Schneider ATV31 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Schneider Electric Altivar 31 (ATV31) compact industrial drive series. Search or filter through the complete fault code directory below.

Compact Industrial Inverter Power: 0.18 to 15 kW (0.25 to 20 HP) Sensorless Flux Vector & Modbus/CANopen
Power Range 0.18 – 15 kW (0.25 – 20 HP)
Supply Voltage 200–240V / 380–500V / 600V (1/3-Phase)
Control Modes Sensorless Vector (SVC) & V/Hz Curve
Operator Interface Integrated 4-Digit Display & Jog Dial

Complete Schneider ATV31 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OCF, OHF, USF, or Overcurrent).

Fault Code and MeaningCause and Remedy
bLF
Brake sequence

Cause:


  • Brake release current not reached.

  • Brake engage frequency bEn = nO (not adjusted) when brake logic bLC is assigned.




Remedy:

  • Check the drive/motor connection.

  • Check the motor windings.

  • Check the Ibr setting in the FUn- menu (see page 60).

  • Carry out the recommended adjustment of bEn (see pages 59 and 60).


CrF
Capacitor load circuit

Cause:

Load relay control fault or charging resistor damaged.



Remedy:

  • Replace the drive.


EEF
EEPROM fault

Cause:

Internal memory fault.



Remedy:

  • Check the environment (electromagnetic compatibility).

  • Replace the drive.


InF
Internal fault

Cause:


  • Short-circuit on the 10 V power supply.

  • Internal fault.




Remedy:

  • Check the circuits connected to the 10 V.

  • Check the wiring of inputs AI1 and AI2 and the connection to the RJ45 connector.

  • Check the environment (electromagnetic compatibility).

  • Replace the drive.


OCF
Overcurrent

Cause:


  • Incorrect parameters in the SEt- and drC- menus.

  • Inertia or load too high.

  • Mechanical blockage.




Remedy:

  • Check the SEt- and drC- parameters.

  • Check the size of the motor/drive/load.

  • Check the state of the mechanism.


SCF
Motor short-circuit

Cause:


  • Short-circuit or earthing at the drive output.

  • Significant earth leakage current at the drive output when several motors are connected in parallel.




Remedy:

  • Check the cables connecting the drive to the motor, and the motor insulation.

  • Reduce the switching frequency.

  • Connect chokes in series with the motor.


SOF
Overspeed

Cause:


  • Instability.

  • Driving load too high.




Remedy:

  • Check the motor, gain and stability parameters.

  • Add a braking resistor.

  • Check the size of the motor/drive/load.


tnF
Auto-tuning fault

Cause:


  • Special motor or motor whose power is not suitable for the drive.

  • Motor not connected to the drive.




Remedy:

  • Use the L or the P ratio (see Uft page 24).

  • Check the presence of the motor during auto-tuning.

  • If a downstream contactor is being used, close it during auto-tuning.


COF
CAnopen fault

Cause:

Interruption in communication on the CANopen bus.



Remedy:

  • Check the communication bus.

  • Please refer to the product-specific documentation.


EPF
External fault

Cause:

According to user.



Remedy:

  • According to user.


LFF
Loss of 4-20mA

Cause:

Loss of the 4-20 mA reference on input AI3.



Remedy:

  • Check the connection on input AI3.


ObF
Overvoltage during deceleration

Cause:

Braking too sudden or driving load.



Remedy:

  • Increase the deceleration time.

  • Install a braking resistor if necessary.

  • Activate the brA function (page 44) if it is compatible with the application.


OHF
Drive overheated

Cause:

Drive temperature too high.



Remedy:

  • Check the motor load, the drive ventilation and the environment. Wait for the drive to cool down before restarting.


OLF
Motor overload

Cause:


  • Triggered by excessive motor current.

  • Incorrect value of parameter rSC.




Remedy:

  • Check the ItH setting (motor thermal protection) (page 20), check the motor load. Wait for the drive to cool down before restarting.

  • Measure rSC again (page 24).


OPF
Motor phase loss

Cause:


  • Loss of one phase at drive output.

  • Downstream contactor open.

  • Motor not connected or motor power too low.

  • Instantaneous instability in the motor current.




Remedy:

  • Check the connections from the drive to the motor.

  • If a downstream contactor is being used, set OPL to OAC (FLt- menu page 67).

  • Test on a low power motor or without a motor: In factory settings mode, motor phase loss detection is active (OPL = YES). To check the drive in a test or maintenance environment without having to switch to a motor with the same rating as the drive, deactivate motor phase loss detection (OPL = no).

  • Check and optimize the UFr, UnS and nCr parameters and perform auto-tuning with tUn.


OSF
Overvoltage

Cause:


  • Line voltage too high.

  • Disturbed line supply.




Remedy:

  • Check the line voltage.


PHF
Line phase failure

Cause:


  • Drive incorrectly supplied or a fuse blown.

  • Failure of one phase.

  • 3-phase ATV31 used on a single phase line supply.

  • Unbalanced load.

  • This protection only operates with the drive on load.




Remedy:

  • Check the power connection and the fuses.

  • Reset.

  • Use a 3-phase line supply.

  • Disable the fault by setting IPL = nO (FLt- menu page 67).


SLF
Modbus fault

Cause:


  • Interruption in communication on the Modbus bus.

  • Remote terminal enabled (LCC = YES page 40) and terminal disconnected.




Remedy:

  • Check the communication bus.

  • Please refer to the product-specific documentation.

  • Check the link with the remote terminal.


CFF
Configuration fault

Cause:

The current configuration is inconsistent.



Remedy:

  • Return to factory settings or call up the backup configuration, if it is valid. See the FCS parameter in the I-O-, drC-, CtL- or FUn- menu.


CFI
Configuration fault via serial link

Cause:

Invalid configuration. The configuration loaded in the drive via the serial link is inconsistent.



Remedy:

  • Check the configuration loaded previously.

  • Load a consistent configuration.


USF
Undervoltage

Cause:


  • Line supply too low.

  • Transient voltage dip.

  • Damaged load resistor.




Remedy:

  • Check the voltage and the voltage parameter. USF trip threshold:


    • ATV31....M2: 160V

    • ATV31....M3X: 160V

    • ATV31....N4: 300V

    • ATV31....S6X: 430V


  • Replace the drive.


How to Clear & Reset Schneider ATV31 Drive Faults

  1. Keypad Reset: Press the red STOP/RESET button directly on the front panel. Ensure the run command is removed before attempting to clear active fault trips.
  2. Logic Input Reset (LI): If configured in the [FAULT MANAGEMENT] (FLt-) menu under parameter [Fault reset] (rSt), toggle the assigned logic input terminal (LI1 through LI6) from 0 to 1.
  3. PowerSuite / SoMove Software: Connect via the RJ45 serial port using a PC connection cable (VW3A8106 / TCSMCNAM3M002P) to view active fault logs and initiate a software reset.
  4. Modbus / CANopen Control Word: Write Bit 7 (Fault Reset) from `0` to `1` in the Command Register (`CMD`) over the embedded Modbus RTU or CANopen interface.
  5. Mains Power Cycle: De-energize the incoming line power supply. Wait at least 15 minutes for the DC bus capacitors to discharge until the 4-digit LED display completely extinguishes, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 42VDC across terminals [PA/+] and [PC/-] before inspecting motor lead connections, removing terminal covers, or touching terminals U, V, and W on the Schneider Altivar 31 (ATV31) drive.