Allen-Bradley PowerFlex 4M Drive Fault Codes & Diagnostic Guide
Complete fault code list, trip indicators, root causes, and troubleshooting procedures for the Rockwell Automation Allen-Bradley PowerFlex 4M compact variable frequency drive. Use the searchable directory below to diagnose and clear drive faults.
Power Range
0.2 – 11 kW (0.25 – 15 HP)
Supply Voltage
120V / 240V / 480V AC
Control Modes
Volts per Hertz (V/Hz)
Operator Interface
4-Digit LED Display & Potentiometer
Complete Allen-Bradley PowerFlex 4M Fault Code Directory
Use the search box in the table below to quickly find your fault code (e.g., search F004, F005, F012, or OverCurrent).
| Fault Codes | Cause & Solutions |
|---|---|
| F2 Auxiliary Input | Cause : Auxiliary input interlock is open. Solution: - Check remote wiring. - Verify communications programming for intentional fault. |
| F3 Power Loss | Cause: Excessive DC Bus voltage ripple. Solution: - Monitor the incoming AC line for low voltage or line power interruption. - Check input fuses. - Reduce load. |
| F4 UnderVoltage | Cause: DC bus voltage fell below the min value. Solution: Monitor the incoming AC line for low voltage or line power interruption. |
| F5 OverVoltage | Cause: DC bus voltage exceeded max value. Solution: - Monitor the AC line for high line voltage or transient conditions. - Bus overvoltage can also be caused by motor regeneration. - Extend the decel time or install dynamic brake option. |
| F6 Motor Stalled | Cause: Drive is unable to accelerate or decelerate motor. Solution: - Increase P109 and/or A402 [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A441 [Current Limit]. - Check for overhauling load. |
| F7 Motor Overload | Cause: Internal electronic overload trip. Solution: - An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P103 [Motor OL Current]. - Verify A453 [Boost Select] setting. |
| F8 Heatsink OvrTmp | Cause: Heatsink/Power Module temperature exceeds a predefined value. Solution: - Check for blocked or dirty heatsink fins. Verify that ambient temperature has not exceeded the rated ambient temperature. - Check fan. |
| F12 HW OverCurrent | Cause: The drive output current has exceeded the hardware current limit. Solution: - Check programming. - Check for excess load, improper A453 [Boost Select] setting, DC brake volts set too high or other causes of excess current. |
| F13 Ground Fault | Cause: A current path to earth ground has been detected at one or more of the drive output terminals. Solution: - Check the motor and external wiring to the drive output terminals for a grounded condition. |
| F33 Auto Rstrt Tries | Cause: Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of A451 [Auto Rstrt Tries]. Solution: Correct the cause of the fault and manually clear. |
| F38 Phase U to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F39 Phase V to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F40 Phase W to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F41 Phase UV Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F42 Phase UW Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F43 Phase VW Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F48 Params Defaulted | Cause: The drive was commanded to write default values to EEPROM. Solution: - Clear the fault or cycle power to the drive. - Program the drive parameters as needed. |
| F63 SW OverCurrent | Cause: Programmed A448 [SW Current Trip] has been exceeded. Solution: - Verify connections between motor and load. - Check load requirements and A448 [SW Current Trip] setting. |
| F64 Drive Overload | Cause: Drive overload rating has been exceeded. Drive rating of 150% for 1 minute or 200% for 3 seconds has been exceeded. Solution: Reduce load or extend Accel Time. |
| F70 Power Unit | Cause: Failure has been detected in the drive power section. Solution: - Check that max ambient temperature has not been exceeded. - Cycle power. - Replace drive if fault cannot be cleared. |
| F71 DSI Net Loss | Cause: The communication network has faulted. Solution: - Cycle power. - Check communications cabling. - Check network adapter setting. - Check external network status. |
| F81 Comm Loss | Cause: RS-485 (DSI) port stopped communicating. Solution: 1. If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port expander, adapters or complete drive as required. 2. Check connection. 3. An adapter was intentionally disconnected. 4. Turn off using C304 [Comm Loss Action]. |
| F100 Parameter Chksum | Cause: The checksum read from the board does not match the checksum calculated. Solution: Set P112 [Reset To Defalts] to option 1 “Reset Defaults”. |
| F122 I/O Board Fail | Cause: Failure has been detected in the drive control and I/O section. Solution: - Cycle power. - Replace drive if fault cannot be cleared. |
How to Clear & Reset Allen-Bradley PowerFlex 4M Faults
- Keypad Reset: Press the red Stop / Reset button on the drive’s integral keypad. If parameter P107 [Stop Mode] is not active or set to keypad control, toggle local/remote or ensure a run command is not asserted.
- Digital Input Terminal Reset: Configure one of the digital inputs (terminal 05, 06, or 07 via parameters A051 – A053) to Option 7 “Clear Fault”, then momentarily close the contact to digital common (terminal 04).
- Connected Components Workbench (CCW) / DSI: Connect your PC via an 1203-USB converter to the RJ45 DSI communication port, open CCW or DriveExplorer, and click “Clear Faults” in the online diagnostics menu.
- Serial Communication (Modbus RTU): Send a fault clear command bit over RS-485 Modbus RTU using the built-in DSI port by toggling the Fault Clear command bit in the drive control word.
- AC Mains Power Cycle: Disconnect the incoming AC power supply. Wait for the 4-digit LED display and status indicators to extinguish completely (allow at least 3 minutes for bus capacitor discharge), then reapply mains line power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous DC bus voltage remains present inside the drive after disconnecting AC mains power. Verify with a calibrated digital multimeter that voltage between the +DC and -DC terminals (or across the dynamic braking terminals on Frame B models) measures under 50 VDC before touching wiring, motor connections, or internal terminal blocks.