Schneider ATV320 Solar Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, MPPT solar pumping alarms, dry-run trip causes, and step-by-step troubleshooting procedures for the Schneider Electric Altivar Machine ATV320 Solar drive series. Search or filter through the complete fault code directory below.
Power Range
0.37 – 15 kW (0.5 – 20 HP)
Supply Voltage
150–800V DC / 200–500V AC
Control Modes
Auto MPPT & Sensorless Vector
Operator Interface
Integrated Display / SoMove Tool
Complete Schneider ATV320 Solar Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OCF, OHF, SCF, or Under-Irradiation).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| AnF Load slipping error | Cause: The difference between the output frequency and the speed feedback is not correct. Remedy:
|
| AsF Angle error | Cause: It occurs during the phase-shift angle measurement, if the motor phase is disconnected or if the motor inductance is too high. Remedy:
|
| blF Brake control error | Cause: Brake release current not reached, or Brake engage frequency threshold [Brake engage freq] bEn only regulated when brake logic control is assigned. Remedy:
|
| brF Brake feedback error | Cause: The brake feedback contact does not match the brake logic control, or the brake does not stop the motor quickly enough. Remedy:
|
| CFF Incorrect configuration error | Cause: Option module changed or removed, or Control block replaced by a control block configured on a drive with a different rating, or the current configuration is inconsistent. Remedy:
|
| CFI Invalid configuration error | Cause: Invalid configuration. The configuration loaded in the drive via the bus or communication network is inconsistent. Remedy:
|
| CFI2 Configuration transfer error | Cause: Invalid configuration. The configuration loaded in the drive via the bus or communication network is inconsistent. Remedy:
|
| CnF Fieldbus module communication interruption error | Cause: Communication interruption on communication module. Remedy:
|
| CoF CANopen communication interruption error | Cause: Communication interruption on the CANopen® bus. Remedy:
|
| CrF1 Precharge capacitor error | Cause: Charging relay control detected error or charging resistor damaged. Remedy:
|
| CSF Channel switching detected error | Cause: Switch to not valid channels. Remedy:
|
| dlF Dynamic load detected error | Cause: Abnormal load variation. Remedy:
|
| EEF1 EEprom control error | Cause: Internal memory detected error, control block. Remedy:
|
| EEF2 EEprom power error | Cause: Internal memory detected error, power board. Remedy:
|
| EPF1 External error | Cause: Event triggered by an external device, depending on user. Remedy:
|
| EPF2 Fieldbus external detected error | Cause: Event triggered by a communication network. Remedy:
|
| fbE Function block error | Cause: Function block detected error. Remedy:
|
| fbES Function block stop error | Cause: Function blocks have been stopped while motor was running. Remedy:
|
| FCF1 Output contactor closed error | Cause: The output contactor remains closed although the opening conditions have been met. Remedy:
|
| FCF2 Output contactor opened error | Cause: The output contactor remains open although the closing conditions have been met. Remedy:
|
| HCF Boards compatibility error | Cause: The [Boards pairing] PPI- function has been configured and a drive card has been changed. Remedy:
|
| HdF IGBT desaturation error | Cause: Short-circuit or grounding at the drive. Remedy:
|
| ILF Internal link error | Cause: Communication interruption between option module and drive. Remedy:
|
| InF1 Internal error 1 (Rating) | Cause: The power board is different from the board stored. Remedy:
|
| InF2 Internal error 2 (Soft) | Cause: The power board is incompatible with the control block. Remedy:
|
| InF3 Internal error 3 (Intern Comm) | Cause: Communication interruption between the internal cards. Remedy:
|
| InF4 Internal error 4 (Manufacturing) | Cause: Internal data inconsistent. Remedy:
|
| InF6 Internal error 6 (Option) | Cause: The option installed in the drive is not recognized. Remedy:
|
| InF9 Internal error 9 (Measure) | Cause: The current measurements are incorrect. Remedy:
|
| InFA Internal error 10 (Mains) | Cause: The input stage is not operating correctly. Remedy:
|
| InFb Internal error 11 (Temperature) | Cause: The drive temperature sensor is not operating correctly. Remedy:
|
| InFE Internal error 14 (CPU) error | Cause: Internal microprocessor detected error. Remedy:
|
| LCF Input contactor error | Cause: The drive is not turned on even though [Mains V. time out] LCt has elapsed. Remedy:
|
| LFF3 AI3 4-20mA loss error | Cause: Loss of the 4-20 mA reference on analog input AI3. Remedy: Check the connection on the analog inputs. |
| OBF DC bus overvoltage error | Cause:
Remedy:
|
| OCF Overcurrent error | Cause:
Remedy:
|
| OHF Drive overheating error | Cause: Drive temperature too high. Remedy: Check the motor load, the drive ventilation and the ambient temperature. Wait for the drive to cool down before restarting. |
| OLC Process overload error | Cause: Process overload. Remedy:
|
| OLF Motor overload error | Cause: Triggered by excessive motor current. Remedy: Check the setting of the motor thermal protection, check the motor load. Wait for the motor to cool down before restarting. |
| OPF1 Single output phase loss error | Cause: Loss of one phase at drive output. Remedy: Check the connections from the drive to the motor. |
| OPF2 Output phase loss error | Cause:
Remedy:
|
| OSF Supply mains overvoltage error | Cause:
Remedy: Check the supply voltage. |
| OTFL DI6=PTC overheat error | Cause: Overheating of PTC probes detected on input DI6. Remedy:
|
| PHF Input phase loss error | Cause:
Remedy:
|
| PEFL DI6=PTC probe error | Cause: PTC probe on input DI6 open or short-circuited. Remedy: Check the PTC probe and the wiring between it and the motor/drive. |
| SAFF Safety function detected error | Cause:
Remedy:
|
| SCF1 Motor short circuit error | Cause: Short-circuit or grounding at the drive output. Remedy:
|
| SCF3 Ground short circuit error | Cause: Significant earth leakage current at the drive output if several motors are connected in parallel. Remedy:
|
| SCF4 IGBT short circuit error | Cause: Power component detected error. Remedy: Contact Schneider Electric Product Support. |
| SCFS Motor short circuit error | Cause: Short-circuit at drive output. Remedy:
|
| SLF1 Modbus communication interruption error | Cause: Communication interruption on the Modbus bus. Remedy:
|
| SLF2 PC communication interruption error | Cause: Communication interruption with PC Software. Remedy:
|
| SLF3 HMI communication interruption error | Cause: Communication interruption with the graphic display terminal or remote display terminal. Remedy:
|
| SOF Motor overspeed error | Cause:
Remedy:
|
| SPF Encoder feedback loss error | Cause:
Remedy:
|
| SSF Torque limitation error | Cause: Switch to torque or current limitation. Remedy:
|
| TJF IGBT overheating | Cause: Drive overheated. Remedy:
|
| tnF Autotuning detected error | Cause:
Remedy:
|
| tSF Tank Probe Error | Cause:
Remedy:
|
| ULF Process underload error | Cause: Process underload. Remedy:
|
| USF Supply mains undervoltage error | Cause:
Remedy: Check the voltage and the parameters of [Undervoltage handling] USB-. |
How to Clear & Reset Schneider ATV320 Solar Drive Faults
- Keypad Reset: Press the red STOP/RESET key on the integrated drive panel or remote display terminal once the solar irradiance or system fault condition has been corrected.
- Digital Input Reset (DI): If configured in parameter [Fault Reset assign.] (rSF) inside the [FAULT MANAGEMENT] (FLt-) menu, send a +24V pulse to the assigned terminal (e.g., DI3 or DI4) to clear latched trips.
- Solar Auto-Recovery: For solar-specific warning conditions (such as low sunlight, undervoltage, or dry-run pump timeouts), the drive’s embedded solar controller automatically attempts a restart once irradiation and DC bus voltage recover above the minimum threshold.
- SoMove Software & Fieldbus: Connect a PC using the USB-to-RJ45 Modbus lead (TCSMCNAM3M002P) via SoMove to execute a remote software reset, or trigger Bit 7 (Fault Reset) in Control Word (CMD / register 8501) via Modbus RTU.
- Dual Supply Power Isolation: Disconnect both the DC PV isolator switch and the auxiliary AC grid/generator supply. Wait at least 15 minutes for the DC bus capacitors to discharge until the display turns off completely before restoring power.
⚠️ Dual-Source High-Voltage Safety Warning:
The ATV320 Solar drive is energized by dual power sources (photovoltaic DC arrays and AC mains/generator). Always open both the DC photovoltaic isolator and the AC circuit breaker. Wait at least 15 minutes, and verify with a calibrated digital multimeter that the DC bus measures strictly below 42VDC across terminals [PA/+] and [PC/-] before removing terminal covers or handling power wiring.