Allen-Bradley PowerFlex 70 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step diagnostic procedures for Allen-Bradley PowerFlex 70 AC drives. Search or filter through the complete diagnostic directory below.
Power Range
0.37 – 37 kW (0.5 – 50 HP)
Supply Voltage
200–600V (3-Phase)
Control Modes
V/Hz, Sensorless & FORCE™ Vector
Operator Interface
LCD HIM / DPI / CCW Software
Complete Allen-Bradley PowerFlex 70 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type F2, F3, F4, or OverCurrent).
| Fault Codes | Cause & Solutions |
|---|---|
| F2 Auxiliary Input | Cause : Auxiliary input interlock is open. Solution: - Check remote wiring. - Verify communications programming for intentional fault. |
| F3 Power Loss | Cause: Excessive DC Bus voltage ripple. Solution: - Monitor the incoming AC line for low voltage or line power interruption. - Check input fuses. - Reduce load. |
| F4 UnderVoltage | Cause: DC bus voltage fell below the min value. Solution: Monitor the incoming AC line for low voltage or line power interruption. |
| F5 OverVoltage | Cause: DC bus voltage exceeded max value. Solution: - Monitor the AC line for high line voltage or transient conditions. - Bus overvoltage can also be caused by motor regeneration. - Extend the decel time or install dynamic brake option. |
| F7 Motor OverLoad | Cause: - Internal electronic overload trip. - Enable/Disable with [Fault Config 1]. Solution: - An excessive motor load exists. - Reduce load so drive output current does not exceed the current set by [Motor NP FLA]. If enabled, check level of flux braking in parameter P549 [Flux Braking %]. |
| F8 Heatsink OvrTmp | Cause: Heatsink/Power Module temperature exceeds a predefined value. Solution: - Check for blocked or dirty heatsink fins. Verify that ambient temperature has not exceeded the rated ambient temperature. - Check fan. |
| F9 Trnsistr OvrTemp | Cause: Output transistors have exceeded their maximum operating temperature. Solution: - Verify that maximum ambient temperature has not been exceeded. - Check fan. - Check for excessive load. |
| F10 Heatsink LowTemp | Cause: Annunciates a too low temperature case or an open NTC (heatsink temperature sensing device) circuit. Solution: - Verify ambient temperature. - In cold ambient temperatures, add space heaters. - Check connections to NTC. |
| F12 HW OverCurrent | Cause: The drive output current has exceeded the hardware current limit. Solution: - Check output of drive or motor for shorts. - Check programming. - Check for excess load, improper DC boost setting, DC brake volts set too high, or other causes of excess current. |
| F13 Ground Fault | Cause: A current path to earth ground has been detected at one or more of the drive output terminals. Solution: - Check the motor and external wiring to the drive output terminals for a grounded condition. |
| F15 Load Loss | Cause: Drive output torque current is below [Load Loss Level] for a time period greater than [Load Loss time]. Solution: - Verify connections between motor and load. - Verify level and time requirements. |
| F16 Motor Thermistor | Cause: Thermistor output is out of range. Solution: - Verify that thermistor is connected. - Motor is overheated. Reduce load. |
| F17 Input Phase Loss | Cause: The DC bus ripple has exceeded a preset level. Solution: - Check incoming power for a missing phase/blown fuse. |
| F24 Decel Inhibit | Cause: The drive is not following a commanded acceleration or deceleration because it is attempting to limit bus voltage. Solution: - Verify that input voltage is within drive specified limits. - Verify that system ground impedance follows proper grounding techniques. - Disable bus regulation and/or add dynamic brake resistor and/or extend deceleration time. |
| F25 Overspeed Limit | Cause: Functions such as Slip Compensation or Bus Regulation have attempted to add an output frequency adjustment greater than that programmed in [Overspeed Limit]. Solution: Remove excessive load or overhauling conditions or increase [Overspeed Limit]. |
| F29 Analog In Loss | Cause: An analog input is configured to fault on signal loss. A signal loss has occurred. - Configure with [Anlg In X Loss]. Solution: - Check the parameters. - Check for broken/loose connections at inputs. |
| F33 Auto Rstrt Tries | Cause: Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of [Flt RstRun Tries]. - Enable/Disable with [Fault Config 1]. Solution: - Correct the cause of the fault and manually clear. |
| F36 SW OverCurrent | Cause: Drive output current has exceeded the 1 ms current rating. - This rating is greater than the 3-second current rating and less than the hardware overcurrent fault level. - It is typically 200…250% of the drive continuous rating. Solution: - Check for excess load, improper DC boost setting. DC brake volts set too high. - If enabled, check level of flux braking in parameter P549 [Flux Braking %]. |
| F38 Phase U to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F39 Phase V to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F40 Phase W to Gnd | Cause: A phase to ground fault has been detected between the drive and motor in this phase. Solution: - Check the wiring between the drive and motor. - Check motor for grounded phase. - Replace drive if fault cannot be cleared. |
| F41 Phase UV Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F42 Phase UW Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F43 Phase VW Short | Cause: Excessive current has been detected between these two output terminals. Solution: - Check the motor and drive output terminal wiring for a shorted condition. - Replace drive if fault cannot be cleared. |
| F48 Params Defaulted | Cause: The drive was commanded to write default values to EEPROM. Solution: - Clear the fault or cycle power to the drive. - Program the drive parameters as needed. |
| F49 Drive Powerup | No fault is displayed. Used as a Powe r Up Marker in the Fault Queue indicating that the drive power has been cycled. |
| F51 Flt QueueCleared | No fault displayed. Used as a marker in the Fault Queue indicating that the clear queue function was performed. |
| F52 Faults Cleared | No fault displayed. Used as a marker in the Fault Queue indicating that the fault clear function was performed. |
| F55 Cntl Bd Overtemp | Cause: The temperature sensor on the Main Control Board detected excessive heat. Solution: - Check Main Control Board fan. - Check surrounding air temperature. - Verify proper mounting/ cooling. |
| F63 Shear Pin | Cause: Programmed [Current Lmt Val] has been exceeded. Enable/Disable with [Fault Config 1]. Solution: Check load requirements and [Current Lmt Val] setting. |
| F64 Drive Overload | Cause: Drive rating of 110% for 1 minute or 150% for 3 seconds has been exceeded. Solution: Reduce load or extend Accel Time. |
| F69 DB Resistance | Cause: The resistance of the internal DB unit is out of range. Solution: - Replace the resistor. |
| F70 Power Unit | Cause: One or more of the output transistors were operating in the active region instead of desaturation. This can be caused by excessive transistor current or insufficient base drive voltage. Solution: - Check for damaged output transistors. - Replace drive. |
| F71…F75 Port 1…5 Adapter | Cause: The communications card has a fault. Solution: - Check DPI device event queue and corresponding fault information for the device. |
| F77 IR Volts Range | Cause: “Calculate” is the autotune default and the value that is determined by the autotune procedure for IR Drop Volts is not in the range of acceptable values. Solution: - Re-enter motor nameplate data. |
| F78 FluxAmpsRef Rang | Cause: The value for flux amps determined by the Autotune procedure exceeds the programmed [Motor NP FLA]. Solution: - Reprogram [Motor NP FLA] with the correct motor nameplate value. - Repeat Autotune. |
| F79 Excessive Load | Cause: Motor did not come up to speed in the allotted time during autotune. Solution: - Uncouple load from motor. - Repeat Autotune. |
| F80 AutoTune Aborted | Cause: Autotune function was canceled by the user or a fault occurred. Solution: - Restart the procedure. |
| Port 1…6 DPI Loss F81…F86 | Cause: - DPI port stopped communicating. - A SCANport device was connected to a drive operating DPI devices at 500k baud. Solution: - If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port expander, adapters, Main Control Board, or complete drive as required. - Check HIM connection. - If an adapter was intentionally disconnected and the [Logic Mask] bit for that adapter is set to “1”, this fault occurs. To disable this fault, set the [Logic Mask] bit for the adapter to “0.” |
| F87 IXo VoltageRange | Cause: Voltage calculated for motor inductive impedance exceeds 25% of [Motor NP Volts]. Solution: - Check for proper motor sizing. - Check for correct programming of [Motor NP Volts], parameter 41. - Additional output impedance can be required. |
| F90 Encoder Quad Err | Cause: Both encoder channels changed state within one clock cycle. Solution: - Check for externally induced noise. - Replace encoder. |
| F91 Encoder Loss | Cause: One or both encoder channel signals is missing. Solution: - Check Wiring. - Replace encoder. |
| F93 Hardware Fault | Cause: Hardware enable is disabled (jumpered high) but logic pin is still low. Solution: - Check jumper. - Replace Main Control Board. |
| F100 Parameter Chksum | Cause: The checksum read from the board does not match the checksum calculated. Solution: - Restore defaults. - Reload User Set if used. |
| F101 UserSet1 Chksum | Cause: The checksum read from the user set does not match the checksum that is calculated. Solution: - Re-save user set. |
| F102 UserSet2 Chksum | Cause: The checksum read from the user set does not match the checksum that is calculated. Solution: - Re-save user set. |
| F103 UserSet3 Chksum | Cause: The checksum read from the user set does not match the checksum that is calculated. Solution: - Re-save user set. |
| F104 Pwr Brd Chksum1 | Cause: The checksum read from the EEPROM does not match the checksum that is calculated from the EEPROM data. Solution: - Clear the fault or cycle power to the drive. |
| F105 Pwr Brd Chksum2 | Cause: The checksum read from the board does not match the checksum that is calculated. Solution: - Cycle power to the drive. - If problem persists, replace drive. |
| F106 Incompact MCB-PB | Cause: Drive rating information that is stored on the power board is incompatible with the main control board. Solution: Load compatible version files into drive. |
| F107 Replaced MCB-PB | Cause: Main Control Board was replaced and parameters were not programmed. Solution: - Restore defaults. - Reprogram parameters. |
| F108 Anlg Cal Chksum | Cause: The checksum read from the analog calibration data does not match the checksum that is calculated. Solution: - Replace the drive. |
| F111 Enable Hardware | Cause: & solution: 1. Safe-Off board is not installed and pins 3 and 4 of the Safe-Off Connector are not jumpered. - Install Safe-Off board or jumper pins 3 and 4. 2. If Safe-Off board is installed, verify that the hardware enable jumper is removed. - Locate and remove the enable jumper on the main control board. Refer to DriveGuard Safe-Off Option (Series B) for PowerFlex 40P and PowerFlex 70 AC Drives, publication PFLEX-UM003, for instructions and location. 3. Safe-Off board has failed. - Replace Safe-Off board. 4. Hardware enable circuitry failed. - Replace control board. |
| F112 Power Down Csum | Cause: EEPROM data is corrupt on drive powerup. Solution: - Clear the fault or cycle power to the drive. |
| F900… F930 Fatal Faults | Cause: Diagnostic code indicating a drive malfunction. Solution: - Cycle power. - Replace Main Control Board. - Contact Tech Support. |
How to Clear & Reset Allen-Bradley PowerFlex 70 Drive Faults
- Keypad / HIM Reset: Press the red Stop / Reset key on the Human Interface Module (HIM). If the drive is in remote control mode, ensure active start/run signals are de-asserted.
- Digital Input Reset (DI): If terminal parameter 361, 362, 363, 364, 365, or 366 [Dig Inx Sel] is set to
1 "Clear Fault", cycle the designated digital input terminal. - Connected Components Workbench (CCW) / DriveExplorer: Connect through the integral DPI communication port using a 1203-USB interface converter, navigate to the fault diagnostics window, and click “Clear Faults”.
- Fieldbus Network Control Word: Assert Bit 3 (Clear Faults) of the Logic Command Word through the installed DPI communication adapter (e.g., 20-COMM-E EtherNet/IP, 20-COMM-D DeviceNet).
- Mains Power Cycle: Shut off incoming 3-phase line power. Wait at least 5 minutes until the LCD screen completely turns off and the internal DC bus capacitors have fully discharged, then restore line power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] before removing power terminal covers, inspecting motor output terminals U/T1, V/T2, W/T3, or working on PowerFlex 70 drive hardware.