Schneider ATV340 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip error causes, and step-by-step troubleshooting procedures for the Schneider Electric Altivar Machine ATV340 high-performance inverter series. Search or filter through the complete fault code directory below.
Power Range
0.75 – 75 kW (1 – 100 HP)
Supply Voltage
380–480V AC (3-Phase)
Control Modes
Open/Closed Loop Vector & V/Hz
Operator Interface
Graphic Keypad Terminal & Embedded Ethernet
Complete Schneider ATV340 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OCF, ObF, SOF, or Overheating).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| NOA [No Warning stored] | Cause: No warning stored. Remedy:
|
| FRF [Fallback Frequency] | Cause: Reaction on event: Fallback frequency. Remedy:
|
| RLS [Speed Maintained] | Cause: Reaction on event: Speed maintained. Remedy:
|
| STT [Type of stop] | Cause: Reaction on event: Stop following [Type of stop] STT without triggering an error. Remedy:
|
| SRA [Ref Frequency Warning] | Cause: Frequency reference reached. Remedy:
|
| PEE [PID error Warning] | Cause: PID error warning. Remedy:
|
| PFA [PID Feedback Warn] | Cause: PID feedback warning. Remedy:
|
| PFAH [PID High Fdbck Warn] | Cause: PID feedback high threshold reached. Remedy:
|
| PFAL [PID Low Fdbck Warn] | Cause: PID feedback low threshold reached. Remedy:
|
| LSA [Limit Switch Reached] | Cause: Limit switch reached. Remedy:
|
| RSDA [Slack Rope Warning] | Cause: Slack rope warning. Remedy:
|
| DLDA [Dynamic Load Warning] | Cause: Dynamic load warning. Remedy:
|
| TP3A [AI3 Th Warning] | Cause: AI3 Thermal warning. Remedy:
|
| TP4A [AI4 Th Warning] | Cause: AI4 Thermal warning. Remedy:
|
| TP5A [AI5 Th Warning] | Cause: AI5 Thermal warning. Remedy:
|
| AP1 [AI1 4-20 Warning] | Cause: AI1 4-20 mA loss warning. Remedy:
|
| AP3 [AI3 4-20 Warning] | Cause: AI3 4-20 mA loss warning. Remedy:
|
| AP4 [AI4 4-20 Warning] | Cause: AI4 4-20 mA loss warning. Remedy:
|
| AP5 [AI5 4-20 Warning] | Cause: AI5 4-20 mA loss warning. Remedy:
|
| THA [Device Therm Warn] | Cause: Drive overheating warning. Remedy:
|
| TJA [IGBT Thermal Warning] | Cause: IGBT thermal state warning. Remedy:
|
| FCTA [Fan Counter Warning] | Cause: Fan counter speed warning. Remedy:
|
| FFDA [Fan Feedback Warning] | Cause: Fan feedback warning. Remedy:
|
| BOA [BR Thermal Warning] | Cause: Braking resistor thermal warning. Remedy:
|
| EFA [Ext. Error Warning] | Cause: External error warning. Remedy:
|
| USA [Undervoltage Warning] | Cause: Undervoltage warning. Remedy:
|
| UPA [Preventive UnderV Active] | Cause: Controlled stop threshold is reached. Remedy:
|
| FTA [Mot Freq High Thd] | Cause: Motor frequency high threshold 1 reached. Remedy:
|
| FTAL [Mot Freq Low Thd] | Cause: Motor frequency low threshold 1 reached. Remedy:
|
| FQLA [Pulse Warn Thd Reached] | Cause: Pulse warning threshold reached. Remedy:
|
| F2AL [Mot Freq Low Thd 2] | Cause: Motor frequency low threshold 2 reached. Remedy:
|
| FLA [High Speed Reached] | Cause: High speed reached warning. Remedy:
|
| RTAH [Ref Freq High Thd reached] | Cause: Reference frequency high threshold reached. Remedy:
|
| RTAL [Ref Freq Low Thd reached] | Cause: Reference frequency low threshold reached. Remedy:
|
| F2A [2nd Freq Thd Reached] | Cause: Motor frequency high threshold 2 reached. Remedy:
|
| CTA [Current Thd Reached] | Cause: Motor current high threshold reached. Remedy:
|
| CTAL [Low Current Reached] | Cause: Motor current low threshold reached. Remedy:
|
| TTHA [High Torque Warning] | Cause: High torque threshold reached. Remedy:
|
| TTLA [Low Torque Warning] | Cause: Low torque threshold reached. Remedy:
|
| ULA [Process Undld Warning] | Cause: Process underload warning. Remedy:
|
| OLA [Process Overload Warning] | Cause: Overload warning. Remedy:
|
| SSA [Torque Limit Reached] | Cause: Torque limit reached. Remedy:
|
| RTA [Torque Control Warning] | Cause: Torque control warning. Remedy:
|
| TAD [Dev Thermal reached] | Cause: Drive thermal threshold reached. Remedy:
|
| TSA [Motor Therm Thd reached] | Cause: Motor thermal threshold reached. Remedy:
|
| TS2 [Mot2 Therm Thd reached] | Cause: Motor 2 thermal threshold reached. Remedy:
|
| TS3 [Mot3 Therm Thd reached] | Cause: Motor 3 thermal threshold reached. Remedy:
|
| TS4 [Mot4 Therm Thd reached] | Cause: Motor 4 thermal threshold reached. Remedy:
|
| PTHA [Power High Threshold] | Cause: Power high threshold reached. Remedy:
|
| PTHL [Power Low Threshold] | Cause: Power low threshold reached. Remedy:
|
| CAS1 [Cust Warning 1] | Cause: Customer warning 1 active. Remedy:
|
| CAS2 [Cust Warning 2] | Cause: Customer warning 2 active. Remedy:
|
| CAS3 [Cust Warning 3] | Cause: Customer warning 3 active. Remedy:
|
| CAS4 [Cust Warning 4] | Cause: Customer warning 4 active. Remedy:
|
| CAS5 [Cust Warning 5] | Cause: Customer warning 5 active. Remedy:
|
| POWD [Power Cons Warning] | Cause: Power consumption warning. Remedy:
|
| ANA [Slipping warn] | Cause: Slipping warning. Remedy:
|
| BSA [Load Mvt Warn] | Cause: Load movement warning. Remedy:
|
| BCA [Brake Cont Warn] | Cause: Brake contact warning. Remedy:
|
| TP1A [AI1 Th Warning] | Cause: AI1 Thermal warning. Remedy:
|
| TLOW [Current Reduc Warn] | Cause: Current reduction warning. Remedy:
|
| MSDA [M/S Device Warn] | Cause: Master/Slave device warning. Remedy:
|
| BSQA [Backlash Warn] | Cause: Backlash warning. Remedy:
|
| TPEA [Encoder Thermal Warn] | Cause: Encoder module thermal warning. Remedy:
|
| TS1A [Temp Sens AI1 Warn] | Cause: Temperature sensor AI1 warning (open circuit). Remedy:
|
| TS3A [Temp Sens AI3 Warn] | Cause: Temperature sensor AI3 warning (open circuit). Remedy:
|
| TS4A [Temp Sens AI4 Warn] | Cause: Temperature sensor AI4 warning (open circuit). Remedy:
|
| TS5A [Temp Sens AI5 Warn] | Cause: Temperature sensor AI5 warning (open circuit). Remedy:
|
| DCRW [DC Bus Ripple Warn] | Cause: DC Bus Ripple Warning. Remedy:
|
| AFFL [Fallback Channel] | Cause: Automatic fallback behavior activated after a fieldbus communication interruption. Remedy:
|
| IWA [MonitorCircuit A Warn] | Cause: Monitoring circuit A warning. Remedy:
|
| IWB [MonitorCircuit B Warn] | Cause: Monitoring circuit B warning. Remedy:
|
| IWC [MonitorCircuit C Warn] | Cause: Monitoring circuit C warning. Remedy:
|
| IWD [MonitorCircuit D Warn] | Cause: Monitoring circuit D warning. Remedy:
|
| LKON [ON Lock Warning] | Cause: ON lock warning resulting from an external device not ready. Remedy:
|
| INFM [Internal Error 22] | Cause: Internal error 22 (Embedded Ethernet). Remedy:
|
| RFTA [Pwr Backup Warn] | Cause: Power backup mode warning. Remedy:
|
| SLF1 [Modbus Com Inter.] | Cause: Modbus communication interruption warning. Remedy:
|
| AnF [Load slipping] | Cause: Not following the ramp. The difference between the output frequency and the speed feedback is not correct. Remedy:
|
| ASF [Angle error] | Cause: This error is triggered during the phase-shift angle measurement if the motor phase is disconnected or if the motor inductance is too high. Remedy:
|
| bLF [Brake Control] | Cause:
Remedy:
|
| bOF [Brake Resistor ovld] | Cause: The braking resistor is overloaded. Remedy:
|
| brF [Brake Feedback] | Cause:
Remedy:
|
| bSqF [Backlash Error] | Cause: The torque threshold used for backlash function cannot be reached after [BL Monit Delay] bqt. Remedy:
|
| bUF [DB unit sh. circuit] | Cause:
Remedy:
|
| bUFo [DB unit op. circuit] | Cause:
Remedy:
|
| CbF [Circuit Breaker Error] | Cause: The DC bus voltage level is not correct compared to the circuit breaker logic control after the configured timeout. Remedy:
|
| CFF [Incorrect Configuration] | Cause:
Remedy:
|
| CFi [Invalid Configuration] | Cause: Invalid configuration. The configuration loaded via tool or fieldbus is inconsistent. Remedy:
|
| CFi2 [Conf Transfer Error] | Cause:
Remedy:
|
| CFi3 [Pre-settings Transfer Error] | Cause: The configuration transfer to the drive was not successful or interrupted. Remedy:
|
| CFi4 [Empty Configuration] | Cause: The selected configuration for the [Multimotors config] has not been created previously. Remedy:
|
| CnF [Fieldbus Com Interrupt] | Cause: Communication interruption on fieldbus module. Remedy:
|
| CoF [CANopen Com Interrupt] | Cause: Communication interruption on the CANopen® fieldbus. Remedy:
|
| CrF1 [Precharge Capacitor] | Cause: Charging circuit control detected error or charging resistor damaged. Supply mains too low. Remedy:
|
| CSF [Channel Switch Error] | Cause: Switch to an invalid channel. Remedy:
|
| dCrE [DC Bus Ripple Error] | Cause: Persistent ripple observed on the DC bus or DC bus capacitors damaged. Remedy:
|
| dLF [Dynamic Load Error] | Cause: Load variation out of range. Remedy:
|
| ECF [Encoder Coupling] | Cause: The mechanical coupling of the encoder is broken. Detection active when [Encoder Coupling Monit] is Yes. Remedy:
|
| EEF1 [EEPROM Control] | Cause: An error of the internal memory of the control block has been detected. Remedy:
|
| EEF2 [EEPROM Power] | Cause: An error of the internal memory of the power board has been detected. Remedy:
|
| EnF [Encoder] | Cause: Encoder feedback error. Difference between measured and estimated speed is > 4%. Remedy:
|
| EPF1 [External Error] | Cause: Event triggered by an external device (depending on user settings) or Ethernet configuration file corrupted. Remedy:
|
| EPF2 [Fieldbus Error] | Cause: Event triggered by an external device, depending on user. Remedy:
|
| EtHF [Embd Eth Com Interrupt] | Cause: Communication interruption on the Ethernet IP ModbusTCP bus. Remedy:
|
| FCF1 [Out Contact Closed Error] | Cause: The output contactor remains closed although the opening conditions have been met. Remedy:
|
| FCF2 [Out Contact Opened Error] | Cause: The output contactor remains opened although the closing conditions have been met. Remedy:
|
| Fdr1 [FDR 1 Error] | Cause:
Remedy:
|
| Fdr2 [FDR 2 Error] | Cause:
Remedy:
|
| FWEr [Firmware Update Error] | Cause: Firmware update function has detected an error. Remedy:
|
| HCF [Boards Compatibility] | Cause: Hardware configuration error. [Pairing password] enabled and option module changed. Remedy:
|
| IFA [MonitorCircuit A Error] | Cause: The digital input assigned to [MonitorCircuit A Assign] is active for longer than delay. Remedy:
|
| IFb MonitorCircuit B Error | Cause: The digital input assigned to [MonitorCircuit B Assign] IFAb is active for longer than [MonitorCircuit B Delay] IFdb. Remedy:
|
| IFC MonitorCircuit C Error | Cause: The digital input assigned to [MonitorCircuit C Assign] IFAC is active for longer than [MonitorCircuit C Delay] IFdC. Remedy:
|
| IFd MonitorCircuit D Error | Cause: The digital input assigned to [MonitorCircuit D Assign] IFAd is active for longer than [MonitorCircuit D Delay] IFdd. Remedy:
|
| iHF Input Overheating | Cause: The AFE brick temperature is too high. Remedy:
|
| ILF Internal Link Error | Cause: Communication interruption between option module and the drive. Remedy:
|
| InF0 Internal Error 0 | Cause: Communication interruption between microprocessors of the control board, or the power board rating is not valid. Remedy:
|
| InF1 Internal Error 1 | Cause: The power board rating is not valid. Remedy:
|
| InF2 Internal Error 2 | Cause: The power board is incompatible with the control block software. Remedy:
|
| InF3 Internal Error 3 | Cause: Internal communication detected error. Remedy:
|
| InF4 Internal Error 4 | Cause: Internal data inconsistent. Remedy:
|
| InF6 Internal Error 6 | Cause:
Remedy:
|
| InF7 Internal Error 7 | Cause: Communication interruption with CPLD component of Control board. Remedy:
|
| InF8 Internal Error 8 | Cause: The internal power switching supply is not correct. Remedy:
|
| InF9 Internal Error 9 | Cause: An error on the current circuit measurement has been detected. Remedy:
|
| InFA Internal Error 10 | Cause: The input stage is not operating correctly. Remedy:
|
| InFb Internal Error 11 | Cause: The internal drive thermal sensor is not operating correctly. Remedy:
|
| InFC Internal Error 12 | Cause: Internal current supply error. Remedy:
|
| InFd Internal Error 13 | Cause: Differential current deviation. Remedy:
|
| InFE Internal Error 14 | Cause: Internal microprocessor detected error. Remedy:
|
| InFF Internal Error 15 | Cause: Serial memory flash format error. Remedy:
|
| InFG Internal Error 16 | Cause: Communication interruption or internal error of output relays option module. Remedy:
|
| InFH Internal Error 17 | Cause: Communication interruption with the Extension module of digital & analog I/O or internal error of the Extension module of digital & analog I/O. Remedy:
|
| InFi Internal Error 18 | Cause: Safety Module Internal Error (Communication interruption or internal error). Remedy:
|
| InFJ Internal Error 19 | Cause: An error on the encoder module has been detected. Remedy:
|
| InFk Internal Error 20 | Cause: Option module interface board error. Remedy:
|
| InFL Internal Error 21 | Cause: Internal Real Time Clock error. It could be a communication error between the keypad and the drive or a clock oscillator start error. Remedy:
|
| InFM Internal Error 22 | Cause: An error on the embedded Ethernet adapter has been detected. Remedy:
|
| InFP Internal Error 25 | Cause: Incompatibility between Control Board hardware version and firmware version. Remedy:
|
| InFr Internal Error 27 | Cause: Diagnostics in CPLD have detected an error. Remedy:
|
| LCF Input Contactor | Cause: The drive is not switched on even though [Mains V. time out] LCt timeout has elapsed. Remedy:
|
| LFF1 AI1 4-20mA loss | Cause: Loss of the 4-20 mA on analog input AI1. This error is triggered when the measured current is below 2 mA. Remedy:
|
| LFF3 AI3 4-20mA loss | Cause: Loss of the 4-20 mA on analog input AI3. This error is triggered when the measured current is below 2 mA. Remedy:
|
| LFF4 AI4 4-20mA loss | Cause: Loss of the 4-20 mA on analog input AI4. This error is triggered when the measured current is below 2 mA. Remedy:
|
| LFF5 AI5 4-20mA loss | Cause: Loss of the 4-20 mA on analog input AI5. This error is triggered when the measured current is below 2 mA. Remedy:
|
| LKon ON Lock Error | Cause: External device not ready. Remedy:
|
| MdCF Load Mvt Error | Cause: Load movement for which no command has been given. Remedy:
|
| MdLF [MultiDrive Link Error] | Cause:
Remedy:
|
| MSdF [M/S Device Error] | Cause:
Remedy:
|
| ObF [DC Bus Overvoltage] | Cause:
Remedy:
|
| OCF [Overcurrent] | Cause:
Remedy:
|
| OHF [Drive Overheating] | Cause: Drive temperature too high. Remedy:
|
| OLC [Process Overload] | Cause: Process overload. Remedy:
|
| OLF [Motor Overload] | Cause: Triggered by excessive motor current. Remedy:
|
| OPF1 [Single Output Phase Loss] | Cause: Loss of one phase at drive output. Remedy:
|
| OPF2 [Output Phase Loss] | Cause:
Remedy:
|
| OSF [Supply Mains Overvoltage] | Cause:
Remedy:
|
| PGLF [Program Loading Error] | Cause: Verify that the error code can be cleared. Remedy:
|
| PGrF [Program Running Error] | Cause: Verify that the error code can be cleared. Remedy:
|
| PHF [Input phase loss] | Cause:
Remedy:
|
| rAdF [Rotation Angle Monit] | Cause: The monitoring of the rotation angle has detected a too high deviation. Remedy:
|
| SAFF [Safety Function Error] | Cause:
Remedy:
|
| SAVF [Safety Violation] | Cause:
Remedy:
|
| SCF1 [Motor short circuit] | Cause: Short-circuit or grounding at the drive output. Remedy:
|
| SCF3 [Ground Short Circuit] | Cause: Significant ground leakage current at the drive output if several motors are connected in parallel. Remedy:
|
| SCF4 [IGBT Short Circuit] | Cause:
Remedy:
|
| SCF5 [Motor Short Circuit] | Cause: Short-circuit at drive output. Remedy:
|
| SCFF [Safety Config Error] | Cause:
Remedy:
|
| SLF1 [Modbus Com Interruption] | Cause: Communication interruption on the Modbus port. Remedy:
|
| SLF2 [PC Com Interruption] | Cause: Communication interruption with the commissioning software. Remedy:
|
| SLF3 [HMI Com Interruption] | Cause:
Remedy:
|
| SIOF [Safety IO Error] | Cause:
Remedy:
|
| SoF Motor Overspeed | Cause: Instability or driving load too high. If a downstream contactor is used, the contacts between the motor and the drive have not been closed before applying a Run command. The overspeed threshold (corresponding to 110% of [Max frequency] tFr) has been reached. Remedy:
|
| SPF Encoder Feedback Loss | Cause: This error is triggered if: The measured speed is lower than 2% of [Nominal Motor Freq] FrS; The difference between stator speed and measured speed is > 20% of FrS; EMC perturbations; No input signal; Encoder feedback missing; Supply voltage missing; Broken wire. Remedy:
|
| SPFC Security Files Corrupt | Cause: Security files corrupted or missing. Remedy:
|
| SrF Torque timeout | Cause: The torque control function is not able to regulate the torque within the configured dead band. The drive has switched to speed control for longer than [Torque ctrl time out] rto. Remedy:
|
| SSF Torque Limitation Error | Cause: The drive was in torque limitation or current limitation state during [Trq/I Limit Timeout] Sto. Remedy:
|
| StF Motor Stall Error | Cause: The stall monitoring function has detected an error. Triggered if: Output frequency is smaller than [Stall Frequency] StP3; Output current is higher than [Stall Current] StP2; Duration longer than [stall Max Time] StP1. Remedy:
|
| t1CF AI1 Thermal Sensor Error | Cause: The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI1: Open circuit or Short circuit. Remedy:
|
| t3CF AI3 Thermal Sensor Error | Cause: The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI3: Open circuit or Short circuit. Remedy:
|
| t4CF AI4 Thermal Sensor Error | Cause: The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI4: Open circuit or Short circuit. Remedy:
|
| t5CF AI5 Thermal Sensor Error | Cause: The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI5: Open circuit or Short circuit. Remedy:
|
| tECF Encoder Th Sensor Error | Cause: The thermal sensor monitoring function has detected a thermal sensor on the encoder module analog input: Open circuit or Short circuit. Remedy:
|
| tH1F AI1 Th Level Error | Cause: The thermal sensor monitoring function has detected a high temperature on analog input AI1. Remedy:
|
| tH3F AI3 Th Level Error | Cause: The thermal sensor monitoring function has detected a high temperature on analog input AI3. Remedy:
|
| tH4F AI4 Th Level Error | Cause: The thermal sensor monitoring function has detected a high temperature on analog input AI4. Remedy:
|
| tH5F AI5 Th Level Error | Cause: The thermal sensor monitoring function has detected a high temperature on analog input AI5. Remedy:
|
| tHEF Encoder Th Detected Error | Cause: The thermal sensor monitoring function has detected a high temperature on encoder module analog input. Remedy:
|
| tJF IGBT Overheating | Cause: Drive power stage overheating. Remedy:
|
| tLoF Drive Overload | Cause: The [Drive overload monit] obr - function has detected an error. Remedy:
|
| tnF Autotuning Error | Cause: Special motor or motor whose power is not suitable for the drive. Motor not connected to the drive. Motor not stopped. Remedy:
|
| ULF Process Underload | Cause: Process underload. Remedy:
|
| USF Supply Mains UnderV | Cause: Supply mains too low. Transient voltage dips. Remedy:
|
How to Clear & Reset Schneider ATV340 Drive Faults
- Keypad Reset: Press the red STOP/RESET button on the Graphic Display Terminal once the error condition is rectified. Ensure remote run commands (DI or fieldbus) are removed before resetting.
- Digital Input Reset (DI): If assigned in [Complete settings] > [Error/Warning handling] > [Fault reset] (parameter
rSF), send a 0-to-1 transition pulse to the designated digital input terminal (e.g., DI3 or DI4). - Embedded Web Server & SoMove PC Tool: Connect your PC via the onboard Ethernet RJ45 port or Modbus serial link, open SoMove or access the embedded Web server interface, and click “Fault Reset” in the monitoring status window.
- Fieldbus Control Word: Toggle Bit 7 (Fault Reset) from `0` to `1` in the drive Command Word (CMD) via embedded Ethernet/IP, Modbus TCP, Profinet, or CANopen networks.
- Mains Power Cycle: Switch off main AC supply line power. Wait until all display LEDs and indicators extinguish completely, and allow a minimum of 15 minutes for the internal DC bus capacitors to fully discharge before repowering.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that the intermediate DC bus voltage measures strictly below 42VDC across terminals [PA/+] and [PC/-] before removing terminal covers, inspecting motor cabling, or touching output terminals U, V, and W on the Schneider Altivar Machine ATV340 drive.