Schneider Lexium LXM15 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip error causes, and step-by-step troubleshooting procedures for the Schneider Electric Lexium 15 (LXM15 LP/MP/HP) servo drive series. Search or filter through the complete fault code directory below.
Power Range
0.5 – 33 kW (0.7 – 45 HP)
Supply Voltage
200–240V / 208–480V (1/3-Phase)
Control Modes
Position, Speed & Torque Control
Operator Interface
2-Digit Display & Uni-Link PC Tool
Complete Schneider Lexium LXM15 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type F01, F02, F06, or Overvoltage).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| F01*Heat sink temperature | Cause: The heat sink temperature is too high; the limit is set by the manufacturer to 80°C. Remedy: Check drive cooling, fan operation, and cabinet ventilation. |
| F02*Overvoltage | Cause: Overvoltage in the DC-link circuit; the limit depends on the mains supply voltage. Remedy: Check mains supply voltage and braking resistor. |
| F03*Following error | Cause: Message from the position controller. Remedy: Check control loop settings and mechanical movement. |
| F04Feedback | Cause: Cable break, short-circuit, short to ground. Remedy: Check feedback cables and connectors. |
| F05*Undervoltage | Cause: Undervoltage in DC-link; the limit is set by the manufacturer to 100V. Remedy: Check mains supply voltage. |
| F06Motor temperature | Cause: Temperature sensor faulty or motor temperature too high; the limit is set by the manufacturer to 145°C. Remedy: Check motor load, cooling, and temperature sensor wiring. |
| F07Auxiliary voltage | Cause: Internal auxiliary voltage not OK. Remedy: Internal device error; check power supply or contact service. |
| F08*Overspeed | Cause: Motor running away; the speed is higher than permitted. Remedy: Check velocity loop parameters and motor connections. |
| F09EEPROM | Cause: Checksum error. Remedy: Reset device; if error persists, replace unit. |
| F11Brake | Cause: Cable break, short-circuit, short to ground. Remedy: Check brake cabling and connections. |
| F12Motor phase | Cause: Motor phase missing (cable break or similar). Remedy: Check motor power cables and connections. |
| F13*Internal temperature | Cause: Ambient temperature in the drive too high. Remedy: Check cabinet ventilation and ambient temperature. |
| F14Output stage | Cause: Fault in the power output stage: earth short circuit of the motor, short circuit of motor phase or regenerative resistor. Remedy: Check motor isolation, cabling, and regenerative resistor. |
| F15I²t max. | Cause: I²t max. value exceeded. Remedy: Check motor sizing and load cycle (duty cycle). |
| F16*Mains R1A/R1C | Cause: 2 or 3 supply phases missing. Remedy: Check mains supply phases and fuses. |
| F17A/D converter | Cause: Error in the analog-digital conversion. Remedy: Internal error; switch off/on. If persistent, replace unit. |
| F18Regen | Cause: Regen circuit faulty or incorrect setting. Remedy: Check regenerative resistor hardware and software settings. |
| F19*Main phase | Cause: A main supply phase is missing (can be switched off for 2-phase operation). Remedy: Check supply phases or configuration for 2-phase operation. |
| F20Slot error | Cause: Hardware error on the expansion card. Remedy: Check expansion card installation or replace card. |
| F21Profibus handling error | Cause: OPMODE error on the Profibus expansion card. Remedy: Check Profibus configuration and mode settings. |
| F22Short circuit to earth | Cause: 40/70 amps types only: short circuit to earth. Remedy: Check for ground faults in motor or cabling. |
| F23CAN bus off | Cause: CAN bus total communication error. Remedy: Check CAN bus wiring, termination, and baud rate. |
| F24Warning | Cause: Error warning display. Remedy: Check active warnings (n-codes). |
| F25Commutation error | Cause: Commutation error (Motor run away). Remedy: Check motor phasing and encoder alignment. |
| F26Limit switch | Cause: Homing error (limit-switch reached). Remedy: Check limit switch position and homing routine. |
| F27PWR-Option | Cause: Operating error for PWR-option. Remedy: Check power option card settings. |
| F29Slot card error | Cause: Slot card error. Remedy: Re-seat slot card or replace. |
| F30Sercos Emerg. Timeout | Cause: Sercos emergency timeout. Remedy: Check Sercos fiber optics and timing parameters. |
| F31Wrong Firmware-version | Cause: Wrong version of Firmware. Remedy: Update firmware to correct version. |
| F32System fault | Cause: The software does not respond correctly. Remedy: Cycle power; if persistent, replace drive. |
| n01I²t | Cause: Threshold I²t exceeded. Remedy: Reduce motor load. |
| n02Regen power | Cause: Preset regen power reached. Remedy: Check deceleration ramp or install external resistor. |
| n03*S_fault | Cause: Exceeded preset following/contouring error window. Remedy: Check PID tuning and mechanical stiffness. |
| n04*Node guarding | Cause: Response monitoring (fieldbus) is active. Remedy: Check fieldbus connection. |
| n05Mains phase missing | Cause: Line phase missing. Remedy: Check mains supply wiring. |
| n06*Sw limit- switch 1 | Cause: Passed software limit-switch SWE1. Remedy: Move axis back within limits. |
| n07*Sw limit- switch 2 | Cause: Passed software limit-switch SWE2. Remedy: Move axis back within limits. |
| n08Motion task error | Cause: A faulty motion task was started. Remedy: Check motion programming sequence. |
| n09No reference point | Cause: No reference point set at start of task. Remedy: Perform homing procedure. |
| n10*PSTOP | Cause: PSTOP limit-switch active. Remedy: Check Positive Stop limit switch. |
| n11*NSTOP | Cause: NSTOP limit-switch active. Remedy: Check Negative Stop limit switch. |
| n12Default values | Cause: only HIPERFACE®: Motor default values were loaded. Remedy: Confirm motor parameters. |
| n13*I/O Expansion card | Cause: Expansion card not properly supplied. Remedy: Check expansion card power supply. |
| n14SinCos | Cause: SinCos communication is not determined. Remedy: Check encoder communication. |
| n15VCT Error | Cause: Wrong VCT entry started. Remedy: Check Velocity Cam Table entry. |
| n16Warning sums | Cause: One or more of warnings n17..n31 active. Remedy: Check other active warning codes. |
| n17Can sync | Cause: Can sync locked. Remedy: Check CAN bus synchronization. |
| n18Abs encoder overrun | Cause: Multiturn encoder overrun. Remedy: Re-reference/Home the absolute encoder. |
| n32Beta version | Cause: Firmware beta version. Remedy: Informational; update to official release if required. |
How to Clear & Reset Schneider Lexium LXM15 Drive Faults
- Front Display / Reset Button: Press the front navigation / reset key on the drive faceplate once the cause of the fault has been rectified. Ensure the hardware ENABLE signal is deactivated before initiating a reset.
- Digital Input Reset (DI): If configured in the I/O assignment parameters (e.g., mapped to function
FAULT_RESET), apply a 24VDC logic high pulse to the assigned digital input terminal. - Uni-Link / PowerSuite PC Tool: Connect your PC via the RS232 serial commissioning port, open the Lexium 15 diagnostic interface, and click “Clear Fault” / “Fault Reset” in the monitoring status panel.
- Fieldbus Control Word: Send a reset command by toggling the Fault Acknowledge bit in the control word via CANopen, SERCOS, or Profibus DP communication modules.
- Mains Line Power Cycle: Disconnect AC mains supply voltage to terminals R/L1, S/L2, T/L3. Wait until the 2-digit 7-segment display turns completely dark and allow at least 5 to 10 minutes for internal DC link capacitors to discharge safely before repowering.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 40VDC across terminals [PA/+] and [PC/-] before servicing terminal connections, inspecting motor leads, or touching terminals U, V, and W on the Schneider Lexium LXM15 drive.