overhauling load. |
| F7 Motor Overload | Cause: Internal electronic overload trip. Solution: - An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current]. - Verify A084 [Boost Select] setting |
| F8 Heatsink OvrTmp | Cause: Heatsink/Power Module temperature exceeds a predefined value. Solution: - Check for blocked or dirty heatsink fins. Verify that ambient temperature has not exceeded the rated ambient temperature. - Check fan. |
| F12 HW OverCurrent | Cause: The drive output current has exceeded the hardware current limit. Solution: - Check programming. - Check for excess load, improper A084 [Boost Select] setting, DC brake volts set too high or other causes of excess current. |
| F13 Ground Fault | Cause: A current path to earth ground has been detected at one or more of the drive output terminals. Solution: - Check the motor and external wiring to the drive output terminals for a grounded condition. |
| F33 Auto Rstrt Tries | Cause: Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of A092 [Auto Rstrt Tries]. Solution: Correct the cause of the fault and manually clear. |
| F38 Phase U to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F39 Phase V to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F40 Phase W to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F41 Phase UV Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F42 Phase UW Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F43 Phase VW Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F48 Params Defaulted | Cause: The drive was commanded to write default values to EEPROM. Solution: - Clear the fault or cycle power to the drive. - Program the drive parameters as needed. |
| F63 SW OverCurrent | Cause: Programmed A098 [SW Current Trip] has been exceeded. Solution: - Verify connections between motor and load. - Check load requirements and A098 [SW Current Trip] setting. |
| F64 Drive Overload | Cause: Drive overload rating has been exceeded. Drive rating of 150% for 1 minute or 200% for 3 seconds has been exceeded. Solution: Reduce load or extend Accel Time. |
| F70 Power Unit | Cause: Failure has been detected in the drive power section. Solution: - Check that max ambient temperature has not been exceeded. - Cycle power. - Replace drive if fault cannot be cleared. |
| F71 Net Loss | Cause: The communication network has faulted. Solution: - Cycle power. - Check communications cabling. - Check network adapter setting. - Check external network status. |
| F81 Comm Loss | Cause: RS-485 (DSI) port stopped communicating. Solution: 1. If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port expander, adapters or complete drive as required. 2. Check connection. 3. An adapter was intentionally disconnected. 4. Turn off using A105 [Comm Loss Action]. |
| F100 Parameter Chksum | Cause: The checksum read from the board does not match the checksum calculated. Solution: Set P041 [Reset To Defalts] to option 1 “Reset Defaults”. |
| F122 I/O Board Fail | Cause: Failure has been detected in the drive control and I/O section. Solution: - Cycle power. - Replace drive if fault cannot be cleared. |
How to Clear & Reset Allen-Bradley PowerFlex 4 Drive Faults
- Keypad Stop/Reset: Press the red Stop button on the integral keypad faceplate. If parameter P037 [Stop Mode] is set to a standard stop function, pressing Stop clears active resettable faults.
- Digital Input Reset (Clear Fault): Momentarily trigger terminal 05 or 06 (DigIn TermBlk 05 / 06) programmed to option 4 (“Clear Fault”) via parameters A051 [Digital In1 Sel] or A052 [Digital In2 Sel].
- Serial / DSI Communication: Send a stop/reset control word command over the integral RS-485 DSI port using Connected Components Workbench (CCW), DriveExecutive, or PLC serial logic.
- Auto-Restart Routine: For non-critical transient faults, configure parameters A092 [Auto Rstrt Tries] and A093 [Auto Rstrt Delay] to allow automated reset attempts after a trip.
- Power Cycle: Disconnect AC line power to the unit. Wait until the LED display and status indicators turn completely dark (allow at least 3 minutes for bus capacitors to discharge safely), then re-apply input power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] (or dynamic brake terminals BR+ and BR-) before inspecting wiring, replacing control terminal jumpers, or touching output terminals U/T1, V/T2, and W/T3 on the PowerFlex 4 drive.