Schneider Altivar ATV303 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip error codes, causes, and step-by-step troubleshooting procedures for the Schneider Electric Altivar 303 (ATV303) compact industrial drive series. Search or filter through the complete diagnostic directory below.

Compact Harsh-Environment Drive Power: 0.37 to 11 kW (0.5 to 15 HP) Embedded Modbus RTU (RJ45)
Power Range 0.37 – 11 kW (0.5 – 15 HP)
Supply Voltage 380–460V AC (3-Phase)
Control Modes Sensorless Vector (SVC), V/f & kn²
Operator Interface Integrated 4-Digit Display & Jog Dial

Complete Schneider ATV303 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type F010, OCF, F011, OHF, or Overcurrent).

Fault Code and MeaningCause and Remedy
F001
Precharge

Cause: Charging relay control fault or charging resistor damaged.



Remedy:

  • Turn the drive off and then back on again.

  • Check the connections.

  • Check the stability of the main supply.

  • Contact local Schneider Electric representative.


F002
Unknown drive rating

Cause: Power card and stored card versions different.



Remedy:

  • Contact local Schneider Electric representative.


F003
Unknown or incompatible power board

Cause: The power card is incompatible with the control card.



Remedy:

  • Contact local Schneider Electric representative.


F004
Internal serial link fault

Cause: Communication interruption between the internal cards.



Remedy:

  • Contact local Schneider Electric representative.


F005
Invalid industrialization zone

Cause: Internal data inconsistent.



Remedy:

  • Contact local Schneider Electric representative.


F006
Current measurement circuit

Cause: Current measurement is not correct due to hardware circuit fault.



Remedy:

  • Contact local Schneider Electric representative.


----
Problem with application firmware

Cause: Invalid application firmware update using the Multi-Loader tool.



Remedy:

  • Re-download application firmware.


F007
Internal thermal sensor detected fault

Cause:

  • The drive temperature sensor is not operating correctly.

  • The drive is in short circuit or open.




Remedy:

  • Contact local Schneider Electric representative.


F008
Internal CPU

Cause: Internal microprocessor fault.



Remedy:

  • Turn the drive off and then back on again.

  • Contact local Schneider Electric representative.


F010
Overcurrent

Cause:

  • Parameters in the Motor control menu (300-) are not correct.

  • Inertia or load too high.

  • Mechanical locking.




Remedy:

  • Check the parameters.

  • Check the size of the motor/drive/load.

  • Check the state of the mechanism.

  • Connect line motor chokes.

  • Reduce the Switching frequency range (315).

  • Check the ground connection of drive, motor cable, and motor insulation.


F018
Motor short-circuit

Cause: Short-circuit or grounding at the drive output.



Remedy:

  • Check the cables connecting the drive to the motor and the motor insulation.

  • Connect line motor chokes.


F019
Ground short-circuit

Cause:

  • Ground fault while in run state.

  • Motor switching while in run state.

  • Significant current leakage to ground while several motors are connected in parallel.




Remedy:

  • Check the cables connecting the drive to the motor and the motor insulation.

  • Connect line motor chokes.


F020
IGBT short circuit

Cause: Internal power component short circuit detected at power on.



Remedy:

  • Contact local Schneider Electric representative.


F025
Overspeed

Cause:

  • Instability.

  • Overspeed associated with the inertia of the application.




Remedy:

  • Check the motor.

  • If overspeed is 10% more than Top frequency (308), adjust this parameter if necessary.

  • Add a braking resistor.

  • Check the size of the motor/drive/load.

  • Check parameters of the speed loop (gain and stability).


F028
Autotuning fault

Cause:

  • Motor not connected to the drive.

  • Motor phase loss.

  • Special motor.

  • Motor is rotating (being driven by the load, for example).




Remedy:

  • Check that the motor/drive are compatible.

  • Check that the motor is present during autotuning.

  • If an output contactor is being used downstream, close it during auto-tuning.

  • Check that the motor is completely stopped.


F033
AI1 current loss

Cause: Detected if:

  • Analog input AI1 is configured as current.

  • AI1 current scaling parameter of 0% (204.1) is greater than 3 mA.

  • Analog input current is lower than 2 mA.




Remedy:

  • Check the terminal connection.


F009
Overbraking

Cause: Sudden braking or load inertia too high.



Remedy:

  • Increase the deceleration time.

  • Install a module unit with a braking resistor if necessary.

  • Check the main supply voltage to ensure it is under the maximum acceptable (20% over maximum main supply during run status).


F011
Drive overheat

Cause: Drive temperature too high.



Remedy:

  • Check the motor load, the drive ventilation, and the ambient temperature.

  • Wait for the drive to cool down before restarting.

  • See Mounting and temperature conditions in manual.


F012
Process overload

Cause: Process overload.



Remedy:

  • Check that drive parameters and application processes are compatible.


F013
Motor overload

Cause: Triggered by excessive motor current.



Remedy:

  • Check configuration of motor thermal protection and motor load.


F014
1 Output phase loss

Cause: Loss of one phase on drive output.



Remedy:

  • Check the connections from the drive to the motor.

  • If using a downstream contactor, make sure the connection, cable, and contactor are right.


F015
3 Output phases loss

Cause:

  • Motor not connected.

  • Motor power too low, below 6% of the rated drive current.

  • Output contactor open.

  • Transient instability in the motor current.




Remedy:

  • Check the connections from the drive to the motor.

  • Test on a low power motor or without a motor. In factory settings mode, motor phase loss detection is active (Output Phase loss detection 605 = 01).

  • To check the drive in a test or maintenance environment, without having to use a motor with the same rating as the drive, deactivate motor phase loss detection (605 = 00).

  • Check and optimize IR compensation (310), Rated motor voltage (304/305), and perform Auto-tuning (318).


F016
Main overvoltage

Cause:

  • Line voltage too high: At drive power on, supply is 10% over maximum acceptable voltage level.

  • At power with no run command, 20% over maximal line supply.

  • Disturbed mains supply.




Remedy:

  • Turn Off the Drive. Check and adjust the line voltage.

  • After line come back to nominal voltage (within tolerance) do power On.

  • If intermittent F016 code appears, set R1 assignment (205) to 01 and it can be connected to upstream protection to avoid overvoltage in the drive.


F017
Input phase loss

Cause:

  • Drive incorrectly supplied or a fuse blown.

  • Failure of one phase.

  • 3-phase ATV310 used on a single-phase line supply.

  • Unbalanced load.

  • This protection only operates with the drive on load.




Remedy:



  • Check the power connection and the fuses.

  • Use a 3-phase line supply.

  • Disable reporting of this fault type by setting Input Phase loss detection (606) to 00.


F021
Load short circuit

Cause:

  • Short-circuit at drive output.

  • Short circuit detection at the run command or DC injection command if parameter IGBT Test (608) is set to 01.




Remedy:



  • Check the cables connecting the drive to the motor and the condition of motor insulation.


F022
Modbus interruption

Cause:

  • Interrupted communication on the Modbus network.




Remedy:



  • Check the connections of communication bus.

  • Check the time-out (parameter Modbus time out 704).

  • Refer to the Modbus user manual.


F024
HMI communication

Cause:

  • Communication interruption with the external display terminal.




Remedy:



  • Check the terminal connection.


F029
Process underload

Cause:

  • Process underload.

  • Time that motor current is below the Application Underload threshold 211 exceeds the Application underload time delay 210 to protect the application.




Remedy:



  • Check that drive parameters and application processes are compatible.


F027
IGBT overheat

Cause:

  • Drive overheated.

  • IGBT internal temperature is too high for the ambient temperature and load.




Remedy:



  • Check the size of the load/motor/drive.

  • Reduce the Switching frequency (315).

  • Wait for the drive to cool down before restarting.


F031
Incorrect configuration

Cause:

  • HMI block replaced by an HMI block configured on a drive with a different rating.

  • The current configuration of customer parameters is inconsistent.




Remedy:



  • Return to factory settings or retrieve the backup configuration, if it is valid.

  • If the fault remains after reverting to the factory settings, contact your local Schneider Electric representative.


F032 (1)
Invalid configuration

Cause:

  • Invalid configuration.

  • The configuration loaded in the drive via the bus or communication network is inconsistent.

  • The configuration upload has been interrupted or is not fully finished.




Remedy:



  • Check the configuration loaded previously.

  • Load a compatible configuration.


F030
Undervoltage

Cause:

  • Line supply too low.

  • Transient voltage dip.




Remedy:



  • Check the voltage and parameters on the Undervoltage phase loss menu (607).


InIt
Auto-initialization on start

Cause:

  • Macro controller initialization.

  • Searching communication configuration.




Remedy:


No specific remedy listed (Status message).
COM.E (1)
Communication error

Cause:

  • 50 ms time out error.

  • This message appears after 220 retry attempts.




Remedy:


Check communication wiring and configuration.
A-17 (1)
Key alarm

Cause:

  • Key pressed down for longer than 10 seconds.

  • Membrane switch disconnected.

  • Display terminal woken up while a key is being pressed.




Remedy:


Check keypad/membrane buttons.
cLr (1)
Confirm fault reset

Cause:

  • This message appears if the STOP key is pressed while the display terminal is displaying a fault.




Remedy:


Confirmation step.
dEU.E (1)
Drive mismatch

Cause:

  • Drive type (brand) does not match display terminal type (brand).




Remedy:


Ensure terminal and drive brands match.
rOM.E (1)
ROM abnormality

Cause:

  • ROM abnormality detected by checksum calculation.




Remedy:


Hardware check required.
rAM.E (1)
RAM abnormality

Cause:

  • Display terminal RAM abnormality detected.




Remedy:


Hardware check required.
CPU.E (1)
Other fault

Cause:

  • The other detected fault.




Remedy:


Check device general status.

How to Clear & Reset Schneider ATV303 Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key directly on the front integrated keypad once the underlying root cause of the fault has been rectified.
  2. Logic Input Terminal Reset (LI): In menu [600-], set parameter 601 (Detected fault reset assignment) to an available logic input terminal (e.g., L1h for LI1 through L4h for LI4). Pulsing this terminal high resets active faults.
  3. Automatic Restart: In menu [602-], set parameter 602.0 (Automatic restart) to Yes [01] to enable the drive to clear transient faults (such as line undervoltage F016 / USF) automatically once line conditions normalize.
  4. Modbus Serial Network: Toggle Bit 7 (Fault Reset) from `0` to `1` in the Control Word (CMD / register 8501) across the integrated Modbus serial communication link (RJ45 port).
  5. Power Cycle: Disconnect the incoming 3-phase line power supply, wait until the front 4-digit LED display completely turns off (approx. 15 minutes for bus capacitor discharge), then restore AC mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated DC voltmeter that the intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] before removing terminal covers, handling wiring, or touching motor terminals U, V, and W on the Schneider ATV303 drive.