Allen-Bradley PowerFlex 400 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, HVAC fan and pump trip alarms, root causes, and troubleshooting procedures for Rockwell Automation Allen-Bradley PowerFlex 400 drives. Search or filter through the complete fault directory below.
Power Range
2.2 – 250 kW (3 – 350 HP)
Supply Voltage
200–240V / 380–480V AC (3-Phase)
Control Modes
V/Hz (Custom Variable Torque)
Operator Interface
Multi-Line Alphanumeric LCD Keypad
Complete Allen-Bradley PowerFlex 400 Fault Code Directory
Use the search box in the table below to quickly find your fault code (e.g., search F004, F005, F012, or OverCurrent).
| Fault Codes | Cause & Solutions |
|---|---|
| F2 Auxiliary Input | Cause : Auxiliary input interlock is open. Solution: - Check remote wiring. - Verify communications programming for intentional fault. |
| F3 Power Loss | Cause: Excessive DC Bus voltage ripple. Solution: - Monitor the incoming AC line for low voltage or line power interruption. - Check input fuses. - Reduce load. |
| F4 UnderVoltage | Cause: DC bus voltage fell below the min value. Solution: Monitor the incoming AC line for low voltage or line power interruption. |
| F5 OverVoltage | Cause: DC bus voltage exceeded max value. Solution: - Monitor the AC line for high line voltage or transient conditions. - Bus overvoltage can also be caused by motor regeneration. - Extend the decel time or install dynamic brake option. |
| F6 Motor Stalled | Cause: Drive is unable to accelerate or decelerate motor. Solution: - Increase P039...A147 [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A179 [Current Limit 1]. - Check for overhauling load. |
| F7 Motor Overload | Cause: Internal electronic overload trip. Solution: - An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current]. - Verify A170 [Boost Select] setting. |
| F8 Heatsink OvrTmp | Cause: Heatsink/Power Module temperature exceeds a predefined value. Solution: - Check for blocked or dirty heatsink fins. Verify that ambient temperature has not exceeded the rated ambient temperature. - Check fan. |
| F12 HW OverCurrent | Cause: The drive output current has exceeded the hardware current limit. Solution: - Check programming. - Check for excess load, improper A170 [Boost Select] setting, DC brake volts set too high or other causes of excess current. |
| F13 Ground Fault | Cause: A current path to earth ground has been detected at one or more of the drive output terminals. Solution: - Check the motor and external wiring to the drive output terminals for a grounded condition. |
| F15 Load Loss | Cause: Output current has dropped below the level set in A184 [Load Loss Level]. Solution: - Check for load loss (i.e., a broken belt). |
| F17 Input Phase Loss | Cause: Excessive DC bus ripple voltage detected. See d329 [DC Bus Ripple V]. Solution: - Check incoming power for a missing phase or blown fuse. If drive is used intentionally with single phase input, apply output derating to 35% actual drive rating. |
| F29 Analog Input Loss | Cause: An analog input is configured to fault on signal loss. A signal loss has occurred. - Configure with T072 [Anlalog In Loss]. Solution: - Check parameters. - Check for broken/loose connections at inputs. |
| F32 Fan Fdbck Loss | Cause: A loss of cooling fan feedback has been detected. (Frames E and F only) Solution: - Make sure cooling fans are clear of debris and spinning freely. Replace fan if necessary. |
| F33 Auto Rstrt Tries | Cause: Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of A163 [Auto Rstrt Tries]. Solution: - Correct the cause of the fault and manually clear. |
| F38 Phase U to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F39 Phase V to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F40 Phase W to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F41 Phase UV Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F42 Phase UW Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F43 Phase VW Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F48 Params Defaulted | Cause: The drive was commanded to write default values to EEPROM. Solution: - Clear the fault or cycle power to the drive. - Program the drive parameters as needed. |
| F63 SW OverCurrent | Cause: Programmed A183 [SW Current Trip] has been exceeded. Solution: - Check load requirements and A183 [SW Current Trip] setting. |
| F64 Drive Overload | Cause: Drive rating of 110% for 1 minute or 150% for 3 seconds has been exceeded. Solution: Reduce load or extend Accel Time. |
| F70 Power Unit | Cause: Failure has been detected in the drive power section. Solution: - Check that max ambient temperature has not been exceeded. - Cycle power. - Replace drive if fault cannot be cleared. |
| F71 Net Loss | Cause: The communication network has faulted. Solution: - Cycle power. - Check communications cabling. - Check network adapter setting. - Check external network status. |
| F81 Comm Loss | Cause: RS485 (DSI) port stopped communicating. Solution: - Check RS485 wiring connection. - Check if a communications adapter or HIM was disconnected. - Increase C106 [Comm Loss Time] to an appropriate time for application. - Change C105 [Comm Loss Action] to a value other than “0” (fault), if appropriate for the application. |
| F94 Function Loss | Cause: P036 [Start Source] is set to setting 6. - The input to terminal 01 has been opened. Solution: - Close input to terminal 01 and re- start the drive. |
| F100 Parameter Chksum | Cause: The checksum read from the board does not match the checksum calculated. Solution: Set P041 [Reset To Defalts] to option 1 “Reset Defaults”. |
| F122 I/O Board Fail | Cause: Failure has been detected in the drive control and I/O section. Solution: - Cycle power. - Replace drive if fault cannot be cleared. |
How to Clear & Reset Allen-Bradley PowerFlex 400 Faults
- Keypad Reset: Press the red Stop / Reset key on the multi-line LCD control panel. Ensure the run command from BAS/HVAC controls is removed if parameter P037 [Stop Mode] requires a stop cycle before restart.
- Digital Input Reset: If one of the digital inputs (terminals 05 through 08, configured in parameters A051 – A054) is set to Option 7 “Clear Fault”, momentary contact closure to digital common (terminal 04) will reset active faults.
- Building Automation System (BAS) Reset: Clear faults remotely by setting the Fault Reset command bit in the control word via embedded RS-485 protocols (Modbus RTU, Johnson Controls Metasys N2, or Siemens FLN P1).
- Connected Components Workbench (CCW): Connect via the RJ45 DSI communication port using a 1203-USB serial converter, launch CCW or DriveExplorer, and select “Clear Faults” in the online diagnostics menu.
- Main AC Power Cycle: Disconnect the incoming 3-phase mains disconnect switch. Wait for the LCD screen backlight and all status LEDs to extinguish completely (allow at least 5 minutes for bus capacitors to discharge), then restore power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous electrical energy remains stored in the intermediate DC bus capacitors after line power is disconnected. Using a calibrated digital multimeter set to 1000V DC, verify that voltage across terminals +DC and -DC measures strictly below 50 VDC before servicing power wiring, motor leads, or internal drive assemblies.