Schneider ATV312 Solar Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Schneider Electric Altivar 312 Solar (ATV312 Solar) pumping drive series. Search or filter through the complete fault code directory below.

Solar Pumping Inverter Power: 0.18 to 15 kW (0.25 to 20 HP) Embedded MPPT & Dual Supply (PV / Grid)
Power Range 0.18 – 15 kW (0.25 – 20 HP)
PV / Line Voltage 100–800V DC (PV) / 200–500V AC
Control Modes Sensorless Vector, V/Hz & Solar MPPT
Operator Interface Integrated 4-Digit Display / SoMove

Complete Schneider ATV312 Solar Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OCF, ObF, USF, or Overcurrent).

Fault Code and MeaningCause and Remedy
bLF[NETWORK FAULT]
Cause:


  • Brake release current not reached.

  • Brake engage frequency bEn = nO (not adjusted) when brake logic bLC is assigned.



Remedy:


  • Check the drive/motor connection.

  • Check the motor windings.

  • Check the Ibr setting in the FUn- menu.

  • Carry out the recommended adjustment of bEn.


CrF[PRECHARGE FAULT]
Cause:

Load relay control fault or charging resistor damaged.

Remedy:


  • Replace the drive.


EEF[EEPROM FAULT]
Cause:

Internal memory detected fault.

Remedy:


  • Check the environment (electromagnetic compatibility).

  • Replace the drive.


IF1[INTERNAL FAULT]
Cause:

Unknown range.

Remedy:


  • Replace the drive.

  • Restart drive.

  • Contact local Schneider Electric representative.


IF2[INTERNAL FAULT]
Cause:


  • MMI card not recognized.

  • MMI card incompatible.

  • Display missing.



Remedy:


  • Contact local Schneider Electric representative.


IF3[INTERNAL FAULT]
Cause:

EEPROM detected fault.

Remedy:


  • Replace the drive.

  • Contact local Schneider Electric representative.


IF4[INTERNAL FAULT]
Cause:

Industrial EEPROM detected fault.

Remedy:


  • Replace the drive.

  • Contact local Schneider Electric representative.


OCF[OVERCURRENT]
Cause:


  • Incorrect parameters in the [SETTINGS] SEt- and [MOTOR CONTROL] drC- menus.

  • Inertia or load too high.

  • Mechanical locking.



Remedy:


  • Check parameters in [SETTINGS] SEt- and [MOTOR CONTROL] drC- menus.

  • Check the size of the motor/drive/load.

  • Check the state of the mechanism.

  • Check wiring isolation if wires are in the water.


SCF[MOTOR SHORT CIRCUIT]
Cause:


  • Short-circuit or grounding at the drive output.

  • Significant ground leakage current at the drive output if several motors are connected in parallel.



Remedy:


  • Check the cables connecting the drive to the motor, and the motor insulation.

  • Reduce the switching frequency.

  • Connect chokes in series with the motor.

  • Check wiring isolation if wires are in the water.


SOF[OVERSPEED]
Cause:


  • Speed instability.

  • Spinning load too important (load too high).



Remedy:


  • Check the motor, gain and stability parameters.

  • Add a braking resistor.

  • Check the size of the motor/drive/load.


CnF[NETWORK FAULT]
Cause:

Communication detected fault on the communication card.

Remedy:


  • Check the environment (electromagnetic compatibility).

  • Check the wiring.

  • Check the time-out.

  • Replace the option card.

  • See the [CANopen fault mgt] COL parameter to define the stop mode with a CnF.


COF[CANopen FAULT]
Cause:

Interruption in communication on the CANopen bus.

Remedy:


  • Check the communication bus.

  • Refer to the product documentation.


EPF[EXTERNAL FAULT]
Cause:

Depending on user.

Remedy:


  • Depending on user.


ILF[INTERNAL LINK FAULT]
Cause:

Identification detected fault of the communication card by the drive.

Remedy:


  • Check that the option card is compatible with the drive.

  • Replace the option card.


LFF[LOSS OF 4-20 mA]
Cause:

Loss of the 4-20 mA reference on input AI3.

Remedy:


  • Check the connection on input AI3.


ObF[OVERBRAKING]
Cause:

Braking too sudden or Driving load.

Remedy:


  • Increase the deceleration time.

  • Install a braking resistor if necessary.

  • See the [Dec ramp adapt] brA function if it is compatible with the application.


OHF[DRIVE OVERHEAT]
Cause:

Drive temperature too high.

Remedy:


  • Check the motor load, the drive ventilation and the environment.

  • Wait for the drive to cool down before restarting.


OLF[MOTOR OVERLOAD]
Cause:


  • Triggered by excessive motor current.

  • [Cold stator resist.] rSC parameter value incorrect.



Remedy:


  • Check the [Mot. therm. current] ItH setting, of the motor thermal protection.

  • Check the motor load. Wait for the drive to cool before restarting.

  • Remeasure [Cold stator resist.] rSC.


OPF[MOTOR PHASE LOSS]
Cause:


  • Loss of one phase at drive output.

  • Output contactor open.

  • Motor not connected or motor power too low.

  • Instantaneous instability in the motor current.



Remedy:


  • Check the connections from the drive to the motor.

  • If an output contactor is being used, set [Output Phase Loss] oPL to [Output cut] oAC ([FAULT MANAGEMENT] FLt- menu).

  • Test on a low-power motor or without a motor: In factory settings mode, motor output phase loss detection is active ([Output Phase Loss] oPL = [Yes] YES).

  • To check the drive in a test or maintenance environment without having to switch to a motor with the same rating as the drive, deactivate motor phase loss detection ([Output Phase Loss] oPL = [No] nO).

  • Check and optimize the [IR compensation] uFr, [Rated motor volt.] unS, and [Rated mot. current] nCr parameters.

  • Perform an [Auto-tuning] tUn operation.


OSF[MAINS OVERVOLTAGE]
Cause:


  • Line voltage is too high.

  • Disturbed line supply.



Remedy:


  • Check the line voltage.


PHF

[INPUT PHASE LOSS]

Cause:

Drive incorrectly supplied or a fuse blown; Failure of one phase; Three-phase ATV312 used on a single-phase line supply; Unbalanced load; This protection only operates with the drive on load.



Remedy:


  • Check the power connection and the fuses.

  • Reset.

  • Use a three-phase line supply.

  • Disable the detection by setting [Input phase loss] IPL = [No] nO ([FAULT MANAGEMENT] FLt- menu).


SLF

[MODBUS FAULT]

Cause:

Interruption in communication on the Modbus bus; Remote display terminal enabled ([HMI command] LCC = [Yes] YES) and terminal disconnected.



Remedy:


  • Check the communication bus.

  • Refer to the relevant product documentation.

  • Check the link with the remote display terminal.


CFF

[INCORRECT CONFIG.]

Cause:

The current configuration is inconsistent; Addition or removal of an option.



Remedy:


  • Return to factory settings or retrieve the backup configuration, if it is valid. See the [Restore config.] FCS parameter.


CFI

[INVALID CONFIG]

Cause:

Invalid configuration; The configuration loaded in the drive via the serial link is inconsistent.



Remedy:


  • Check the configuration loaded previously.

  • Load a consistent configuration.


USF

[UNDERVOLTAGE]

Cause:

Insufficient line supply; Transient voltage dip; Damaged precharge resistor.



Remedy:


  • Check the voltage and the voltage parameter. Tripping threshold in [UNDERVOLTAGE] USF.

  • ATV312••••M2: 160 V

  • ATV312••••M3: 160 V

  • ATV312••••N4: 300 V

  • Replace the drive.


LL

[Low Light]

Cause:

Not enough power from photovoltaic arrays; Cloudy weather; Sunrise or sunset period.



Remedy:

Check the configuration of rPG/rIG and rPG2/rIG2 parameters.

If there is enough sunshine:

  • Clean up the photovoltaic arrays.

  • Check the installation requirements for the number of photovoltaic arrays to deliver enough power.


If there is not enough sunshine:

  • With many LL detected faults during sunrise and sunset: increase the value of [Light timeout restart] LItr.


tF

[Tank Full]

Cause:

The tank is detected full.



Remedy:

If the tank is full:

  • No action to realize.


If the tank is not full:

  • Check the liquid probe connection.

  • Check LPt and LPtP parameters.


tSF

[Tank sensor detected fault]

Cause:

Tank water sensor disconnected; Tank water sensor broken; Alarm threshold too low (LPtP value).



Remedy:


  • Check the liquid probe connection.

  • Check LPt and LPtP parameters.


ULF

[Underload detected fault]

Cause:

Not enough water to pump; Pump blocked.



Remedy:


  • Check if the pumping water level is OK.

  • Check if the pump is blocked.

  • If there is enough water and the pump is not blocked: set [State Unld. function] SUL to AUtO.


How to Clear & Reset Schneider ATV312 Solar Drive Faults

  1. Keypad Reset: Press the red STOP/RESET button on the front integrated control panel. If running via terminal 2-wire/3-wire control, ensure the running command is de-asserted first.
  2. Logic Input Reset (LI): Configure an assigned logic terminal (LI1 to LI6) configured for [Fault reset] (rSt) in the [FAULT MANAGEMENT] (FLt-) menu, then switch the input from 0 to 1.
  3. SoMove PC Software: Connect via the front RJ45 Modbus serial port using a USB-to-RS485 PC adapter cable (TCSMCNAM3M002P) and select “Fault Reset” in the monitoring menu.
  4. Modbus RTU Control Word: Write Bit 7 (Fault Reset) from `0` to `1` in Command Word (`CMD`) via RS-485 serial communication.
  5. Dual Power Cycle (Solar PV & AC Backup): Open both the photovoltaic DC array isolator and any AC grid/generator backup switch. Wait at least 15 minutes for the DC bus capacitors to discharge until the 4-digit display completely clears before switching power back on.
⚠️ High-Voltage Photovoltaic & Electrical Safety Warning: Photovoltaic (PV) arrays generate lethal DC voltages whenever exposed to light. Always open both the DC PV isolator and AC grid disconnect switches, and verify using a calibrated DC multimeter that intermediate bus voltage measures strictly below 42VDC across terminals [PA/+] and [PC/-] before inspecting terminal connections, wiring, or touching terminals U, V, and W on the Schneider ATV312 Solar drive.